1646469 PHOENIX | Alldatasheet

Document overview

  • Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
  • PDF pages: 10

Technical content

Please be informed that the data shown in this PDF document is generated from our online catalog. Please find the complete data in the user documentation. Our general terms of use for downloads are valid. Controller (SPS), PLCnext Control; Programming: High-level language and IEC 61131-3; Operating system: Yocto/Linux® (real-time); Programming tool: PLCnext Engineer, Eclipse®, Visual Studio®, MATLAB®/ Simulink®; IoT connection: PROFICLOUD and every cloud via cloud connectors; Development process certified in accordance with IEC 62443-4-1; Processor: Arm® Cortex®-A55, 2x 1.7 GHz. Product description The PLCnext Control AXC F 1252 for the Axioline I/O system is fast, robust, and easy to use. This means it is consistently designed for maximum performance, easy handling, and use in harsh industrial environments. Your advantages Real-time-capable Linux operating system for deterministic and reliable execution of time-critical processes• Supports numerous protocols such as: HTTP, HTTPS, FTP, OPC UA, SNTP, SNMP, SMTP, SQL, MySQL, DCP, etc. – for smooth communication with IT systems Direct connection to the Proficloud, the PLCnext Store and any cloud platforms – for seamless IoT integration of your applications Support for numerous fieldbus protocols (PROFINET, Modbus TCP/RTU, Ethernet/IP, etc.) for easy integration into existing automation technology systems and installations Maximum design freedom thanks to the combination of classic PLC programming with modern high-level languages such as C++, C#, or Python Meets the highest security requirements of industrial automation – for the protection of your applications and data Commercial data Item number 1646469 Packing unit 1 pc Minimum order quantity 1 pc Product key DRADAI GTIN 4067923176423 Weight per piece (including packing) 170.2 g Weight per piece (excluding packing) 137 g Customs tariff number 85371091 Country of origin DE AXC F 1252 - Controller 1646469 https://www.phoenixcontact.com/pc/products/1646469 Jul 13, 2026, 12:21AM Page 1 (10)

Product family PLCnext Control Type modular Special properties Development process certified in accordance with IEC 62443-4-1 Insulation characteristics Protection class III (IEC 61140, EN 61140, VDE 0140-1) Overvoltage category II (IEC 60664-1, EN 60664-1) Pollution degree 2 (IEC 60664-1, EN 60664-1) System properties Trusted Platform Module TPM 2.0 Flash memory 1.1 GByte (internal flash memory) Retentive data storage 16 kByte RAM 1024 Mbyte IoT capability: PROFICLOUDIoT capability: PROFICLOUD IoT platform PROFICLOUD Supports cloud computing yes IoT capability: PROFICLOUDIoT capability: PROFICLOUD IoT platform PROFICLOUD Supports cloud computing yes IEC 61131 runtime system Program memory 8 Mbyte Data storage system 12 Mbyte Axioline max. 1482 Byte (per station (total input and output data)) max. 1024 Byte (Axioline F local bus (input)) Amount of process data max. 1024 Byte (Axioline F local bus (output)) Number of supported devices max. 63 (per station) Number of local bus devices that can be connected max. 63 (observe current consumption) INTERBUS-Master Amount of process data (Axioline input/output data max.) max. 1482 Byte (per station (total input and output data)) Amount of process data (Axioline input data max.) max. 1024 Byte (Axioline F local bus (input)) Amount of process data (Axioline output data max.) max. 1024 Byte (Axioline F local bus (output)) PROFINET Device function PROFINET controller, PROFINET device min. 8 ms (4 devices)Update rate AXC F 1252 - Controller 1646469 https://www.phoenixcontact.com/pc/products/1646469 Jul 13, 2026, 12:21AM Page 2 (10)

min. 32 ms (16 devices) Process data width 2 Byte ... 512 Byte (PROFINET device) Conformance Class B Device ID 0193hex Vendor ID 00B0hex Function Industrial cybersecurity yes Programming data Register length (master) 1482 Byte Functionality Symbolic flowchart (SFC) Ladder diagram (LD) Function block diagram (FBD) Structured text (ST) C++ Java Python® Programming languages supported Simulink® System requirements Application interface OPC UA® Electrical properties Maximum power dissipation for nominal condition 3.2 W (3.2 W = 13.2 W - 10.0 W) Real-time clock Realtime clock yes (not buffered) Potentials: Communications power UL feed-in (the supply of the Axioline F local bus UBus is generated from UL) Supply voltage 24 V DC Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple (± 5 %)) Current draw max. 640 mA (with 2 A at UBus for the I/Os and UL = 19.2 V) Current consumption typ. 63 mA (without I/Os and UL = 24 V) Power consumption max. 13.2 W (with 2 A at UBus for the I/Os and UL = 24 V) Protective circuit Reverse polarity protection; electronic Potentials: Axioline F local bus supply (UBus) Supply voltage 5 V DC (via bus base module) Power supply unit 2 A Connection data Supply of the logic voltage UL AXC F 1252 - Controller 1646469 https://www.phoenixcontact.com/pc/products/1646469 Jul 13, 2026, 12:21AM Page 3 (10)

Connection method Push-in connection Conductor cross-section AWG 24 ... 16 Stripping length 10 mm Interfaces HTTP (only for access to the recovery system) HTTPS PROFINET INTERBUS (via the extension module AXC F IL ADAPT) Modbus/TCP Modbus/RTU (via corresponding library) CANopen® (via corresponding library) DALI (via corresponding library) DALI-2 (via corresponding app) HART (via corresponding library) IO-Link® (via corresponding library) MQTT (via corresponding app) OPC UA® Server OPC UA® Client (License required) DHCP (via corresponding library) SFTP SMTP (via corresponding library) SNTP (via corresponding library) SNMP (via corresponding library) DNS (via corresponding library) DNP3 (via corresponding library) IEC 60870-5-1 (via corresponding library) IEC 60870-5-104 (via corresponding library) IPsec Supported protocols syslog Web server yes Axioline F local bus Number of interfaces 1 Connection method integrated bus socket Transmission speed 100 Mbps Ethernet Bus system RJ45 AXC F 1252 - Controller 1646469 https://www.phoenixcontact.com/pc/products/1646469 Jul 13, 2026, 12:21AM Page 4 (10)

Connection method RJ45 jack Note on the connection method Auto negotiation and autocrossing Transmission speed 10/100 Mbps (full duplex) Transmission physics Ethernet in RJ45 twisted pair Transmission length max. 100 m Dimensions Dimensional drawing Width 45 mm Height 122 mm Depth 75 mm Note on dimensions The depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715). Material specifications Color (Housing) gray (RAL 7042) Environmental and real-life conditions Ambient conditions Degree of protection IP20 -25 °C ... 60 °C up to 2000 m above mean sea levelAmbient temperature (operation) Operating altitude > 2000 m above mean sea level: Observe temperature derating Ambient temperature (storage/transport) -40 °C ... 85 °C Permissible humidity (operation) 5 % ... 95 % (according to DIN EN 61131-2) Permissible humidity (storage/transport) 5 % ... 95 % (according to DIN EN 61131-2) Shock (operation) 30g (IEC 60068-2-27) Vibration (operation) 5g (IEC 60068-2-6) Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level) Air pressure (storage/transport) 58 kPa ... 106 kPa (up to 4500 m above mean sea level) Approvals UL, USA/Canada Identification cULus Certificate E238705 AXC F 1252 - Controller 1646469 https://www.phoenixcontact.com/pc/products/1646469 Jul 13, 2026, 12:21AM Page 5 (10)

Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU Immunity test in accordance with EN IEC 61000-6-2 Electrostatic discharge (ESD)IEC 61000-4-2 Criterion B, ±6 kV contact discharge, ±8 kV air discharge Immunity test in accordance with EN IEC 61000-6-2 Electromagnetic fieldsIEC 61000-4-3 Criterion A, Field intensity:

10 V/m

Immunity test in accordance with EN IEC 61000-6-2 Fast transients (burst)IEC 61000-4-4 Criterion B, ±2 kV Immunity test in accordance with EN IEC 61000-6-2 Transient overvoltage (surge)IEC 61000-4-5 Criterion B; DC supply lines: ±0.5 kV/±1.0 kV (symmetrical/asymmetrical), fieldbus cable shielding: ±1.0 kV Immunity test in accordance with EN IEC 61000-6-2 Conducted interferenceIEC 61000-4-6 Criterion A, Test voltage 10 V Conformance with EMC directives Noise emission test in accordance with EN IEC 61000-6-3 Class B Mounting Mounting type DIN rail mounting AXC F 1252 - Controller 1646469 https://www.phoenixcontact.com/pc/products/1646469 Jul 13, 2026, 12:21AM Page 6 (10)

https://www.phoenixcontact.com/pc/products/1646469 Jul 13, 2026, 12:21AM Page 7 (10)

To download certificates, visit the product detail page: https://www.phoenixcontact.com/pc/products/1646469  cULus Listed Approval ID: E238705 AXC F 1252 - Controller 1646469 https://www.phoenixcontact.com/pc/products/1646469 Jul 13, 2026, 12:21AM Page 8 (10)

ECLASS-13.0 27242207 ECLASS-15.0 27242207 AXC F 1252 - Controller 1646469 https://www.phoenixcontact.com/pc/products/1646469 Jul 13, 2026, 12:21AM Page 9 (10)

Environmental product compliance EU RoHS Fulfills EU RoHS substance requirements Yes Exemption 6(c), 7(a), 7(c)-I China RoHS EFUP-50Environment friendly use period (EFUP) An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required. EU REACH SVHC Diboron trioxide(CAS: 1303-86-2)REACH candidate substance (CAS No.) Lead(CAS: 7439-92-1) Phoenix Contact 2026 © - all rights reserved https://www.phoenixcontact.com PHOENIX CONTACT GmbH & Co. KG Flachsmarktstraße 8 D-32825 Blomberg +49 (0) 5235-3 00 info@phoenixcontact.com AXC F 1252 - Controller 1646469 https://www.phoenixcontact.com/pc/products/1646469 Jul 13, 2026, 12:21AM Page 10 (10)