https://www.phoenixcontact.com/us/products/1087081 12/24/2021 Page 1 / 8 I/O module - AXL F EX IS AO4 HART XC 1F - 1087081 Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's documentation. Our General Terms of Use for Downloads are valid (http://phoenixcontact.com/download) technology: 2-conductor, transmission speed in the local bus: 100 Mbps, Extreme conditions version, Intrinsically safe, degree of protection: IP20, including bus base module and Axioline F connectors Product Description The module is an Axioline F I/O module for use in the Axioline F modular I/O system. The module is a modular I/O device that can be affixed to the Axioline P local bus, to communicate I/O data up to the Axioline P bus coupler, which forms the head of the station. The module allows the connection of up to four HART devices. The analog output I/O module with HART capabilities manages analog output and HART data to and from the field I/O terminals and makes this information available to the controller / bus coupler through the Axioline F local bus. As an intrinsic safety I/O module, this device allows direct connection from intrinsically safe field I/O to the terminals of the module. Your advantages 4 analog output-powered control signals for HART Cyclic access to PV, SV, TV, QV, and Loop Current Can be used under extreme ambient conditions Extended temperature range of -40 °C ... +70 °C (see “Tested successfully: use under extreme ambient conditions” in the data sheet) Intrinsically safe analog inputs with connection to Zone 1, Zone 0 or Division 1 Key Commercial Data Packing unit 1 pc GTIN GTIN 4055626882901 Weight per Piece (excluding packing) 380.000 g Country of origin China
https://www.phoenixcontact.com/us/products/1087081 12/24/2021 Page 2 / 8 I/O module - AXL F EX IS AO4 HART XC 1F - 1087081 Technical data Note Utilization restriction EMC: class A product, see manufacturer's declaration in the download area Use in potentially explosive areas is not permitted in China. Dimensions Width 53.6 mm Height 129.9 mm Depth 77.14 mm Note on dimensions The depth is valid when a TH 35-7,5 DIN rail is used (according to EN 60715). Ambient conditions Ambient temperature (operation) -25 °C ... 60 °C (Standard) -40 °C ... 70 °C (Extended, see section “Tested successfully: use under extreme ambient conditions” in the data sheet.) Ambient temperature (storage/transport) -40 °C ... 85 °C Permissible humidity (operation) 5 % ... 95 % (non-condensing) Permissible humidity (storage/transport) 5 % ... 95 % (non-condensing) Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level) Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level) Maximum altitude 3000 m Degree of protection IP20 Connection data Designation Axioline F connector Connection method Push-in connection Note on the connection method Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual. Conductor cross section solid min. 0.2 mm² Conductor cross section solid max. 1.5 mm² Conductor cross section flexible min. 0.2 mm² Conductor cross section flexible max. 1.5 mm² Conductor cross section AWG min. 24 Conductor cross section AWG max. 16 Stripping length 8 mm General Mounting type DIN rail Color traffic grey A RAL 7042 Net weight 235.9 g
https://www.phoenixcontact.com/us/products/1087081 12/24/2021 Page 3 / 8 I/O module - AXL F EX IS AO4 HART XC 1F - 1087081 Technical data General Note on weight specifications with connectors and bus base module Mounting position any (no temperature derating) Maximum altitude 3000 m Interfaces Designation Axioline F local bus Number 2 Connection method Bus base module Transmission speed 100 Mbps Axioline potentials Designation Axioline F local bus supply (UBus) Supply voltage 5 V DC (via bus base module) Current consumption typ. 40 mA max. 60 mA Designation Supply for analog modules (UA) Supply voltage 24 V DC Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple) Current consumption max. 150 mA Electrical isolation Test section 5 V supply of the local bus (UBus) / 24 V supply (I/Os) 500 V AC 50 Hz 1 min.
5 V supply of the local bus (UBus) / functional ground 500 V AC 50 Hz 1
min. 24 V supply (I/O) / functional ground 500 V AC 50 Hz 1 min. Field to functional earth 500 V AC 50 Hz 1 min. Field to 5V or 24V supplies 1500 V AC 50 Hz 1 min. Standards and Regulations Immunity to ESD Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Electrostatic discharge (ESD) EN 61000-4-2/IEC 61000-4-2 Criterion A, 6 kV contact discharge, 8 kV air discharge Immunity to EF Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Electromagnetic fields EN 61000-4-3/IEC 61000-4-3 Criterion A, Field intensity: 10 V/m Immunity to burst Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Fast transients (burst) EN 61000-4-4/IEC 61000-4-4 Criterion B, 2 kV Immunity to surge Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Transient overvoltage (surge) EN 61000-4-5/IEC 61000-4-5 Criterion A, supply lines DC: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical), ±1 kV to shielded I/O cables
https://www.phoenixcontact.com/us/products/1087081 12/24/2021 Page 4 / 8 I/O module - AXL F EX IS AO4 HART XC 1F - 1087081 Technical data Standards and Regulations Immunity to conducted interference Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Conducted interference EN 61000-4-6/IEC 61000-4-6 Criterion A, Test voltage 10 V Interference emission Noise emission test in accordance with EN 61000-6-4/IEC 61000-6-4 Class A Mechanical tests Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g Shock in acc. with EN 60068-2-27/IEC 60068-2-27 30g Continuous shock according to EN 60068-2-27/IEC 60068-2-27 10g Max. output voltage Uo 24.8 V Max. output current Io 86.7 mA Max. output power Po 538 mW Group A, B / IIC Max. external capacitance Co 0.112 µF Additional text (A, B, or IIC) Group C/IIB, IIIC Max. external capacitance Co 0.859 µF Additional text (C, IIB, or IIIC) Group D/IIA, E, F, G, Class III Max. external capacitance Co 3.049 µF Additional text (D, E, F, G, Class III, or IIA) Group A, B / IIC Max. external inductivity Lo 4.1 mH Additional text (A, B, or IIC) Group C/IIB, IIIC Max. external inductivity Lo 18.29 mH Additional text (C, IIB, or IIIC) Group D/IIA, E, F, G, Class III Max. external inductivity Lo 37.21 mH Additional text (D, E, F, G, Class III, or IIA) ATEX DEMKO 20 ATEX 2370X II 3(1)G Ex ec [ia Ga] IIC T4 Gc II (1)D [Ex ia Da] IIIC IECEx IECEx UL 20.0044X Ex ec [ia Ga] IIC T4 Gc [Ex ia Da] IIIC UL, USA / Canada Ind. Cont. Eq. (E238705) also Listed Install in: Class I, Div. 2, Groups A, B, C, D T4 Intrinsically safe outputs for: Class I, Groups A, B, C, D; Class II, Groups E, F, G; Class III; [Ex ia] Haz loc Class I, Zone 2, AEx ec [ia Ga] IIC T4 Gc [AEx ia Da] IIIC
https://www.phoenixcontact.com/us/products/1087081 12/24/2021 Page 5 / 8 I/O module - AXL F EX IS AO4 HART XC 1F - 1087081 Technical data Standards and Regulations Ex ec [ia Ga] IIC T4 Gc [Ex ia Da] IIIC Safety-related maximum voltage Um 250 V Protection class III (IEC 61140, EN 61140, VDE 0140-1) Environmental Product Compliance REACh SVHC Lead 7439-92-1 China RoHS Environmentally Friendly Use Period = 25; For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” Drawings Connection diagram connection drawing missing!!! Dimensional drawing 53,6 77,1 129,9 122,4 Classifications eCl@ss eCl@ss 10.0.1 27242601 eCl@ss 11.0 27242601 eCl@ss 9.0 27242601 UNSPSC UNSPSC 18.0 32151602 UNSPSC 19.0 32151602 UNSPSC 20.0 32151602 UNSPSC 21.0 32151602 Approvals Approvals
https://www.phoenixcontact.com/us/products/1087081 12/24/2021 Page 6 / 8 I/O module - AXL F EX IS AO4 HART XC 1F - 1087081 Approvals Approvals UL Listed / cUL Listed / cULus Listed Ex Approvals ATEX / IECEx / UL Listed / cUL Listed / CCC / cULus Listed Approval details UL Listed http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 238705 cUL Listed http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 238705 cULus Listed Accessories Accessories Device marking Insert label - EMT (35X46)R - 0801604 Insert label, for the Axioline F series from Phoenix Contact, Roll, white, unlabeled, can be labeled with: THERMOMARK ROLLMASTER 300/600, THERMOMARK X1.2, THERMOMARK ROLL X1, THERMOMARK ROLL 2.0, THERMOMARK ROLL, mounting type: snapped, lettering field size: 35 x 46 mm, Number of individual labels: 500 DIN rail connector
https://www.phoenixcontact.com/us/products/1087081 12/24/2021 Page 7 / 8 I/O module - AXL F EX IS AO4 HART XC 1F - 1087081 Accessories Bus connector - AXL F BS F - 2688129 Axioline F bus base module for housing type F Partition plate Separating plate - AXL F/P IO EX PP - 1100201 Axioline F/P partition plate for intrinsically safe modules Shield connection Shield connection - AXL SHIELD SET - 2700518 Axioline shield connection set (contains 2 shield bus holders and 2 SK 5 shield connection clamps) Terminal marking Zack marker strip - ZB 20,3 AXL UNPRINTED - 0829579 Zack marker strip for Axioline F (device labeling), in 2 x 20.3 mm pitch, unprinted, 25-section, for individual labeling with B-STIFT 0.8, X-PEN, or CMS-P1-PLOTTER
https://www.phoenixcontact.com/us/products/1087081 12/24/2021 Page 8 / 8 I/O module - AXL F EX IS AO4 HART XC 1F - 1087081 Accessories Zack Marker strip, flat - ZBF 10/5,8 AXL UNPRINTED - 0829580 Zack Marker strip, flat, Strip, white, unlabeled, can be labeled with: PLOTMARK, CMS-P1-PLOTTER, mounting type: snapped, for terminal block width: 10.15 mm, lettering field size: 4 of 10.15 x 5 mm and 1 of 5.8 x 5 mm, Number of individual labels: 50 Phoenix Contact 2021 © - all rights reserved http://www.phoenixcontact.com