Technical content
Features
– Configurable fault monitoring module –C o n f i g u r a b l e v i a D I P s w i t c h – Approval for Ex-zone 2 (nA) – Screw or spring-cage co nnection can be provided WARNING: Correct usage in potentially explosive areas The module is a category 3 item of electrical equipment. It is absolutely vital to follow the instructions provided here during installation and observe the information in the "Safety regulations and installation notes". Make sure you always use the latest documentation. It can be downloaded from the product at www.phoenixcontact.net/products. This data sheet is valid for all products listed on the following page: 105448_en_00 2013-01-14
105448_en_00 PHOENIX CONTACT 2 2T a b l e o f c o n t e n t s
105448_en_00 PHOENIX CONTACT 3 Description Type Order No. Pcs. / Pkt. The fault monitoring module is used to evaluate and report group errors from the fault monitoring system and to monitor the supply voltages. The error is reported via an N/O contact. Screw connection, standard configu- ration. MINI MCR-SL-FM-RC-NC 2902961 1 The fault monitoring module is used to evaluate and report group errors from the fault monitoring system and to monitor the supply voltages. The error is reported via an N/O contact. Spring-cage connection, standard configuration. MINI MCR-SL-FM-RC-SP-NC 2902962 1 3O r d e r i n g d a t a Accessories Type Order No. Pcs. / Pkt. The MINI MCR-SL-PTB-FM(-SP) power terminal block is used to supply the supply voltage to the T-connector. The FM power terminal block offers the additional function of monitoring in combination with the fault monitor- ing module. Screw connection. MINI MCR-SL-PTB-FM 2902958 1 The MINI MCR-SL-PTB-FM(-SP) power terminal block is used to supply the supply voltage to the T-connector. The FM power terminal block offers the additional function of monitoring in combination with the fault monitor- ing module. Spring-cage connection. MINI MCR-SL-PTB-FM-SP 2902959 1 DIN rail connector (TBUS), 5-pos., for bridging the supply voltage, can be snapped onto NS 35/... DIN rails according to EN 60715 ME 6,2 TBUS-2 1,5/5-ST-3,81 GN 2869728 10 DIN rail power supply unit, primary-switched mode, slim design, output: 24 V DC / 1.5 A MINI-SYS-PS-100-240AC/24DC/1.5 2866983 1 Fold up transparent cover for MINI MCR modules with additional labeling option using insert strips and flat Zack marker strip 6.2 mm MINI MCR DKL 2308111 10 Label for extended marking of MINI MCR modules in connection with the MINI MCR-DKL MINI MCR-DKL-LABEL 2810272 10
4 Technical data
Description of the input Voltage input for redundancy monitoring Voltage input signal 9.6 V DC ... 30 V DC Output Voltage output signal 9.6 V DC ... 30 V DC Max. current output signal 2 A Output description Switching output Maximum switching voltage 30 V DC Max. switching current 50 mA Supply Supply voltage range 9.6 V DC ... 30 V DC (The T connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715)) Max. current consumption < 5 mA (at 24 V DC) Power consumption < 120 mW (at 24 V DC) Diagnostic and status indicators Status display Yellow LED (switching output active), red LED (error)
105448_en_00 PHOENIX CONTACT 4 General data Maximum temperature coefficient < 0.01 %/K Electrical isolation Basic insulation according to EN 61010 Surge voltage category II Degree of protection IP20 Pollution degree 2 Rated insulation voltage 50 V AC/DC Dimensions W / H / D 6.2 mm / 93.1 mm / 102.5 mm Type of housing PBT green Connection data Screw connection Spring-cage conn. Stripping length 12 mm 8 mm Ambient conditions Ambient temperature (operation) -20 °C ... 65 °C Ambient temperature (storage/transport) -40 °C ... 85 °C Conformance with EMC Directive 2004/108/EC Noise immunity according to EN 61000-6-2 When being exposed to interference, there may be minimal deviations. Noise emission according to EN 61000-6-4 Conformance / approvals Conformance CE-compliant ATEX II 3 G Ex nA nC IIC T4 Gc X UL, USA / Canada UL 508 Recognized applied for UL, USA / Canada Class I, Div. 2, Groups A, B, C, D T5 applied for Shipbuilding GL applied for
105448_en_00 PHOENIX CONTACT 5
5 Safety regulations and installation notes
5.1 Installation notes
– The category 3 device is suit able for installation in the zone 2 potentially explosive area. It fulfills the require- ments of EN 60079-0:2009 and EN 60079-15:2010. – Installation, operation, and maintenance may only be car- ried out by qualified electricians. Follow the installation in- structions described. When installing and operating the device, the applicable regulations and safety directives (including national safety directives), as well as general technical regulations, must be observed. The technical data is provided in this package slip and on the certifi- cates (conformity assessment, additional approvals where applicable). – It is not permissible to open or modify the device. Do not repair the device yourself but replace it with an equivalent device. Repairs may only be carried out by the manufac- turer. The manufacturer is not liable for damage resulting from violation. – The IP20 degree of protection (IEC 60529/EN 60529) of the device is intended for use in a clean and dry environ- ment. Do not subject the device to any load that exceeds the described limits. – The device is not designed for use in atmospheres with a danger of dust explosions.
5.2 Installation in the Ex area (zone 2)
– Observe the specified conditions for use in potentially ex- plosive areas. – The device must be installed in a housing (control or dis- tributor box) which meets the requirements of EN 60079- 15 and provides at least IP54 (EN 60529) degree of pro- tection. – During installation and when connecting the supply and signal circuits, observe the requirements of EN 60079- 14. Devices may only be connected to circuits in zone 2 if they are suitable for operation in Ex zone 2 and for the prevailing conditions at the place of use. – In potentially explosive areas, terminals may only be snapped onto or off the DIN rail connector and wires may only be connected or disconnected when the power is switched off. – The device must be stopped and immediately removed from the Ex area if it is damaged, has been subjected to an impermissible load, has been stored incorrectly, or if it malfunctions. – You can download the latest documents for these devic- es from www.phoenixcontact.net/products.
105448_en_00 PHOENIX CONTACT 6
6 Installation
6.1 Connection notes
6.2 Structure
- Supply voltage input 2. Cover 3. Diagnostics LED 4. Groove for ZBF 6 zack marker strip 5. Fault monitoring: N/C contact 6. Drawing off a supply voltage 7. Connection for DIN rail connector 8. Universal snap-on foot for EN DIN rails 9. DIP switch S1
6.3 Block diagram
6.4 Power supply
Supply via the MINI Analog Module Where the total current consumption of the aligned modules does not exceed 400 mA, the power can be supplied directly at the connection terminal blocks of the module. A 400 mA fuse should be connected upstream. Supply via a Power Terminal Block The MINI MCR-SL-PTB-FM power terminal block (Order No. 2902958) or the MINI MCR-SL-PTB-FM-SP power terminal block (Order No. 2902959), which are the same shape, are used to feed the supply voltage to the DIN rail connector. We recommend connecting a 2.5 A slow-blow fuse (e.g., SIBA 179 120.2,5 20x5). Supply via a system power supply unit The system power supply unit with 1.5 A output current con- nects the DIN rail connector to the supply voltage and can therefore be used to supply several modules from the mains. – MINI-SYS-PS-100-240AC/24DC/1.5 (Order No. 2866983) – Potentially explosive areas: MINI-PS-100-240AC/24DC/1.5/EX (Order No. 2866653) NOTE: Electrostatic discharge! The device contains components that can be damaged or destroyed by electrostatic dis- charge. When handling the device, observe the necessary safety precautions against electro- static discharge (ESD) according to EN 61340- 5-1 and EN 61340-5-2. Serial No.
32825 Blomberg, Germany
–SL-FM-RC-NC Ord.–No.: 29 02 96 1 www.phoenixcontact.com Warning – Do n ot seperate when energized II 3 G Ex nA II C T4 Gc X LED1 yl: Open Contact LED2 rd: Fault detected OUT: 9,6...30VDC max. 2A FAULT Monitoring Module
1 S1 4
IN: 9,6...30VDC PWR 1IN PWR 2IN +24V +24V FAULT CONTACT +24V PWR OUT +24V OUT RC OUT RC FM 2 1 + - NOTE: Never connect the supply voltage di- rectly to the DIN rail connector. It is not permit- ted to draw power from the DIN rail connector or from individual modules. IN PWR 1 IN FAULT CONTACT +24V +24V Zone 2 +24V OUT RC OUT RC1 5 2 6 OUT21 PWR OUT +24V PWR 1 IN FM
105448_en_00 PHOENIX CONTACT 7
6.5 Assembly
Figure 3 Mounting and removing – Mount the module on a 35 mm DIN rail according to EN 60715. – When using the DIN rail connector, first place it into the DIN rail (see A – C). It is used to bridge the power supply. It is also absolutely vital that you snap the module and the DIN rail connector into position in the correct direction: the snap-on foot should be at the bottom and the connec- tor on the left.
6.6 Connecting the wires
The module is available in two connection versions: – Screw terminal blocks (for MINI MCR-SL-FM-RC-NC) – Spring-cage terminal blocks (for MINI MCR-SL-FM-RC- SP-NC) Screw connection: Figure 4 Screw connection
- Insert the wire into the corresponding connection terminal block.
- Use a screwdriver to tighten the screw in the opening above the connection terminal block. Spring-cage connection: Figure 5 Spring-cage connection
- Insert a screwdriver into the opening above the connec- tion terminal block.
- Insert the wire into the corresponding connection terminal block. D E C BA www.interface.phoenixcontact.com Serial No. XXXXXXXX A B www.interface.phoenixcontact.com Serial No. XXXXXXXX A B
105448_en_00 PHOENIX CONTACT 8 7F a u l t m o n i t o r i n g F M Fault monitoring simplifies error evaluation in multi-channel isolation amplifier applications using a group error message.
7.1 Fault monitoring for group error detection
- Use MINI Analog signal conditioners that support fault monitoring.
- Connect these signal conditioners to the MINI MCR-SL- FM-RC(-SP)-NC fault monitoring module via the DIN rail connector . Detected errors on the signal input of a MINI Analog isolation amplifier or in the isolation amplifier are reported to the fault monitoring module via the DIN rail connector. The module re- ports the error centrally via an N/C contact.
7.2 Fault monitoring for redundancy monitoring
With "supply via power terminal", the fault monitoring module can be used to monitor the supply voltage in the group. Fail- ure of the supply voltage generates a central message via an N/C contact.
- Install a power terminal and a fault monitoring module of the same shape side-by-side without spacing.
- Bridge terminals 1 to 4 of the power terminal with termi- nals 1 to 4 of the fault monitoring module. Use the provid- ed plug-in bridges FB S2-6 (Order No. 3030336) or normal cables.
7.3 Application options
– When using a power terminal in combination with a fault monitoring module on the DIN rail connector: Redundant voltage supply on the DIN rail connector is possible, re- dundancy can be monitored, the group error can be eval- uated. – When using a fault monitoring module without power ter- minal in the DIN rail connector: Group errors can be mon- itored only. – When using a power terminal in combination with a fault monitoring module without DIN rail connector: Redun- dancy of two supply voltages can be monitored. For additional mechanical redundancy, two power terminals and two fault monitoring mod- ules can be used. Only one supply may be con- nected to each power terminal. In the second fault monitoring module, fault monitoring of ex- ternal measuring transducers must be deacti- vated because evaluation can only take place via a module in a group.
105448_en_00 9PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany www.phoenixcontact.com
8 Configuration
At delivery, all DIP switches are in the "OFF" position. This corresponds to the following standard configuration: – Group error detection “on” – Redundancy monitoring “on” – Relay “active” DIP switch S1 is used to activate and deactivate group error detection, redundancy monitoring of the supply voltages, and the relay. Configure the DIP switches according to the planned applica- tion using the configuration tables. Configuration table
9 Diagnostic indicator
The LEDs indicate the following error states: – LED red: Fault monitoring system detected an error – LED yellow: Fault monitoring relay is open The module can also be configured with the supply voltage not connected.
- = ON DIP S1 1234 Group error detection ON OFF • Redundancy monitoring ON OFF • Fault monitoring relay Active Deacti- vated • No function