https://www.phoenixcontact.com/us/products/1105522 10/27/2021 Page 1 / 9 Extension module - PSR-M-EF8-SDI8-SDO2-DO2-SC - 1105522 Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's documentation. Our General Terms of Use for Downloads are valid (http://phoenixcontact.com/download) Safe extension module with 8 safe inputs and 2 safe outputs, 2 reset inputs, 2 signal outputs, 4 clock outputs, TBUS interface, up to SILCL 3, Cat. 4/PL e, SIL 3, pluggable screw terminal block, TBUS connector included Product Description The configurable and individually scalable PSRmodular safety system is a flexible safety solution for monitoring your machine or system. The safe extension module provides the system additional safe inputs and outputs as well as signal outputs. Your advantages Cost-effective safety solution with a high level of adaptability to individual requirements Fast startup, thanks to easy hardware and software configuration Machine downtimes minimized with comprehensive, easy-to-understand diagnostics Narrow housing width of just 22.6 mm Up to Cat. 4/PL e in accordance with ISO 13849-1, SIL 3 in accordance with IEC 62061, SIL 3 in accordance with IEC 61508 Suitable for lift applications according to EN 81-20 Key Commercial Data Packing unit 1 pc GTIN GTIN 4055626987934 Weight per Piece (excluding packing) 200.000 g Custom tariff number 85371098 Country of origin Italy Technical data Dimensions Width 22.61 mm

https://www.phoenixcontact.com/us/products/1105522 10/27/2021 Page 2 / 9 Extension module - PSR-M-EF8-SDI8-SDO2-DO2-SC - 1105522 Technical data Dimensions Height 112.58 mm Depth 113.6 mm Ambient conditions Ambient temperature (operation) -10 °C ... 55 °C (observe derating) Ambient temperature (storage/transport) -20 °C ... 85 °C Max. permissible relative humidity (operation) 95 % (non-condensing) Max. permissible humidity (storage/transport) 95 % (non-condensing) Maximum altitude ≤ 2000 m (Above sea level) Power supply Designation A1/A2 Rated control circuit supply voltage US 24 V DC -20 % / +20 % (provide external protection, typically 8 A) Rated control supply current IS typ. 40 mA (Outputs inactive) typ. 55 mA (Outputs active, without load) Current consumption max. 2.3 A (with full load) Power consumption at US typ. 0.96 W (Outputs inactive) Inrush current < 9 A (Δt = 1 ms at Us) Filter time typ. 5 ms (at A1 in the event of voltage dips at Us) Protective circuit Serial protection against polarity reversal Suppressor diode Digital inputs Input name IN1, IN2, IN3, IN4, IN5, IN6, IN7, IN8 Description of the input Safety-related digital inputs EN 61131-2 type 1 Number of inputs 8 Input voltage range "0" signal 0 V DC ... 5 V DC Input voltage range "1" signal 15 V DC ... 28.8 V DC Input current range "0" signal < 1 mA Current consumption typ. 8 mA (typically with US) max. 10 mA (at a control voltage of 28.8 V DC) Filter time min. 3 ms ±2 ms (adjustable) max. 250 ms ±2 ms (adjustable) Test pulse rate ≥ 2x set filter time, min. Test pulse rate = 10 ms Max. permissible overall conductor resistance max. 1.2 kΩ (Input and reset circuit at US) Cable length max. 100 m (per input) Protective circuit/component Suppressor diode

https://www.phoenixcontact.com/us/products/1105522 10/27/2021 Page 3 / 9 Extension module - PSR-M-EF8-SDI8-SDO2-DO2-SC - 1105522 Technical data 2. Digital inputs Input name Reset inputs FBK1, FBK2 Description of the input IEC 61131-2 type 3 Number of inputs 2 Input voltage range "0" signal 0 V DC ... 5 V DC Input voltage range "1" signal 11 V DC ... 28.8 V DC Input current range "0" signal < 1 mA Current consumption typ. 10 mA (typically with US) max. 13 mA (at a control voltage of 28.8 V DC) Filter time 250 ms ±2 ms (Test pulse rate > 500 ms) Max. permissible overall conductor resistance 1.2 kΩ (Input and reset circuit at US) Cable length max. 100 m (per input) Protective circuit/component Suppressor diode Digital outputs Output name O1A, O1B, O2A, O2B Output description Safety-related digital outputs PNP, OSSD IEC 61131-2 type 0.5 (observe limiting continuous current) Number of outputs 4 (can be used as 2 two-channel outputs) Nominal output voltage 24 V DC (Supply via A1) Limiting continuous current 400 mA (per channel)

1.6 A (Total current of all safe digital outputs)

Inrush current max. 750 mA (Δt  1 s) Output voltage when switched off < 1.5 V Leakage current max. 500 µA Cable length max. 100 m (per output) Ohmic load min. 50 Ω (Observe limiting continuous current) Max. capacitive load max. 680 nF Max. inductive load max. 1.4 mH Switching frequency max. 1/4 x tCycle [Hz] Test pulses < 80 µs (Test pulse width of low test pulses) Test pulse rate for low test pulses > 2 x TCycle < 20 µs (Test pulse width, high test pulse) ≥ 1.5 s (Test pulse rate, high test pulse) Protective circuit/component Suppressor diode

https://www.phoenixcontact.com/us/products/1105522 10/27/2021 Page 4 / 9 Extension module - PSR-M-EF8-SDI8-SDO2-DO2-SC - 1105522 Technical data Digital outputs Short-circuit protection Yes (self-limitation at 1.1 A) Error detection time at 1-channel structure < 3.5 s (OFF state) < 4 x tCycle [ms] (ON state) Discharging circuit Yes, internal Alarm outputs Designation MO1, MO2 Output description PNP, IEC 61131-2 Typ 0,1 non-safety-related Number of outputs 2 Voltage 24 V DC (via A1) Output voltage when switched off max. 0.1 V Maximum inrush current 1.1 A (Δt = 3 s at Us) Switching frequency max. 1/4 x tCycle [Hz] Limiting continuous current 100 mA (per channel) 200 mA (Total current of all digital signal outputs) Leakage current max. 100 µA Protective circuit/component Suppressor diode Short-circuit protection Yes (self-limitation at 1.1 A) Cable length max. 100 m (per output) Clock outputs Designation T1, T2, T3, T4 Output description PNP, IEC 61131-2 type 0.5 Number of outputs 4 Voltage 24 V DC (via A1) Output voltage when switched off max. 0.1 V Maximum inrush current 1.1 A (Δt = 3 s at Us) Limiting continuous current 100 mA (per channel) 400 mA (Total current of all outputs) Leakage current max. 100 µA Cable length max. 100 m (per output) Max. capacitive load max. 470 nF Max. inductive load max. 2.4 mH Test pulses ≤ 220 µs (Test pulse duration) Test pulse rate = 8 x tCycle [ms]

https://www.phoenixcontact.com/us/products/1105522 10/27/2021 Page 5 / 9 Extension module - PSR-M-EF8-SDI8-SDO2-DO2-SC - 1105522 Technical data Clock outputs Protective circuit/component Suppressor diode Short-circuit protection Yes (self-limitation at 1.1 A) Discharging circuit Yes, internal Times Response time see user manual Restart time min. 5 s (Boot time) max. 10 s (Boot time) Cycle time see user manual General Nominal operating mode 100% operating factor Net weight 159 g Mounting position vertical or horizontal Mounting type DIN rail mounting Assembly instructions Observe derating Degree of protection IP20 Min. degree of protection of inst. location IP54 Protection class III (EN 50178) Housing material Polyamide PA non-reinforced Housing color yellow Operating voltage display 1 x green LED Status display 1 x LED (green), 2 x LED (orange) 12 x LED (yellow) 2 x LED (green, red) Indication 2 x LED (red) Connection data Connection method Screw connection pluggable Yes Conductor cross-section AWG 24 ... 12 Stripping length 7 mm Screw thread M3 Safety-related characteristic data Stop category in accordance with IEC 60204 0

https://www.phoenixcontact.com/us/products/1105522 10/27/2021 Page 6 / 9 Extension module - PSR-M-EF8-SDI8-SDO2-DO2-SC - 1105522 Technical data Safety-related characteristic data Designation IEC 61508 - High-demand for 2-channel wiring Safety Integrity Level (SIL) 3 Designation IEC 61508 - High-demand for 1-channel wiring Safety Integrity Level (SIL) 2 Designation EN ISO 13849 Performance level (PL) e (2-channel wiring) d (1-channel wiring) Designation EN 62061 Safety Integrity Level (SIL) 3 (2-channel wiring) 2 (1-channel wiring) Standards and Regulations Designation Air clearances and creepage distances between the power circuits Standards/regulations EN 50178 Rated insulation voltage 250 V AC Rated surge voltage/insulation Basic insulation 4 kV between 24 V power supply and I/Os to the housing Degree of pollution 2 Overvoltage category II Shock 10g for Δt = 16 ms (continuous shock, 1000 shocks in each space direction) Vibration (operation) 10 Hz ... 150 Hz, 2g Conformance CE-compliant Environmental Product Compliance China RoHS Environmentally friendly use period: unlimited = EFUP-e No hazardous substances above threshold values Drawings

https://www.phoenixcontact.com/us/products/1105522 10/27/2021 Page 7 / 9 Extension module - PSR-M-EF8-SDI8-SDO2-DO2-SC - 1105522 Application drawing 24V DC SDO2-DO2 PSR-M-B1-SDI8- PSR-TBUS IN2 FBK1 FBK2 EN1 EN2 MO1 MO2 1 4 2 3 13 14 15 16 7 11 8 12 IN1 IN5 O1A IN6 O1B IN3 IN7 IN4 IN8 O2A O2B 17 18 19 20 21 22 23 24 5 6 9 10 PSR-M-EF8-SDI8- SD02-D02 PSR-TBUS PSR-TBUS ADR0 ADR1 11 4 2 3 13 14 15 16 FBK1 FBK2 MO1 MO2 7 11 8 12 IN1 IN5 IN2 IN6 IN3 IN7 IN4 IN8 17 18 19 20 21 22 23 24 O1A O1B O2A O2B 5 6 9 10 Block diagram PWR 24V DC TEST PULSE OUTPUT SAFE INPUT ADR SELECTION SAFE OUTPUT MONITORING OUTPUTRESTART/FBK MO1O1A FBK1ADR0 MO2FBK2O1B O2A O2BADR1A2 T2 T3 T4 IN1 IN2 IN3 IN4 IN5 IN6 IN7 IN8 PSR-M-EF8-SDI8-SDO2-DO2 LOGIC T-BUS 128117109653241 13 14 15 16 17 18 19 20 21 22 23 24 Classifications eCl@ss eCl@ss 10.0.1 27371819 eCl@ss 11.0 27371819 eCl@ss 9.0 27371819 ETIM ETIM 7.0 EC001449 UNSPSC UNSPSC 18.0 39122205 UNSPSC 19.0 39122205 UNSPSC 20.0 39122205 UNSPSC 21.0 39122205

https://www.phoenixcontact.com/us/products/1105522 10/27/2021 Page 8 / 9 Extension module - PSR-M-EF8-SDI8-SDO2-DO2-SC - 1105522 Approvals Approvals Approvals UL Listed / cUL Listed / EAC / cULus Listed Ex Approvals Approval details UL Listed http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 238705 cUL Listed http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 238705 EAC RU*-DE*B.00606/20 cULus Listed Accessories Accessories Coding element Coding profile - CP-MSTB - 1734634 Coding profile, is inserted into the slot on the plug or inverted header, red insulating material

https://www.phoenixcontact.com/us/products/1105522 10/27/2021 Page 9 / 9 Extension module - PSR-M-EF8-SDI8-SDO2-DO2-SC - 1105522 Accessories Coding section - CR-MSTB - 1734401 Coding section, inserted into the recess in the header or the inverted plug, red insulating material Phoenix Contact 2021 © - all rights reserved http://www.phoenixcontact.com