145X992 MARATHON | Alldatasheet

Document overview

  • Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
  • PDF pages: 4

Technical content

www.marathonsp.com 145X992 Replace “x” with 1, 2, or 3 for number of poles Power Terminal Block

760 Amps 600 Volts AC/DC

  • Line: (2) 500 kcmil - #4 AWG
  • Load: (12) #2 - #14 AWG Electrical Ratings
  • 760 Amps
  • 600V per UL 1059 & CSA 22.2 No.158, class B & C requirements
  • SCCR of 10,000 A (default for terminal blocks).
  • CU9 - 90°C connector terminal rating with copper wire
  • Factory & Field Wiring Agency Compliance
  • UR - UL Recognized Terminal Block, Evaluated to UL 1059, File No.XCFR2.E62806
  • CSA - certifed to C22.2 No. 158, File No. LR19766 (wire classes B & C only)
  • CE compliant to IEC 60947-7-1 Material Information
  • Insulator base:
  • Phenolic
  • Flammability rating of insulator base UL94V0
  • Insulator base temperature rating: -40°C to 150°C (UL RTI)
  • Connector: copper, tin plated
  • Line terminal set screws: aluminum, tin plated
  • Load terminal set screws: steel, nickel plated
  • Connector mounting screws: steel, zinc plated
  • RoHS compliant

www.marathonsp.com PDS 0090 REV-E 1/15/18 Termination Specifications

  • Wire strip length: 1 5/8 in. (41mm)
  • Terminal screw drive: 3/8 in. hex Line Side Wire Size (CU Stranded) Torque Wires / Terminal Wire Class (UL) 1 500 kcmil 42.4 N·m (375 lbf·in) 1 B, C 400 - 2 42.4 N·m (375 lbf·in) 1 B, C, G, H, I (DLO) 4 42.4 N·m (375 lbf·in) 1 B, C

1 For information on copper stranded wire classes please visit:

http://www.marathonsp.com/flexible-stranded-wire.php 2 Multiple wire rating applies to class B, C, & I.

  • Solid copper wire range: #10 - 14
  • Wire strip length:
  • Top row: 5/8 in. (16mm)
  • Bottom row: 1.0 in. (25mm)
  • Terminal screw drive: slotted Load Side Wire Size (CU Stranded) Torque Wires / Terminal Wire Class (UL) 1 2 AWG 5.6 N·m (50 lbf·in) 1 B, C 4 - 6 5.1 N·m (45 lbf·in) 1 B, C, G, H, I (DLO) 8 4.5 N·m (40 lbf·in) 1 - 2 2 B, C, G, H, I (DLO) 10 4 N·m (35 lbf·in) 1 - 2 B, C, I (DLO) 12 - 14 4 N·m (35 lbf·in) 1 - 2 I (DLO) 1 - 4 B, C

www.marathonsp.com PDS 0090 REV-E 1/15/18

  • The suitable conductor ranges are limited to the table values only for achieving the SCCR in excess of the default rating of 10,000A.
  • Other conductor combinations within the “Terminal Specifications” noted are suitable for achieving a SCCR of 10,000A (the default rating of terminal blocks).
  • Enclosure size – Investigated with a minimum 16x12x6 enclosure. Use in smaller enclosures is subject to end use evaluation. Short Circuit Current Ratings (SCCR) Wire Class Suitable Conductors Max Overcurrent Protection Fuse Required Amp Rating / Class SCCR RMS Sym. Amps 600V. MaxLine Load J T RK1 RK5 G CC B, C 500 - 4 2- 10 400 400 400 200 60 30 100,000 B, C 500 - 250 2 - 8 600 600 - - - - 100,000 G, H, I 350 - 2 4 - 10 400 400 400 200 60 30 100,000 G, H, I 350 - 250 4 - 8 600 600 - - - - 100,000 (*) 500 - 4 2 - 14 None 10,000 SCCR With Fuses * Any wire class evaluated (see terminal specification section)

www.marathonsp.com PDS 0090 REV-E 1/15/18 Drawing

  • Mounting (Panel):
  • For use with 1/4 fastener.
  • Torque mounting fastener to 30-40 lbf·in (3.4 - 4.5 N·m).
  • Covers:
  • Flat covers available upon request
  • Catalog Number: CC 145x (replace “x” with number of poles)
  • Covers are clear polycarbonate
  • Accessory covers are not intended to provide insulation for electrical spacings.
  • Marker Strip: white vinyl strip with mounting screws available.
  • Printing options available, consult customer service for specifications. Installation & Accessories