145X282 MARATHON | Alldatasheet
Document overview
- Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
- PDF pages: 3
Technical content
www.marathonsp.com 145X282 Replace “x” with 1, 2, or 3 for number of poles Power Terminal Block
760 Amps 600 Volts AC/DC
- Line: (2) 3/8 - 16 X 1” stud
- Load: (8) 2/0 - 14 AWG Electrical Ratings
- 760 Amps
- 600V per UL 1059 & CSA 22.2 No.158, class B & C requirements
- SCCR of 10,000 A (default for terminal blocks).
- CU7AL - 75°C connector terminal rating with copper or aluminum wire
- Factory & Field Wiring Agency Compliance
- UR - UL Recognized Terminal Block, Evaluated to UL 1059, File No.XCFR2.E62806
- CSA - certifed to C22.2 No. 158, File No. LR19766 (wire classes B & C only)
- CE compliant to IEC 60947-7-1 Material Information
- Insulator base:
- Phenolic
- Flammability rating of insulator base UL94V0
- Insulator base temperature rating: -40°C to 150°C (UL RTI)
- Connector: aluminum, tin plated
- Terminal set screws: aluminum, tin plated
- Threaded stud: brass, tin plated
- Hex nut: brass, nickel plated
- Washer: 3/8” flat - steel, zinc plated
- Washer: 3/8” split - steel, zinc plated
- Connector mounting screws: steel, zinc plated
- RoHS compliant
www.marathonsp.com PDS 0462 REV-D 1/12/18 Termination Specifications
- Aluminum wire range: 2/0 - 8 AWG
- Wire strip length: 11/16 in. (17mm)
- Terminal screw drive: 3/16 in. hex Load Side Wire Size (CU Stranded) Torque Wires / Terminal Wire Class (UL) 1 2/0 - 4 13.6 N·m (120lbf·in) 1 B, C 6 13.6 N·m (120lbf·in) 1 - 2 B, C
4.5 N·m (40lbf·in) 1 B, C
6.8 N·m (60lbf·in) 2 B, C
4 N·m (35lbf·in) 1 B, C
14 4 N·m (35lbf·in) 1 B, C
1 For information on copper stranded wire classes please reference:
http://www.marathonsp.com/CatalogPDFs/Flexible-Stranded-Wire.pdf Line Side Termination Type Torque Stud Length Maximum Lug/Bar Width Listed lugs on 3/8 - 16
21.7 N·m
(192 lbf·in) (25mm) 2.25” (57mm)
- For use with conductors prepared with listed connectors such as single hole compression/crimp lugs or listed ring, fork or spade terminals.
- Conductor size, ampacity, temperature rating and type are dictated by the ratings of the listed lugs utilized and applicable code requirements.
- Hex nuts provided: 9/16 across flats
www.marathonsp.com PDS 0462 REV-D 1/12/18 Installation & Accessories
- Mounting (Panel):
- For use with 1/4 fastener.
- Torque mounting fastener to 30-40 lbf·in (3.4 - 4.5 N·m).
- Covers:
- Flat covers available upon request
- Catalog Number: CC 145x (replace “x” with number of poles)
- Covers are clear polycarbonate
- Accessory covers are not intended to provide insulation for electrical spacings.
- Marker Strip: white vinyl strip with mounting screws available.
- Printing options available, consult customer service for specifications. Drawing