1496723 PHOENIX | Alldatasheet

Document overview

  • Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
  • PDF pages: 8

Technical content

Please be informed that the data shown in this PDF document is generated from our online catalog. Please find the complete data in the user documentation. Our general terms of use for downloads are valid. Contact insert, number of positions: 2+PE, size: D7, power contacts: 2, number of connections per position: 1, Pin, Axial screw connection, 400 V, 40 A, 1.5 mm2 ... 10 mm2, application: Power Your advantages Shock and vibration-resistant in accordance with DIN EN 61373• Commercial data Item number 1496723 Packing unit 1 pc Minimum order quantity 1 pc Sales key BF61 Product key BF7ABJ GTIN 4063151946180 Weight per piece (including packing) 23.3 g Weight per piece (excluding packing) 22.22 g Customs tariff number 85366990 Country of origin PL HC-Q02-I-AT-M - Contact insert 1496723 https://www.phoenixcontact.com/us/products/1496723 Oct 31, 2024, 6:52 AM Page 1 (8)

General Connectors may be operated only when there is no load/voltage. General The axial screw connection must be established using a 2 mm Allen key (for stranded conductors only) Mounting To ensure correct use, installation in housing with IP54 protection or better is required Assembly note Note regarding axial connection technology: Only for stranded wires. The specified conductor cross sections refer to the geometric cross section of the cable used. Cables with a geometric cross section which deviates significantly from the nominal cable cross section must be checked before use. The axial connection technology connection space is designed for fine strand cables according to VDE 0295 Class 5. Deviating cable structures (e.g., Class 6 cables) must be checked before use. Assembly instructions Before assembly, ensure that the tapered screw is fully loosened (chamber is open). Cables must not be twisted. The wires must be pushed into the contact chamber as far as they will go (until the insulation touches the contact). Hold the wires in position and tighten using an Allen key. The used wire end must be cut off before reconnection. The terminal screw must only be retightened once to prevent the litz wires from breaking. To prevent damage to the contact, the wire/cable must be mechanically held at an appropriate distance from the connection point (e.g., when used in a plate cut out). For notes on correct execution, see DIN VDE 0100-520:2003-06. Unused connections must be tightened with maximum torque. Hexagonal socket SW2,0 Product properties Product type Contact insert with a fixed no. of positions Series HC-Q Application Power Type D7 Number of positions 2 Connection profile 2+PE Number of connections per position 1 No. of power contacts 2 Contact material type turned Data management status Article revision 01 Insulation characteristics HC-Q02-I-AT-M - Contact insert 1496723 https://www.phoenixcontact.com/us/products/1496723 Oct 31, 2024, 6:52 AM Page 2 (8)

Mechanical characteristics Contact diameter 4 mm Connection data Connection technology Connection technology Axial screw connection Number of connections per position 1 Connection in acc. with standard IEC / EN Conductor connection Conductor cross section 1.5 mm² ... 10 mm² (The cross section specification refers to the geometric cross section of the cable used) HEAVYCON housing) 0.5 Nm (1.5 mm²) Tightening torque 1.5 Nm (6 mm² ... 10 mm²) Stripping length of the individual wire 6 mm Stripping length 5 mm ... 7 mm Electrical properties Rated voltage (III/3) 400 V Rated surge voltage 6 kV Rated current 40 A Mechanical properties Mechanical data Insertion/withdrawal cycles ≥ 500 Material specifications Flammability rating according to UL 94 V0 Seal material NBR Contact material Copper alloy Contact surface material Ag Contact carrier material PC Standards/regulations PC: Fire protection in rail vehicles - requirement sets R22, R23, and R24 acc. to DIN EN 45545-2 (Risk level HL1 - HL3) Environmental and real-life conditions Ambient conditions HC-Q02-I-AT-M - Contact insert 1496723 https://www.phoenixcontact.com/us/products/1496723 Oct 31, 2024, 6:52 AM Page 3 (8)

Ambient temperature (operation) -40 °C ... 125 °C (including heating up of contacts) Standards and regulations Testing Standards/regulations PC: Fire protection in rail vehicles - requirement sets R22, R23, and R24 acc. to DIN EN 45545-2 (Risk level HL1 - HL3) HC-Q02-I-AT-M - Contact insert 1496723 https://www.phoenixcontact.com/us/products/1496723 Oct 31, 2024, 6:52 AM Page 4 (8)

23,6 38 Male insert Schematic diagram Connector pin assignment HC-Q02-I-AT-M - Contact insert 1496723 https://www.phoenixcontact.com/us/products/1496723 Oct 31, 2024, 6:52 AM Page 5 (8)

0 10 20 30 40 50 60 70 80 90 100 110 120 130 I [A]  [°C] = 10,0 mm = 6,0 mm = 4,0 mm Derating diagram HC-Q02-I-AT-M - Contact insert 1496723 https://www.phoenixcontact.com/us/products/1496723 Oct 31, 2024, 6:52 AM Page 6 (8)

ECLASS-11.0 27440205 ECLASS-12.0 27440205 ECLASS-13.0 27440205 ETIM ETIM 9.0 EC000438 HC-Q02-I-AT-M - Contact insert 1496723 https://www.phoenixcontact.com/us/products/1496723 Oct 31, 2024, 6:52 AM Page 7 (8)

Environmental product compliance EU RoHS Fulfills EU RoHS substance requirements Yes, No exemptions China RoHS EFUP-EEnvironment friendly use period (EFUP) No hazardous substances above the limits EU REACH SVHC REACH candidate substance (CAS No.) No substance above 0.1 wt% Phoenix Contact 2024 © - all rights reserved https://www.phoenixcontact.com Phoenix Contact USA

586 Fulling Mill Road

Middletown, PA 17057, United States (+717) 944-1300 info@phoenixcon.com HC-Q02-I-AT-M - Contact insert 1496723 https://www.phoenixcontact.com/us/products/1496723 Oct 31, 2024, 6:52 AM Page 8 (8)