Please be informed that the data shown in this PDF document is generated from our Online Catalog. Please find the complete data in the user documentation. Our General Terms of Use for Downloads are valid. Active redundancy module QUINT ORING with decoupling MOSFET, ACB Technology, DIN rail mounting, 12 V DC ... 24 V DC, 2x 10 A, 1x 20 A Your advantages Service life of the redundant solution is doubled, thanks to uniform distribution of the load• Save energy Permanent monitoring of redundancy Consistent redundancy up to the load Commercial Data Item number 1088206 Packing unit 1 pc Minimum order quantity 1 pc Sales Key C15 Product Key CMRI43 GTIN 4055626887395 Weight per Piece (including packing) 597.7 g Weight per Piece (excluding packing) 320 g Customs tariff number 85049090 Country of origin CN Redundancy module - QUINT4-ORING/12- 24DC/2X10/2X10 1088206 https://www.phoenixcontact.com/us/products/1088206 Nov 16, 2022, 6:27 AM Page 1 (15)

Nominal input voltage range 12 V DC ... 24 V DC Input voltage range 8 V DC ... 29.5 V DC Voltage type of supply voltage DC Nominal input current (IN) 2x 10 A Static Boost (IStat.Boost) 2x 12.5 A Dynamic Boost (IDyn.Boost) 2x 20 A (5 s) Selective Fuse Breaking (ISFB) 2x 60 A (15 ms) Reverse polarity protection < yes60 V DC Intended listed circuit breaker for input protection 60 V DC Intended listed circuit breaker for input protection 16 A (Characteristic B, C) Voltage drop, input/output typ. 0.1 V (IOUT = 10 A) Output data typ. 98.5 % (12 V DC)Efficiency typ. 99 % (24 V DC) Nominal output voltage UIn - 0.1 V Output voltage UIn - 2x 10 ANominal output current (IN) 1x 20 A 2x 12.5 AStatic Boost (IStat.Boost) 1x 25 A 2x 20 A (5 s)Dynamic Boost (IDyn.Boost) 1x 40 A (5 s) 2x 60 A (15 ms)Selective Fuse Breaking (ISFB) 1x 120 A (15 ms) Connection in series No Feedback voltage resistance ≤ 32 V DC Protection against overvoltage at the output (OVP) < 32 V DC 4.08 W (IOUT = 40 A)Power loss nominal load max.

4.25 W (IOUT = 20 A)

Connection labeling 3.1, 3.2 Switch contact (floating) floating

30 V DCMaximum contact load

Signal option Redundancy OK Signal relay 23/24 Connection labeling 3.3, 3.4 Switch contact (floating) floating Redundancy module - QUINT4-ORING/12- 24DC/2X10/2X10 1088206 https://www.phoenixcontact.com/us/products/1088206 Nov 16, 2022, 6:27 AM Page 2 (15)

Position 1.x Conductor connection Connection method Screw connection rigid 0.2 mm² ... 6 mm² flexible 0.2 mm² ... 4 mm² flexible with ferrule without plastic sleeve 0.25 mm² ... 4 mm² flexible with ferrule with plastic sleeve 0.25 mm² ... 4 mm² rigid (AWG) 24 ... 10 Stripping length 8 mm Drive form screw head Slotted L Output Position 2.x Conductor connection Connection method Screw connection rigid 0.2 mm² ... 6 mm² flexible 0.2 mm² ... 4 mm² flexible with ferrule without plastic sleeve 0.25 mm² ... 4 mm² flexible with ferrule with plastic sleeve 0.25 mm² ... 4 mm² rigid (AWG) 24 ... 10 Stripping length 8 mm Drive form screw head Slotted L Signal Position 3.x Conductor connection Connection method Push-in connection rigid 0.2 mm² ... 1 mm² rigid (AWG) 24 ... 16 Stripping length 8 mm LED signaling Redundancy module - QUINT4-ORING/12- 24DC/2X10/2X10 1088206 https://www.phoenixcontact.com/us/products/1088206 Nov 16, 2022, 6:27 AM Page 3 (15)

Types of signaling DC OK (green) Redundancy OK (LED lights up green) I < In (LED lights up green) ACB OK (LED lights up green) ACB OK (sources are slightly asymmetrical) (LED lights up green and yellow) Signal threshold Sources are asymmetrical (LED flashing red) Electrical properties

500 V ACInsulation voltage input, output / housing

710 V DC

Product type Redundancy module > 2101000 h (25 °C) > 1247000 h (40 °C) MTBF (IEC 61709, SN 29500) > 599000 h (60 °C) RoHS Directive 2011/65/EU WEEE Environmental protection directive Reach Insulation characteristics Protection class III Degree of pollution 2 Life expectancy (electrolytic capacitors) Current 20 A Temperature 40 °C Time 295000 h Additional text 12 V DC Life expectancy (electrolytic capacitors) Current 20 A Temperature 40 °C Time 240000 h Additional text 24 V DC Dimensions Dimensional drawing Redundancy module - QUINT4-ORING/12- 24DC/2X10/2X10 1088206 https://www.phoenixcontact.com/us/products/1088206 Nov 16, 2022, 6:27 AM Page 4 (15)

Depth Device depth (DIN rail mounting) 125 mm (Device depth (DIN rail mounting)) Installation dimensions Installation distance right/left 5 mm / 5 mm Installation distance top/bottom 50 mm / 50 mm Alternative assembly Width 122 mm Height 130 mm Depth 36 mm Mounting Mounting type DIN rail mounting Assembly instructions alignable: PN ≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm vertically alignable: PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom Mounting position horizontal DIN rail NS 35, EN 60715 Material specifications Flammability rating according to UL 94 (housing / terminal blocks) Housing material Metal Type of housing Aluminum (AlMg3) Hood version Galvanized sheet steel, free from chrome (VI) Side element version Aluminum Environmental and real-life conditions Ambient conditions Degree of protection IP20 Ambient temperature (operation) -40 °C ... 70 °C (> 60 °C Derating: 2,5 %/K) Ambient temperature (storage/transport) -40 °C ... 85 °C Maximum altitude 5000 m Max. permissible relative humidity (operation) ≤ 100 % (at 25 °C, non-condensing) Shock (operation) 18 ms, 30g, per spatial direction (IEC 60068-2-27) < 15 Hz, amplitude ±2.5 mm (IEC 60068-2-6)Vibration (operation) Standards and regulations Electrical safety Standards/specifications IEC 61010-1 Protective extra-low voltage Standards/specifications EN 61010-1 (SELV) Redundancy module - QUINT4-ORING/12- 24DC/2X10/2X10 1088206 https://www.phoenixcontact.com/us/products/1088206 Nov 16, 2022, 6:27 AM Page 5 (15)

Protective extra-low voltage Standards/specifications IEC 61010-2-201 (PELV) Approval data Shipbuilding Identification DNV UL Identification UL Listed UL 61010-1 UL Identification UL Listed UL 61010-2-201 UL Identification UL 121201 & CSA C22.2 No. 213-17 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location) CSA Identification CAN/CSA-C22.2 No. 61010-1-12 Identification CAN/CSA C22.2 No. 61010-2-201:18 EMC data Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU EN 61000-6-3EMC requirements for noise emission EN 61000-6-4 EN 61000-6-1EMC requirements for noise immunity EN 61000-6-2 EN 55016Conducted noise emission EN 61000-6-3 (Class B) Interference emission Interference emission in accordance with EN 61000-6-3 (residential and commercial) and EN 61000-6-4 (industrial) Noise emission Additional basic standard EN 61000-6-5 (immunity in power station) EN 55016Noise emission EN 61000-6-3 (Class B) Noise immunity Immunity in accordance with EN 61000-6-1 (residential), EN 61000-6-2 (industrial), and EN 61000-6-5 (power station equipment zone 1, 2) DNV GL conducted interference Class B Additional text Bridge and deck area DNV GL noise radiation Class B Additional text Bridge and deck area Electrostatic discharge Standards/regulations EN 61000-4-2 Redundancy module - QUINT4-ORING/12- 24DC/2X10/2X10 1088206 https://www.phoenixcontact.com/us/products/1088206 Nov 16, 2022, 6:27 AM Page 6 (15)

Contact discharge 6 kV (Test Level 3) Discharge in air 8 kV (Test Level 3) Comments Criterion B Electromagnetic HF field Standards/regulations EN 61000-4-3 Electromagnetic HF field Frequency range 80 MHz ... 1 GHz Test field strength 20 V/m (Test Level 3) Frequency range 1 GHz ... 6 GHz Test field strength 10 V/m (Test Level 3) Comments Criterion A Fast transients (burst) Standards/regulations EN 61000-4-4 Fast transients (burst) Input 2 kV (Test Level 3 - asymmetrical) Output 2 kV (Test Level 3 - asymmetrical) Signal 2 kV (Test Level 4 - asymmetrical) Comments Criterion A Surge voltage load (surge) Standards/regulations EN 61000-4-5 0.5 kV (Test Level 2 - symmetrical)Input 1 kV (Test Level 2 - asymmetrical) 0.5 kV (Test Level 2 - symmetrical)Output 1 kV (Test Level 2 - asymmetrical) Comments Criterion A Conducted interference Standards/regulations EN 61000-4-6 Conducted interference I/O/S asymmetrical Frequency range 0.15 MHz ... 80 MHz Comments Criterion A Voltage 10 V (Test Level 3) Criterion A Normal operating behavior within the specified limits. Criterion B Temporary impairment to operational behavior that is corrected by the device itself. Redundancy module - QUINT4-ORING/12- 24DC/2X10/2X10 1088206 https://www.phoenixcontact.com/us/products/1088206 Nov 16, 2022, 6:27 AM Page 7 (15)

Device dimensions (dimensions in mm) Redundancy module - QUINT4-ORING/12- 24DC/2X10/2X10 1088206 https://www.phoenixcontact.com/us/products/1088206 Nov 16, 2022, 6:27 AM Page 8 (15)

3.1 3.2 3.3 3.4 2.1 2.2 2.3 2.4 Output DC 1.1 1.2 1.3 1.4 + − + − + − + − QUINT ORING Ord.No.xxxxxxx Input DC 12-24V Redundancy OK IN OK I<IN 130 Device dimensions (dimensions in mm) Redundancy module - QUINT4-ORING/12- 24DC/2X10/2X10 1088206 https://www.phoenixcontact.com/us/products/1088206 Nov 16, 2022, 6:27 AM Page 9 (15)

1.2 1.4 1.1 1.3 2.1 2.3 Input DC Output DC Functions User Interface Signal 2.2 2.4 3.3 3.4 3.1 3.2 ACB OVP IIn IIn Bargraph OK OK Redundancy INI<IN ACB OK Redundancy OK SCP OVP Block diagram Diagram 5 10 15 20 25 30 35 40 100 IOut [A] Eta [%] = UIn: 24 V DC = UIn: 12 V DC Redundancy module - QUINT4-ORING/12- 24DC/2X10/2X10 1088206 https://www.phoenixcontact.com/us/products/1088206 Nov 16, 2022, 6:27 AM Page 10 (15)

H [m] 100 125 150 175 200 225 P Out = P 125 % 40 °CStat. = PDyn. 200 % 60 °C = PN 100 % 60 °C 0 1000 2000 3000 4000 5000 Output power/installation altitude Redundancy module - QUINT4-ORING/12- 24DC/2X10/2X10 1088206 https://www.phoenixcontact.com/us/products/1088206 Nov 16, 2022, 6:27 AM Page 11 (15)

 IECEE CB Scheme Approval ID: DK-114506-UL Nominal Voltage UN Nominal Current IN Cross Section AWG Cross Section mm2 - -  cULus Listed Approval ID: FILE E 123528 DNV Approval ID: TAA000011F  cULus Listed Approval ID: FILE E 199827 Redundancy module - QUINT4-ORING/12- 24DC/2X10/2X10 1088206 https://www.phoenixcontact.com/us/products/1088206 Nov 16, 2022, 6:27 AM Page 12 (15)

ECLASS-11.0 27371010 ETIM ETIM 8.0 EC000683 UNSPSC UNSPSC 21.0 32151500 Redundancy module - QUINT4-ORING/12- 24DC/2X10/2X10 1088206 https://www.phoenixcontact.com/us/products/1088206 Nov 16, 2022, 6:27 AM Page 13 (15)

Environmental Product Compliance REACh SVHC Lead 7439-92-1 Redundancy module - QUINT4-ORING/12- 24DC/2X10/2X10 1088206 https://www.phoenixcontact.com/us/products/1088206 Nov 16, 2022, 6:27 AM Page 14 (15)

Mounting adapter - UTA 107/30 - 2320089 https://www.phoenixcontact.com/us/products/2320089 Universal DIN rail adapter Mounting adapter Mounting adapter - UWA 182/52 - 2938235 https://www.phoenixcontact.com/us/products/2938235 Universal wall adapter for securely mounting the device in the event of strong vibrations. The device is screwed directly onto the mounting surface. The universal wall adapter is attached on the top/bottom. Phoenix Contact 2022 © - all rights reserved https://www.phoenixcontact.com Phoenix Contact USA

586 Fulling Mill Road

Middletown, PA 17057, United States (+717) 944-1300 info@phoenixcon.com Redundancy module - QUINT4-ORING/12- 24DC/2X10/2X10 1088206 https://www.phoenixcontact.com/us/products/1088206 Nov 16, 2022, 6:27 AM Page 15 (15)