Please be informed that the data shown in this PDF document is generated from our online catalog. Please find the complete data in the user documentation. Our general terms of use for downloads are valid. Electronic reversing load relay, for controlling DC motors, with LED display and protective circuit, output: 24 V DC/3 A with a switch-over time of 5 ms Commercial data Item number 1291615 Packing unit 1 pc Minimum order quantity 1 pc Sales key C476 Product key CK7622 GTIN 4063151523985 Weight per piece (including packing) 119.7 g Weight per piece (excluding packing) 92.37 g Customs tariff number 85371098 Country of origin DE ELR DCR-PT-24DC-3 - Reversing load relay 1291615 https://www.phoenixcontact.com/us/products/1291615 Dec 20, 2024, 4:50 AM Page 1 (7)
Product type Solid-state contactor Product family CONTACTRON Operating mode 100% operating factor MTTF 244 Years ( = 20°C ) Insulation characteristics: Air clearances and creepage distances between the power circuits Insulation Basic insulation Electrical properties Number of phases 1 Switching frequency ≤ 10 Hz Mains type 1-phase Test voltage (Input/output) 2.5 kVrms (50 Hz, 60 s) Switching frequency ≤ 10 Hz Insulation characteristics Rated insulation voltage 50 V Rated surge voltage 800 V Overvoltage category III Degree of pollution 2 Air clearances and creepage distances between the power circuits Basic insulation Input data Input name DC input Rated control circuit supply voltage US 24 V DC Control supply voltage range 11 V DC ... 30 V DC Protective circuit Surge protection Control Input name Control input right/left Current consumption 3 mA Rated actuating voltage UC 24 V DC Rated actuating current IC < 2 mA Reverse polarity protectionProtective circuit Surge protection Surge voltage protection > 33 V DC Switchover time RL/LL (turn-on time) 5 ms Output data DC output ELR DCR-PT-24DC-3 - Reversing load relay 1291615 https://www.phoenixcontact.com/us/products/1291615 Dec 20, 2024, 4:50 AM Page 2 (7)
Rated operating voltage Ue 24 V DC Operating voltage range 11 V DC ... 30 V DC Rated operating current (DC-13 / Load output) 3 A (see to derating) Quiescent current 14 mA Short-circuit current 100 A Reverse polarity protectionProtective circuit Surge protection Surge voltage protection > 33 V DC Current limitation at short-circuits 75 A Connection data Control circuits Connection method Push-in connection Stripping length 10 mm Conductor cross section AWG 26 ... 14 Load circuit Connection method Push-in connection Stripping length 10 mm Conductor cross section AWG 26 ... 14 Signaling Status display LED (yellow) Operating voltage display Green LED Error indication Red LED Dimensions Width 12.5 mm Height 107 mm Depth 114.5 mm Material specifications Color gray (RAL 7042) Environmental and real-life conditions Ambient conditions Degree of protection IP20 Ambient temperature (operation) -25 °C ... 70 °C Ambient temperature (storage/transport) -40 °C ... 80 °C Altitude ≤ 2000 m ELR DCR-PT-24DC-3 - Reversing load relay 1291615 https://www.phoenixcontact.com/us/products/1291615 Dec 20, 2024, 4:50 AM Page 3 (7)
Certificate UKCA-compliant UL approval Certificate NKCR.E172140 Standards and regulations Air clearances and creepage distances between the power circuits Standards/regulations EN 60947-5-1 Mounting Mounting type DIN rail mounting Assembly note alignable, for spacing see derating Mounting position vertical (horizontal DIN rail, motor output below) ELR DCR-PT-24DC-3 - Reversing load relay 1291615 https://www.phoenixcontact.com/us/products/1291615 Dec 20, 2024, 4:50 AM Page 4 (7)
To download certificates, visit the product detail page: https://www.phoenixcontact.com/us/products/1291615 cULus Listed Approval ID: E172140 ELR DCR-PT-24DC-3 - Reversing load relay 1291615 https://www.phoenixcontact.com/us/products/1291615 Dec 20, 2024, 4:50 AM Page 5 (7)
ECLASS-11.0 27371014 ECLASS-13.0 27371014 ECLASS-12.0 27371014 ETIM ETIM 9.0 EC002055 ELR DCR-PT-24DC-3 - Reversing load relay 1291615 https://www.phoenixcontact.com/us/products/1291615 Dec 20, 2024, 4:50 AM Page 6 (7)
Environmental product compliance EU RoHS Fulfills EU RoHS substance requirements Yes Exemption 7(a), 7(c)-I China RoHS EFUP-50Environment friendly use period (EFUP) An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required. EU REACH SVHC REACH candidate substance (CAS No.) Lead(CAS: 7439-92-1) SCIP 93b31a84-4d8e-45fd-aef0-6e740e316201 Phoenix Contact 2024 © - all rights reserved https://www.phoenixcontact.com Phoenix Contact USA
586 Fulling Mill Road