18BXE MSYSTEM | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 6
Technical content
MODEL: 18BXE http://www.m-system.co.jp/ 18BXE SPECIFICATIONS ES-1806 Rev.9 Page 1/6 Rack-mounted DCS Signal Conditioners 18-RACK STANDARD RACK Functions & Features
- Standard 19" rack for 18-RACK signal conditioners
- Line power supplied via the rear rack bus
- Dual-redundant power supply or two independent power sources selectable with AC power supply
- Direct interface to various DCS with the rack connector MODEL: 18BXE–[1]-[2][3]
ORDERING INFORMATION
- Code number: 18BXE-[1]-[2][3] Specify a code from below for each [1] through [3]. (e.g. 18BXE-Y0-K2/M) [1] CONNECTOR 0: None U1: Fujitsu FCN type I/O connector Y0: Yokogawa DCS connector N1: Nippon Shokubai DCS connector K1: Azbil DCS AI connector K2: Azbil DCS AO connector K3: Azbil DCS AI connector (ELCO connector) K4: Azbil DCS AO connector (ELCO connector) E1: Toshiba DCS SAMP1 card use E2: Toshiba DCS SAOP1 card use E3: Toshiba DCS SAIN1 card use (Panasonic AXM220001 used) (DISCONTINUED; replace with code "E3A".) E3A: Toshiba DCS SAIN1 card supported (Omron XG4A-2031 used) M-System guarantees the connecting section. [2] POWER SUPPLY UNIT AC Power K: 85 – 132 V AC; single power source (Operational voltage range 85 – 132 V, 47 – 63 Hz) K2: 85 – 132 V AC; dual-redundant power supply (Operational voltage range 85 – 132 V, 47 – 63 Hz) KK: 85 – 132 V AC; two independent power sources (Operational voltage range 85 – 132 V, 47 – 63 Hz) L: 170 – 264 V AC; single power source (Operational voltage range 170 – 264 V, 47 – 63 Hz) L2: 170 – 264 V AC; dual-redundant power supply (Operational voltage range 170 – 264 V, 47 - 63 Hz) DC Power R: 24 V DC; no power supply unit (Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) AC/DC Power KR: 85 – 132 V AC / 24 V DC; two independent power sources (85 – 132 V, 47 – 63 Hz or 24V ±10 %, ripple 10 %p-p max.) (Redundant or independent power sources are recommended for long time use without interruption.) [3] OPTIONS Mounting Bracket blank: Rack mounting, standard /M: Center mounting /W: Surface mounting
RELATED PRODUCTS
- Blank filler plate (model: P-181)
- Connector terminal block (model: CNT)
- Special cable with 40-pin connector (model: FCN) GENERAL SPECIFICATIONS Construction: Metal plates assembly Coating: Colored Zn-Cr Capacity: 16 positions Connection Power input: M4 screw terminals (torque 0.8 N·m) Power alarm output: M4 screw terminals (torque 0.8 N·m) Screw terminal: Nickel-plated brass Power alarm output: N.C. contact turns off at power failure or failure of power units. Supplied only with dual-redundant power supply or two independent power sources Power RUN LED: Light turns on in normal conditions (supplied only with dual-redundant power supply or two independent power sources) OUTPUT SPECIFICATIONS ■ Alarm Output Rated load: 250 V AC @ 3 A (cos ø = 1)
30 V DC @ 3 A (resistive load)
Maximum switching voltage: 250 V AC, 30 V DC Maximum switching power: 750 VA, 90 W Minimum load: 5 V DC @ 10 mA Mechanical life: ≥ 5 × 107 cycles
MODEL: 18BXE http://www.m-system.co.jp/ 18BXE SPECIFICATIONS ES-1806 Rev.9 Page 2/6 INSTALLATION Power consumption
- AC: 130 VA min.
- DC: 2.5 A min. Operating temperature: -5 to +55°C (23 to 131°F) 0 to 50°C (32 to 122°F) for AC power Operating humidity: 30 to 90 %RH (non-condensing) Mounting: JIS or EIA standard rack or surface Weight Single power supply w/o power units: 3.5 kg (7.7 lb) with DC power type 4.0 kg (8.8 lb) with AC power type Dual-redundant or two independent power sources: 4.0 kg (8.8 lb) with AC/DC power type 4.5 kg (9.9 lb) with AC/AC power type PERFORMANCE Insulation resistance: ≥ 100 MΩ with 500 V DC (I/O connector to power to FG) Dielectric strength: 500 V AC @ 1 minute (I/O connector to power)
1500 V AC @ 1 minute (power to FG)
500 V AC @ 1 minute (1000 V for 24 V DC)
(I/O connector to FG) MOUNTING REQUIREMENTS 101.6 (4.00) * 450 (17.72) 465 (18.31) 4–M5 SCREW ANGLE BRACKET Observe an appropriate wiring space over and below. 100 (3.94) for JIS standard
MODEL: 18BXE http://www.m-system.co.jp/ 18BXE SPECIFICATIONS ES-1806 Rev.9 Page 3/6 CONNECTION DIAGRAM PWR1 PWR2 COM. PWR2 ALM. OUTPUT PWR1 ALM. OUTPUT FG ■ Single Power Source, Dual-redundant Power Supply ■ Two Independent Power Sources, DC/AC Power Supply ■ Two Independent Power Sources, AC/AC Power Supply U V AC POWER 1CN1 CN2 CN3 CN4 U V AC POWER PWR1 COM. DC POWER ALM. OUTPUT PWR1 ALM. OUTPUT FG U V AC POWER 1 + DC POWER COM. PWR2 ALM. OUTPUT PWR1 ALM. OUTPUT FG U(+) V(–) POWER *Alarm output not provided for single power supply. CN1 CN2 CN3 CN4 CN1 CN2 CN3 CN4 Note 1: CN1 through CN4 are not available without connector. Note 2: CN2 is available with Y okogawa, Y amatake and Toshiba for DCS type. Note 3: CN3 is available with Y okogawa and Toshiba for DCS type. Note 4: CN4 is available with Toshiba for DCS type. DIMENSIONS unit: mm (inch) 153 (6.02) 465 (18.31) 480 (18.90) 435 (17.13) 8.5 (.33) 3–M4 POWER TERMINAL ■ RACK (standard) * PWR1 only for AC single power supply. Alarm output provided only for dual-redundant power supply or two independent power sources. 1 3 15 6 14 12 1 3 5 7 9 11 13 15 2 4 6 8 10 12 14 16 PWR2 1 2 3 4 5 4 5 6 PWR1 1 2 3 4 5 5–M4 POWER UNIT TERMINAL 3–M4 ALARM OUTPUT TERMINAL POWER UNIT *POWER LED ** CONNECTORS 100 (3.94) 2 (.08) ■ CENTER (option /M) 86 (3.39) 186 (7.32) ■ SURFACE (option /W)
MODEL: 18BXE http://www.m-system.co.jp/ 18BXE SPECIFICATIONS ES-1806 Rev.9 Page 4/6 I/O CONNECTOR PIN ASSIGNMENT PIN NO. ASSIGNMENT PIN NO. ASSIGNMENT A 1 ch. 1 + B 1 ch. 1 – A 2 ch. 2 + B 2 ch. 2 – A 3 ch. 3 + B 3 ch. 3 – A 4 ch. 4 + B 4 ch. 4 – A 5 ch. 5 + B 5 ch. 5 – A 6 ch. 6 + B 6 ch. 6 – A 7 ch. 7 + B 7 ch. 7 – A 8 ch. 8 + B 8 ch. 8 – A 9 ch. 9 + B 9 ch. 9 – A10 ch.10 + B10 ch.10 – A11 ch.11 + B11 ch.11 – A12 ch.12 + B12 ch.12 – A13 ch.13 + B13 ch.13 – A14 ch.14 + B14 ch.14 – A15 ch.15 + B15 ch.15 – A16 ch.16 + B16 ch.16 – A17 – A20, B17 – B20: Unused CN1: FCN-364P040-AU
- Fujitsu FCN type I/O connector Connector pin assignment The input or output 1 is connected to the connector. 18-RACK LOCATION NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 VM1/PM1/VM4 CARD INPUT or OUTPUT CN3 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 VM2 CARD INPUT NO. VM2 CARD OUTPUT NO.
3 N C3 N C
1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 i o i o i o i o i o i o i o i o MAC2/PAC CARD I/O (i = input, o = output) CN1, CN2
- Yokogawa DCS connector Location I/O connector : PS-40PE-D4T1-PN1 CN1 : MAC2 / PAC card use* CN2 : MAC2 / PAC card use* for redundancy CN3 : VM ❑ / PM1 card use** The input or output 1 is connected to the connector. *MAC2 card (uses KS1 cable) I/O card used for control I/O. Composed of 8 inputs and 8 outputs. Input and output are paired. (Replace with pulse inputs for PAC card.) **VM❑ / PM1 card (uses KS2 cable) VM1: analog input 16 points VM2: analog input 8 points / analog output 8 points VM4: analog output 16 points PM1: pulse input 16 points PIN NO. ASSIGNMENT PIN NO. ASSIGNMENT 1 No Connection 19 ch. 8 – 2 No Connection 20 ch. 8 + 3 ch.16 – 21 ch. 7 – 4 ch.16 + 22 ch. 7 + 5 ch.15 – 23 ch. 6 – 6 ch.15 + 24 ch. 6 + 7 ch.14 – 25 ch. 5 – 8 ch.14 + 26 ch. 5 + 9 ch.13 – 27 ch. 4 – 10 ch.13 + 28 ch. 4 + 11 ch.12 – 29 ch. 3 – 12 ch.12 + 30 ch. 3 + 13 ch.11 – 31 ch. 2 – 14 ch.11 + 32 ch. 2 + 15 ch.10 – 33 ch. 1 – 16 ch.10 + 34 ch. 1 + 17 ch. 9 – 18 ch. 9 + 18-RACK LOCATION NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 NIPPON SHOKUBAI DCS LOCATION NO.
- Nippon Shokubai DCS connector Location CN1 : HIF3F-34PA-2.54DSA The input or output 1 is connected to the connector. Connector Pin Assignment
- Azbil DCS AI connector I/O cable : J-RSL / J-RSK J-RRL / J-RRK Location Input connector : 57GE-40500-751 CN1, CN2 : J-HAM50 / J-HMM00 module use The output 1 is connected to the connector. The CN1 and CN2 are connected in parallel. 18-RACK LOCATION NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 AZBIL DCS AI CONNECTOR
MODEL: 18BXE http://www.m-system.co.jp/ 18BXE SPECIFICATIONS ES-1806 Rev.9 Page 5/6 18-RACK LOCATION NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 AZBIL DCS AO CONNECTOR
- Azbil DCS AO connector I/O cable : J-RSL / J-RSK J-RRL / J-RRK Location Output connector : 57GE-40500-751 CN1, CN2 : J-AOM10 module use The input is connected to the connector. The CN1 and CN2 are connected in parallel. Install the Extender Module (model: 18BW) to unused channels in order to close the circuit.
- Azbil DCS AI connector I/O cable : J-SSL / J-SSK J-SRL / J-SRK Location Input connector : 00-8016-056-296-707V CN1, CN2 : J-HAM50 / J-HMM00 module use The output 1 is connected to the connector. The CN1 and CN2 are connected in parallel. 18-RACK LOCATION NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 AZBIL DCS AI CONNECTOR 18-RACK LOCATION NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 AZBIL DCS AO CONNECTOR I/O cable : J-SSL / J-SSK J-SRL / J-SRK Location Output connector : 00-8016-056-296-707V CN1, CN2 : J-AOM10 module use The input is connected to the connector. The CN1 and CN2 are connected in parallel. Install the Extender Module (model: 18BW) to unused channels in order to close the circuit.
- Azbil DCS AO connector Location Output connector : HIF3CA-40PA-2.54DSA (11) CN1, CN2 : SAMP1 CN3, CN4 : SAMP1 for redundancy The output 1 is connected to the connector. 18-RACK LOCATION NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 CN1, CN3 CN2, CN4 SAMP1 INPUT POINT NO.
- Toshiba DCS SAMP1 card use Location Input connector : HIF3CA-40PA-2.54DSA (11) CN1, CN2 : SAOP1 CN3, CN4 : SAOP1 for redundancy The input is connected to the connector. 18-RACK LOCATION NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 CN1, CN3 CN2, CN4 SAOP1 OUTPUT POINT NO.
- Toshiba DCS SAOP1 card use Location Input connector : Omron XG4A-2031 The output 1 is connected to the connector. 18-RACK LOCATION NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 CN1, CN2 CN3, CN4 SAIN1 INPUT POINT NO. Toshiba DCS SAMP1 uses Panasonic AXM220001. As connector is discontinued, Omron XG4A-2031 is used as an alternative. (Replace cable side.) CN1 : SAIN1 (ch.1 – ch.8) CN2 : SAIN1 (ch.1 – ch.8) for redundancy CN3 : SAIN1 (ch.9 – ch.16) CN4 : SAIN1 (ch.9 – ch.16) for redundancy
- Toshiba DCS SAIN1 card use
MODEL: 18BXE http://www.m-system.co.jp/ 18BXE SPECIFICATIONS ES-1806 Rev.9 Page 6/6 Specifications are subject to change without notice.