10BX MSYSTEM | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 5
Technical content
MODEL: 10BX http://www.m-system.co.jp/ 10BX SPECIFICATIONS ES-0891 Rev.12 Page 1/5 High-density Signal Conditioners 10-RACK STANDARD RACK Functions & Features
- Standard 19" rack for 10-RACK signal conditioners
- 4 – 16 modules mountable
- Line power access at the terminal card, supplied via the rear rack bus
- Direct interface to various DCS with the rack side connector MODEL: 10BX–[1][2]
ORDERING INFORMATION
- Code number: 10BX-[1][2] Specify a code from below for each [1] and [2]. (e.g. 10BX-1/W/Q)
- Specify the specification for option code /Q (e.g. /C01) [1] CAPACITY & TERMINAL CARD FUNCTION 1: 16 ch.; 24 V DC powered 2-K: 15 ch.; 85 – 132 V AC powered 2-L: 15 ch.; 170 – 264 V AC powered 3: 15 ch.; 24 V DC & 85 – 132 V AC powered (two independent power sources) 4: 16 ch.; 24 V DC (Fujitsu FCN type I/O connector) 7: 16 ch.; 24 V DC (Yokogawa VMx / PM1 card use) 8: 16 ch.; 24 V DC (Omron 3G8B2-NA000 / NA001 use) 10: 16 ch.; 24 V DC (Nippon Shokubai DCS use) 11: 16 ch.; 24 V DC (Azbil J-HAM50 / J-HMM00 module use) 12: 16 ch.; 24 V DC (Azbil J-AOM10 module use) 13: 8 ch.; 24 V DC (Azbil J-PIM00 module use) A: 4 ch.; 24 V DC powered B: 4 ch.; 85 – 132 V AC powered C: 9 ch.; 24 V DC powered D-K: 8 ch.; 85 – 132 V AC powered D-L: 8 ch.; 170 – 264 V AC powered M-System guarantees the connecting section. [2] OPTIONS (multiple selections) Mounting Bracket blank: Rack mounting, standard /W: Surface mounting Other Options blank: none /Q: Option other than the above (specify the specification) SPECIFICATIONS OF OPTION: Q COATING (For the detail, refer to M-System's web site.) Power supply and signal conditioner side of the main PWB are not coated. /C01: Silicone coating /C02: Polyurethane coating /C03: Rubber coating
RELATED PRODUCTS
- Blank filler plate (model: P-101)
- Connector terminal block (model: CNT)
- Special cable with 40-pin connector (model: FCN) GENERAL SPECIFICATIONS Construction: Metal plates assembly Coating: Zn-Cr (black), alumetized steel Connection Power input: M4 screw terminals (torque 0.8 N·m) Screw terminal: Nickel-plated brass Isolation: I/O connector to power to FG INSTALLATION Power consumption
- AC: 85 – 132 V or 170 – 264 V, 47 – 63 Hz, 130 VA minimum
- DC: Operating voltage range 24 V DC ±10 %, 2.5 A minimum (ripple 10 % p-p max.) Operating temperature: -5 to +55°C (23 to 131°F) 0 to 50°C (32 to 122°F) for AC power Operating humidity: 30 to 90 %RH (non-condensing) Mounting 15, 16-position rack, 10BX-13: JIS or EIA standard rack or surface 4, 8, 9-position rack: Angle bracket or surface Weight 10BX-A: 1.1 kg (2.4 lb) 10BX-B: 1.3 kg (2.9 lb) 10BX-C: 1.5 kg (3.3 lb)
MODEL: 10BX http://www.m-system.co.jp/ 10BX SPECIFICATIONS ES-0891 Rev.12 Page 2/5 PERFORMANCE Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength:
500 V AC @ 1 minute (I/O connector to power)
1500 V AC @ 1 minute (power to FG)
500 V AC @ 1 minute (1000 V for 24 V DC) (I/O connector to
FG) MOUNTING REQUIREMENTS Observe appropriate wiring space under the rack. B 4–M5 SCREW A 57.2 (2.25) < EIA > 15 (.59) 50 (1.97) < JIS > ANGLE BRACKET MODEL SIZE A B 10, 11, 12, 13 10BX-C, D 290 (11.42) 265 (10.43) Observe appropriate wiring space under the rack. B 4–M5 SCREW A 57.2 (2.25) < EIA > 15 (.59) 50 (1.97) < JIS > ANGLE BRACKET MODEL SIZE A B 10, 11, 12, 13 10BX-C, D DIMENSIONS unit: mm (inch) MODEL SIZE A B C 10, 11, 12, 13 10BX-C, D 305 (12.01) 290 (11.42) 260 (10.24) 168.5 (6.63) B 50 (1.97) 7 (.28) 2 (.08) 15 (.59) 57.2 (2.25) A C 207 (8.15) 2 (.08) ■ RACK ■ SURFACE 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 13 14 15 16 POWER INPUT TERMINALS DCS CONNECTOR
MODEL: 10BX http://www.m-system.co.jp/ 10BX SPECIFICATIONS ES-0891 Rev.12 Page 3/5 SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM FG U(+) V(–) POWER CN1 CONNECTOR PWR 24VDC I/O SIGNALS 10-RACK SIGNAL CONDITIONERS *The connector is deleted with some models. ■ 10BX-2, D PWR FG U V POWER CONNECTOR PWR 24VDC 10-RACK SIGNAL CONDITIONERS ■ 10BX-3 PWR FG U V AC POWER DC POWER CONNECTOR PWR 24VDC 10-RACK SIGNAL CONDITIONERS ■ 10BX-11, 12, 13 FG CN1 CONNECTOR PWR 24VDC I/O SIGNALS 10-RACK SIGNAL CONDITIONERS POWER I/O CONNECTOR PIN ASSIGNMENT Fujitsu FCN type I/O connector
- Connector Pin Assignment CN1: Fujitsu FCN-365P040-AU PIN NO. ASSIGNMENT PIN NO. ASSIGNMENT A 1 ch. 1 + B 1 ch. 1 – A 2 ch. 2 + B 2 ch. 2 – A 3 ch. 3 + B 3 ch. 3 – A 4 ch. 4 + B 4 ch. 4 – A 5 ch. 5 + B 5 ch. 5 – A 6 ch. 6 + B 6 ch. 6 – A 7 ch. 7 + B 7 ch. 7 – A 8 ch. 8 + B 8 ch. 8 – A 9 ch. 9 + B 9 ch. 9 – A10 ch.10 + B10 ch.10 – A11 ch.11 + B11 ch.11 – A12 ch.12 + B12 ch.12 – A13 ch.13 + B13 ch.13 – A14 ch.14 + B14 ch.14 – A15 ch.15 + B15 ch.15 – A16 ch.16 + B16 ch.16 – A17 – A20, B17 – B20: Unused Yokogawa DCS VMx / PM1 card use
- Location I/O connector : PS-40PE-D4LT1-PN1 CN1: VM x / PM1 card use (uses KS2 cable) RACK LOCATION NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 VM1/PM1/VM4 CARD INPUT or OUTPUT CN1 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 VM2 CARD INPUT NO. VM2 CARD OUTPUT NO.
1 N C1 N C
VM1: analog input 16 points VM2: analog input 8 points / analog output 8 points VM4: analog output 16 points PM1: pulse input 16 points
MODEL: 10BX http://www.m-system.co.jp/ 10BX SPECIFICATIONS ES-0891 Rev.12 Page 4/5 Omron 3G8B2-NA000 / NA001 use
- Location CN1 : Fujitsu FCN-365P024-AU RACK LOCATION NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 OMRON 3G8B2-NA000 / NA001
- Connector Pin Assignment PIN NO. ASSIGNMENT PIN NO. ASSIGNMENT A 3 NC B 3 ch.9 – 16 (–) A 5 ch. 8 + B 5 ch.16 + A 6 ch. 7 + B 6 ch.15 + A 7 ch. 6 + B 7 ch.14 + A 8 ch. 5 + B 8 ch.13 + A 9 ch. 4 + B 9 ch.12 + A10 ch. 3 + B10 ch.11 + A11 ch. 2 + B11 ch.10 + A12 ch. 1 + B12 ch. 9 + Nippon Shokubai DCS connector
- Location CN1 : HIF3F-34PA-2.54DS RACK LOCATION NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 NIPPON SHOKUBAI DCS LOCATION NO.
- Connector Pin Assignment PIN NO. ASSIGNMENT PIN NO. ASSIGNMENT 1 No Connection 19 ch. 8 – 2 No Connection 20 ch. 8 + 3 ch.16 – 21 ch. 7 – 4 ch.16 + 22 ch. 7 + 5 ch.15 – 23 ch. 6 – 6 ch.15 + 24 ch. 6 + 7 ch.14 – 25 ch. 5 – 8 ch.14 + 26 ch. 5 + 9 ch.13 – 27 ch. 4 – 10 ch.13 + 28 ch. 4 + 11 ch.12 – 29 ch. 3 – 12 ch.12 + 30 ch. 3 + 13 ch.11 – 31 ch. 2 – 14 ch.11 + 32 ch. 2 + 15 ch.10 – 33 ch. 1 – 16 ch.10 + 34 ch. 1 + 17 ch. 9 – 18 ch. 9 + Azbil J-HAM50 / J-HMM00 module use I/O cable : J-RSL / J-RSK J-RRL / J-RRK
- Location Input connector : 57GE-40500-751 CN1 : J-HAM50 / J-HMM00 module use RACK LOCATION NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 AZBIL DCS AI CONNECTOR Azbil J-AOM10 module use I/O cable : J-RSL / J-RSK J-RRL / J-RRK
- Location Output connector : 57GE-40500-751 CN1 : J-AOM10 module use RACK LOCATION NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 AZBIL DCS AO CONNECTOR Azbil J-PIM00 module use I/O cable : J-RSL / J-RSK J-RRL / J-RRK
- Location Output connector : 57GE-40500-751 CN1 : J-PIM00 module use RACK LOCATION NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8 AZBIL DCS PI CONNECTOR The internal power supply is used for excitation of the pulse input module.
MODEL: 10BX http://www.m-system.co.jp/ 10BX SPECIFICATIONS ES-0891 Rev.12 Page 5/5 Specifications are subject to change without notice.