1467800 PHOENIX | Alldatasheet
Document overview
- Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
- PDF pages: 17
Technical content
Please be informed that the data shown in this PDF document is generated from our online catalog. Please find the complete data in the user documentation. Our general terms of use for downloads are valid. TRIO capacity module, with maintenance-free energy storage based on double-layer capacitor, USI (Universal Service Interface), DIN rail mounting, input: 230 V AC, input:1-phase, output: 24 V DC / 5 A / 3 kJ incl. mounted UTA 107 universal DIN rail adapter Product description The TRIO3 capacity module combines the power supply, electronic switch-over unit, and energy storage in the same housing. The capacity module stores the energy required to bridge mains failures in maintenance-free double-layer capacitors. Several minutes of mains buffering is possible depending on the required load current. The USB-C (USI) or RS-485 interfaces make it convenient to shut down your PC. Commercial data Item number 1467800 Packing unit 1 pc Minimum order quantity 1 pc Product key CMUDC3 GTIN 4063151864859 Weight per piece (including packing) 1,852 g Weight per piece (excluding packing) 1,367 g Country of origin CN TRIO3-CAP/1AC/24DC/5/3KJ/USB-485 - Capacity module 1467800 https://www.phoenixcontact.com/us/products/1467800 Nov 6, 2025, 12:21AM Page 1 (17)
115 V AC ... 240 V AC ±10 % (UL) 100 V DC ... 240 V DC ±10 % Input voltage range 160 V DC ... 240 V DC ±10 % (UL) Frequency range (fN) 50 Hz ... 60 Hz ±10 % < 100 V AC (1 %/V)Derating < 140 V DC (1 %/V) typ. 1.45 A (100 V AC) typ. 0.75 A (240 V AC) typ. 1.4 A (100 V DC) Current consumption typ. 0.7 A (240 V DC) Charging time approx. 5 min (For completely discharged capacitors) Recharging time approx. 3 min Switch-on time ≤ 1 ms Recommended breaker for input protection 6 A ... 20 A (Characteristic B, C, D, K or comparable) Output data typ. 93.5 % (230 V AC)Efficiency typ. 92.1 % (120 V AC) Short-circuit-proof yes No-load proof yes typ. 1.58 (120 V AC)Crest factor typ. 1,7 (230 V AC) Connection in parallel yes, for increased performance Connection in series yes Feedback voltage resistance ≤ 35 V DC Protection against overvoltage at the output (OVP) ≤ 35 V DC Residual ripple < 100 mV Rise time ≤ 1 s (UOUT (10 % ... 90 %)) Mains operation Output voltage 24 V DC ±2 % Output voltage range 24 V DC ... 28 V DC (> 24 V constant capacity) Output current IN 5 A Dynamic Boost (IDyn.Boost) 7.5 A (5 s) Dynamic BOOST (ICAP.Boost) 17.5 A (350 ms) Output power POUT (UN, IOUT = IN) 120 W Output power POUT (UN, IOUT = Istat.Boost) 420 W (350 ms) Output power POUT (UN, IOUT = Idyn.Boost) 180 W (5 s) Power dissipation Nominal load (UN, IOut = IN, ICharge = 0) 10.3 W TRIO3-CAP/1AC/24DC/5/3KJ/USB-485 - Capacity module 1467800 https://www.phoenixcontact.com/us/products/1467800 Nov 6, 2025, 12:21AM Page 2 (17)
Output voltage 23.5 V DC ±2 % Output current IN 5 A Dynamic Boost (IDyn.Boost) 7.5 A (5 s) Dynamic BOOST (ICAP.Boost) 17.5 A (350 ms) Output power POUT (UN, IOUT = IN) 120 W Power dissipation No load (UN, IOut = 0, ICharge = 0) 5 W Power dissipation Nominal load (UN, IOut = IN, ICharge = 0) 11 W Power loss nominal load max. 9 W Maximum no-load power dissipation 4 W Output current limit 17.5 A (350 ms) 55 s (dyn. Boost)Recovery time 2 h (buffer mode) Short-circuit-proof yes Idling-proof yes Energy storage Input Charging current 1 A ... 5 A Charging power 24 W General Capacity 3 kJ Storage medium Double-layer capacitor Permissible backup fuse B10 Connection data Input Position 1.x Identification 1.1 (L/+), 1.2 (N/-), 1.3 () Conductor connection Connection method Push-in spring connection 0.2 mm² ... 4 mm²rigid 1.5 mm² 1.5 mm² 1.5 mm² TRIO3-CAP/1AC/24DC/5/3KJ/USB-485 - Capacity module 1467800 https://www.phoenixcontact.com/us/products/1467800 Nov 6, 2025, 12:21AM Page 3 (17)
1.5 mm² 24 ... 12AWG Stripping length 10 mm Output Position 2.x Identification 2.1 (+), 2.2 (-) Conductor connection Connection method Push-in spring connection 0.2 mm² ... 10 mm²rigid 4 mm² 0.2 mm² ... 6 mm²flexible 4 mm² 4 mm² 4 mm² 24 ... 12AWG Stripping length 10 mm Signal Position 3.x Identification 3.1 (Mains Mode), 3.2 (Alarm), 3.3 (Ready), 3.4 (Remote) Conductor connection Connection method Push-in spring connection 0.5 mm² 0.5 mm² 0.5 mm² 0.5 mm² 24 ... 16AWG Stripping length 10 mm Interfaces Communication Connection method RS-485 Communication TRIO3-CAP/1AC/24DC/5/3KJ/USB-485 - Capacity module 1467800 https://www.phoenixcontact.com/us/products/1467800 Nov 6, 2025, 12:21AM Page 4 (17)
Connection method USI (USB-C) USI (Universal Service Interface)Interface RS-485 Signaling Signal state Mains_Mode Connection labeling 3.1 Channel DO (digital output) Switching contact non-floating State condition (configurable) High: Uout > Uset -2 V 2% and Uout < 30.5 2% Low: Uout < Uset -2V 2% or Uout > 30.5 2% Device is in buffer mode Output can be loaded 20 mA State - signal assignment active - high Reference potential SGnd LED status indicator green Resistance 1.2 kΩ (Pull-up) Signal state Alarm Connection labeling 3.2 Channel DO (digital output) Switching contact non-floating State condition (configurable) Alarm threshold Output can be loaded 20 mA State - signal assignment NC (Normally Closed) Current carrying capacity 20 mA Reference potential SGnd LED status indicator red Resistance 1.2 kΩ (Pull-up) Signal state Ready Connection labeling 3.3 Channel DO (digital output) Switching contact non-floating State condition (configurable) High: CAPs are fully charged Device is in buffer mode Low: CAPs are charging Output can be loaded 20 mA State - signal assignment active - high Current carrying capacity 20 mA Reference potential SGnd LED status indicator green Resistance 1.2 kΩ (Pull-up) Signal state Remote Connection labeling 3.4 TRIO3-CAP/1AC/24DC/5/3KJ/USB-485 - Capacity module 1467800 https://www.phoenixcontact.com/us/products/1467800 Nov 6, 2025, 12:21AM Page 5 (17)
Channel DI (digital input) State (configurable) Remote State condition (configurable) Remote State - signal assignment active - low Reference potential 2.2 (negative pole, identical to 3.1, 3.2, 3.3) Electrical properties Number of phases 1 5.3 kV DC (type test) 3.1 kV DC (routine test) Insulation voltage input/output 6 kV DC Insulation voltage input / PE 4 kV DC Product properties Product type DC UPS with integrated capacitor Product family TRIO capacity module Insulation characteristics Protection class I Degree of pollution 2 Dimensions Item dimensions Width 133 mm Height 135 mm Depth 125 mm Depth (Device depth (DIN rail mounting)) 125 mm Mounting Mounting type DIN rail mounting Mounting position horizontal DIN rail NS 35, EN 60715 Material specifications Flammability rating according to UL 94 (housing / terminal blocks) Environmental and real-life conditions Ambient conditions Degree of protection IP20 Ambient temperature (operation) -25 °C ... 60 °C Ambient temperature (storage/transport) -40 °C ... 70 °C Ambient temperature (start-up type tested) -40 °C Maximum altitude ≤ 5000 m (> 2000 m, Derating: 10 %/1000 m) Climatic class 3K3 Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing) TRIO3-CAP/1AC/24DC/5/3KJ/USB-485 - Capacity module 1467800 https://www.phoenixcontact.com/us/products/1467800 Nov 6, 2025, 12:21AM Page 6 (17)
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2- 27) 10 Hz ... 50 Hz, amplitude ±0.2 mmVibration (operation) Standards and regulations Overvoltage category EN 61010-1 III (≤ 2000 m) / II (≤ 5000 m) EN 61010-2-201 III (≤ 2000 m) Safety of power supply units up to 1100 V (insulation distances) Standard designation Safety of power supply units up to 1100 V (insulation distances) Standards/specifications DIN EN 61558-2-16 Electrical safety Standard designation Electrical safety Standards/specifications IEC 61010-2-201 (SELV) Electronic equipment for use in power installations Standard designation Equipping high voltage installations with electronic equipment Standards/specifications EN 50178/VDE 0160 (PELV) Safety for measurement, control, and laboratory equipment Standard designation Safety for equipment for measurement, control, and laboratory use Standards/specifications IEC 61010-1 Protective extra-low voltage Standard designation Protective extra-low voltage IEC 61010-1 (SELV)Standards/specifications IEC 61010-2-201 (PELV) Safe isolation Standard designation Safe isolation IEC 61558-2-16Standards/specifications IEC 61010-2-201 Limitation of harmonic line currents Standard designation Limitation of harmonic line currents Standards/specifications EN 61000-3-2 Approvals UL Identification UL/C-UL Listed UL 61010-1 UL Identification UL/C-UL Listed UL 61010-2-201 TRIO3-CAP/1AC/24DC/5/3KJ/USB-485 - Capacity module 1467800 https://www.phoenixcontact.com/us/products/1467800 Nov 6, 2025, 12:21AM Page 7 (17)
PROCESS CONTROL EQUIPEMENT FOR HAZARDOUS LOCATIONS (EN) This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D, Hazardous Locations, or non-hazardous locations only. (FR) Cet appareil convient uniquement pour une utilisation en atmosphères explosibles de classe I, division 2, groupes A, B, C et D ou en atmosphères non explosibles. (EN) WARNING: Explosion Hazard - Do not connect or disconnect equipment unless power has been switched off or the area is known to be non-hazardous. (FR) AVERTISSEMENT : risque d'explosion - ne pas connecter ou déconnecter les équipements sauf si l'alimentation a été coupée ou si la zone est réputée non dangereuse. (EN) If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. (FR) Si l'équipement est utilisé d'une manière non spécifiée par le fabricant, la protection fournie par cet équipement peut être altérée. Identification (EN) This equipement must be installed in a suitable, tool secured/key locked enclosure. (FR) Cet équipement doit être installé dans un boîtier approprié, verrouillé par une clé ou dont l'ouverture nécessite l'utilisation d'un outil. EMC data Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC Interference emission Interference emission in accordance with EN 61000-6-3 (residential and commercial) and EN 61000-6-4 (industrial) Noise immunity Immunity in accordance with EN 61000-6-1 (residential), EN 61000-6-2 (industrial) Conducted noise emission Standards/regulations EN 61000-6-3 Noise emission Standards/regulations EN 61000-6-3 DNV GL conducted noise emissions DNV Class A Additional text Area power distribution DNV GL noise radiation DNV Class B Additional text Bridge and deck area Harmonic currents Standards/regulations EN 61000-3-2 Flicker TRIO3-CAP/1AC/24DC/5/3KJ/USB-485 - Capacity module 1467800 https://www.phoenixcontact.com/us/products/1467800 Nov 6, 2025, 12:21AM Page 8 (17)
Standards/regulations EN 61000-3-3 Electrostatic discharge Standards/regulations EN 61000-4-2 Electrostatic discharge Contact discharge 6 kV (Test Level 3) Discharge in air 8 kV (Test Level 3) Comments Criterion B Electromagnetic HF field Standards/regulations EN 61000-4-3 Electromagnetic HF field Frequency range 80 MHz ... 6 GHz Test field strength 10 V/m (Test Level 3) Fast transients (burst) Standards/regulations EN 61000-4-4 Fast transients (burst) Input asymmetrical 4 kV (Test Level 3) Comments Criterion A Surge voltage load (surge) Standards/regulations EN 61000-4-5 Surge voltage load (surge) symmetrical 1 kV (Test Level 3)Input asymmetrical 2 kV (Test Level 3) symmetrical 1 kV (Test Level 2)Output asymmetrical 1 kV (Test Level 3) Signal asymmetrical 1 kV (Test Level 2) Comments Criterion B Conducted interference Standards/regulations EN 61000-4-6 Conducted interference Input/output/signal asymmetrical Frequency range 0.15 MHz ... 80 MHz Comments Criterion A Voltage 10 V Voltage dips Standards/regulations EN 61000-4-11 Voltage 230 V AC Frequency 50 Hz Voltage dip 70 % TRIO3-CAP/1AC/24DC/5/3KJ/USB-485 - Capacity module 1467800 https://www.phoenixcontact.com/us/products/1467800 Nov 6, 2025, 12:21AM Page 9 (17)
Number of periods 25 periods Additional text Class 3 Comments Criterion A Voltage dip 40 % Number of periods 10 periods Additional text Class 3 Comments Criterion A Voltage dip 0 % Number of periods 1 period Additional text Class 3 Comments Criterion A TRIO3-CAP/1AC/24DC/5/3KJ/USB-485 - Capacity module 1467800 https://www.phoenixcontact.com/us/products/1467800 Nov 6, 2025, 12:21AM Page 10 (17)
63,5 135 133 Dimensions, front view (in mm) TRIO3-CAP/1AC/24DC/5/3KJ/USB-485 - Capacity module 1467800 https://www.phoenixcontact.com/us/products/1467800 Nov 6, 2025, 12:21AM Page 11 (17)
Dimensions, side view (in mm) TRIO3-CAP/1AC/24DC/5/3KJ/USB-485 - Capacity module 1467800 https://www.phoenixcontact.com/us/products/1467800 Nov 6, 2025, 12:21AM Page 12 (17)
B A C D F E Housing Test sections, insulation voltage TRIO3-CAP/1AC/24DC/5/3KJ/USB-485 - Capacity module 1467800 https://www.phoenixcontact.com/us/products/1467800 Nov 6, 2025, 12:21AM Page 13 (17)
IF μC COM USI, RS485 μC L Input AC 1.1 Internal fuse EMI Filter Inrush control Charger Buffer EMI Filter 1.2 2.1 2.2 3.1 3.2 3.3 3.4 1.3 N Output DC Mains Mode LEDs „Mains Mode“ „Device State“ „SOH“ USI 5.1 5.2RS 485 Remote Ready Alarm Block diagram Graphic Load Current Buffertime Seconds Minutes 5 10 15 20 30 40 50 1 3 5 7 10 15 20 30 45 0,10 A 0,25 A 0,50 A 1,00 A 2,50 A 5,00 A 7,50 A 10,0 A 12,0 A 15,0 A 20,0 A 26,0 A 30,0 A The data is based on an ambient temperature of +25 °C at the start of use.
1467800 TRIO3-CAP/1AC/24DC/5/3KJ/USB-485
1467808 TRIO3-CAP/1AC/24DC/10/6KJ/USB-485
1467815 TRIO3-CAP/1AC/24DC/20/12KJ/USB-485
TRIO3-CAP/1AC/24DC/5/3KJ/USB-485 - Capacity module 1467800 https://www.phoenixcontact.com/us/products/1467800 Nov 6, 2025, 12:21AM Page 14 (17)
To download certificates, visit the product detail page: https://www.phoenixcontact.com/us/products/1467800 IECEE CB Scheme Approval ID: SI-12205 cULus Listed Approval ID: UL-US-2433162-0 cULus Listed Approval ID: E199827-20241204 TRIO3-CAP/1AC/24DC/5/3KJ/USB-485 - Capacity module 1467800 https://www.phoenixcontact.com/us/products/1467800 Nov 6, 2025, 12:21AM Page 15 (17)
ECLASS-13.0 27040705 ECLASS-15.0 27040705 ETIM ETIM 8.0 EC000382 TRIO3-CAP/1AC/24DC/5/3KJ/USB-485 - Capacity module 1467800 https://www.phoenixcontact.com/us/products/1467800 Nov 6, 2025, 12:21AM Page 16 (17)
Environmental product compliance EU RoHS Fulfills EU RoHS substance requirements Yes Exemption 6(c), 7(a), 7(c)-I China RoHS EFUP-25Environment friendly use period (EFUP) An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required. EU REACH SVHC REACH candidate substance (CAS No.) Lead(CAS: 7439-92-1) Phoenix Contact 2025 © - all rights reserved https://www.phoenixcontact.com Phoenix Contact USA
586 Fulling Mill Road
Middletown, PA 17057, United States (+717) 944-1300 info@phoenixcon.com TRIO3-CAP/1AC/24DC/5/3KJ/USB-485 - Capacity module 1467800 https://www.phoenixcontact.com/us/products/1467800 Nov 6, 2025, 12:21AM Page 17 (17)