www.marathonsp.com 141X400 Replace “x” with 1, 2, 3 or 4 for number of poles Power Terminal Block
115 Amps 600 Volts AC/DC
- Line: (1) #2-#14 AWG
- Load: (4) #10-#18 AWG Electrical Ratings
- 115 Amps
- 600V per UL 1059 & CSA 22.2 No.158, class B & C requirements
- Short circuit current ratings (SCCR): See SCCR section below for specifications.
- CU7AL - 75°C connector terminal rating with copper or aluminum wire
- Factory & Field Wiring Agency Compliance
- UR - UL Recognized Terminal Block, Evaluated to UL 1059, File No.XCFR2.E62806
- CSA - certifed to C22.2 No. 158, File No. LR19766 (wire classes B & C only)
- CE compliant to IEC 60947-7-1 Material Information
- Insulator base:
- Thermoplastic
- Flammability rating of insulator base UL94V0
- Insulator base temperature rating: -40°C to 125°C (UL RTI)
- Connector: aluminum, tin plated
- Terminal screws: steel, nickel plated
- Connector mounting screws: steel, zinc plated
- RoHS compliant
www.marathonsp.com 08/02/21 Load Side Wire Size (CU Stranded) Torque Wires / Terminal Wire Class (UL) 1 10 - 12 .8 N·m (7 lbf·in) 1 B, C, I (DLO) 14 .8 N·m (7 lbf·in) 1 - 2 2 B, C, I (DLO) 16 - 18 .8 N·m (7 lbf·in) 1 B, C Termination Specifications Line Side Wire Size (CU Stranded) Torque Wires / Terminal Wire Class (UL) 1 2 5.6 N·m (50 lbf·in) 1 B, C 4 - 6 5.1 N·m (45 lbf·in) 1 B, C, G, H, I (DLO) 8 4.5 N·m (40 lbf·in) 1 B, C, G, H, I (DLO) 10 - 14 4 N·m (35 lbf·in) 1 B, C, I (DLO)
- Aluminum wire range: 2 - 12 AWG
- Solid copper wire range: 10 - 14 AWG
- Wire strip length: 1/2 in. (13 mm)
- Terminal screw drive: slotted
- Solid copper wire range: 10-18 AWG
- Wire strip length:
- top row: 3/8in. (10mm)
- bottom row: 5/8in. (16mm)
- Terminal screw drive: slotted
1 For information on copper stranded wire classes please visit:
http://www.marathonsp.com/flexible-stranded-wire.php 2 Multiple wire rating applies to Class-I only. Classes B & C are rated for 1 wire per terminal.
www.marathonsp.com 08/02/21 Short Circuit Current Ratings (SCCR)
- The suitable conductor ranges are limited to the table values only for achieving the SCCR in excess of the default rating of 10,000A.
- Other conductor combinations within the “Terminal Specifications” noted are suitable for achieving a SCCR of 10,000A (the default rating of terminal blocks).
- Enclosure size – Investigated with a minimum 16x12x6 enclosure. Use in smaller enclosures is subject to end use evaluation. Wire Type Suitable Conductors Max Overcurrent Protection Fuse Required Amp Rating / Class SCCR RMS Sym. Amps 600V . MaxLine Load J T RK1 RK5 G CC B, C 2 - 6 10 200 200 200 60 60 30 100,000 B, C 2 - 10 10 -14 150 150 100 30 60 30 100,000 B, C 4 - 14 10 - 14 60 60 30 30 60 30 100,000 G, H, I 4 - 10 10 - 14 150 150 100 30 60 30 100,000 (*) 2 - 14 10 - 18 None 10,000 Suitable Conductors Overcurrent Protection Circuit Breaker Required Max AMP Volts Max SCCR RMS Sym. Amps 600V . MaxLine Load MFR TYPE 2 - 6 AWG 10 AWG Square-D JDL36250 250 480 18,000 Square-D JGL36250 250 480 35,000 Square-D JJL36250 250 480 65,000 Square-D JLL36250 250 480 65,000 8 - 10 AWG 14 AWG Square-D JDL36250 250 480 18,000 Square-D JGL36250 250 480 35,000 Square-D JJL36250 250 480 65,000 Square-D JLL36250 250 480 65,000 Square-D HDL36100 250 480 18,000 Square-D HGL36100 250 480 35,000 Square-D HJL36100 250 480 65,000 Square-D HLL36100 250 480 65,000 SCCR With Fuses SCCR With Circuit Breakers * Any wire class evaluated (see terminal specification section)
www.marathonsp.com 08/02/21 Drawing Installation & Accessories
- Mounting (Panel):
- For use with #10 fastener.
- Recommended mounting torque: 25-30 lbf·in (2.8 - 3.4 N·m).
- Covers:
- Snap-on covers available upon request
- Catalog Number: CC141x (replace “x” with number of poles)
- Covers are semiclear polycarbonate
- Accessory covers are not intended to provide insulation for electrical spacings.