Features

– 10/100Base-T(X) auto negotiation – Auto MDI/MDIx switchover –O p e r a t i n g m o d e a n d s peed can be set manually – Link fault pass through (LFP) – Far End Fault signaling (FEF) –B - F O C ( S T R) connection – Mounting on a 35 mm DIN rail – Redundant power supply possible WARNING: Explosion hazard when used in potentially explosive areas The module is a category 3 item of electrical equipment. Follow the instructions provided here during installa- tion and observe the safety instructions. Make sure you always use the latest documentation. It can be downloaded from the product at phoenixcontact.net/products. This data sheet is valid for all products listed on the following page: 104914_en_02 2013-12-16

104914_en_02 PHOENIX CONTACT 2 2T a b l e o f c o n t e n t s

104914_en_02 PHOENIX CONTACT 3 Description Type Order No. Pcs. / Pkt. FO converter with B-FOC (ST®) fiber optic connection (1300 nm), for con- verting 10/100Base-T(X) to multi-mode fiberglass (50/125 µm). Auto nego- tiation and auto MDI(X) function. Comprehensive link diagnostics. DIN-rail mountable, 18 ... 30 V DC supply. FL MC EF 1300 MM ST 2902854 1 3O r d e r i n g d a t a Accessories Type Order No. Pcs. / Pkt. RJ45 connector, shielded, with bend protection sleeve, 2 pieces, gray for straight cables, for assembly on site. For connections that are not crossed, it is recommended that you use the connector set with gray bend protection sleeve. FL PLUG RJ45 GR/2 2744856 1 RJ45 connector, shielded, with bend protection sleeve, 2 pieces, green for crossed cables, for assembly on site. For connections that are crossed, it is recommended that the connector set with green bend protection sleeves is used. FL PLUG RJ45 GN/2 2744571 1 CAT5-SF/UTP cable (J-02YS(ST)C HP 2 x 2 x 24 AWG), heavy-duty instal- lation cable, 2 x 2 x 0.22 mm², solid conductor, shielded, outer sheath: 7.8 mm diameter, inner sheath: 5.75 mm ± 0.15 mm diameter FL CAT5 HEAVY 2744814 1 CAT5-SF/UTP cable (J-LI02YS(ST)C H 2 x 2 x 26 AWG), light-duty, flexi- ble installation cable 2 x 2 x 0.14 mm², stranded, shielded, outer sheath: 5.75 mm ± 0.15 mm diameter FL CAT5 FLEX 2744830 1 Crimping pliers, for assembling the RJ45 plugs FL PLUG RJ45..., for assembly on site FL CRIMPTOOL 2744869 1 DIN rail connector for DIN rail mounting. Universal for TBUS housing. Gold-plated contacts, 5-pos. ME 22,5 TBUS 1,5/ 5-ST-3,81 GN 2707437 50 DIN rail power supply unit, primary-switched mode, narrow design, output: 24 V DC / 1.5 A MINI-SYS-PS-100-240AC/24DC/1.5 2866983 1 DIN rail connector for DIN rail mounting. Universal for TBUS housing. Gold-plated contacts, 5-pos. ME 17,5 TBUS 1,5/ 5-ST-3,81 GN 2709561 10 Assembled fiber optic cable, break-out cable, fiberglass multi-mode 50/125 µm, connector: LC/B-FOC (ST), degree of protection: IP20, for installation in cable ducts or control cabinets, length: 1 m FL MM PATCH 1,0 LC-ST 2989174 1 Assembled fiber optic cable, break-out cable, fiberglass multi-mode 50/125 µm, connector: LC/B-FOC (ST), degree of protection: IP20, for installation in cable ducts or control cabinets, length: 2 m FL MM PATCH 2,0 LC-ST 2989271 1 Assembled FO cable, break out cable, multi-mode fiberglass 50/125 µm, plug: LC / B-FOC (ST), protection type: IP20, for installation in cable ducts or control cabinets, length: 5 m FL MM PATCH 5,0 LC-ST 2901801 1 Assembled FO cable, break out cable, multi-mode fiberglass 50/125 µm, connector: SC Duplex / B-FOC, protection type: IP20, for installation in cable ducts or control cabinets, length: 1 m FL MM PATCH 1,0 SC-ST 2901809 1 Assembled FO cable, break out cable, multi-mode fiberglass 50/125 µm, connector: SC Duplex / B-FOC (ST), protection type: IP20, for installation in cable ducts or control cabinets, length: 2 m FL MM PATCH 2,0 SC-ST 2901810 1 Assembled FO cable, break out cable, multi-mode fiberglass 50/125 µm, connector: SC Duplex / B-FOC (ST), protection type: IP20, for installation in cable ducts or control cabinets, length: 5 m FL MM PATCH 5,0 SC-ST 2901811 1 Assembled FO cable, break out cable, multi-mode fiberglass 50/125 µm, connector: B-FOC (ST) / B-FOC (ST), protection type: IP20, for installation in cable ducts or control cabinets, length: 1 m FL MM PATCH 1,0 ST-ST 2901815 1 Assembled FO cable, break out cable, multi-mode fiberglass 50/125 µm, connector: B-FOC (ST) / B-FOC (ST), protection type: IP20, for installation in cable ducts or control cabinets, length: 2 m FL MM PATCH 2,0 ST-ST 2901816 1 Assembled FO cable, break out cable, multi-mode fiberglass 50/125 µm, connector: B-FOC (ST) / B-FOC (ST), protection type: IP20, for installation in cable ducts or control cabinets, length: 5 m FL MM PATCH 5,0 ST-ST 2901817 1

104914_en_02 PHOENIX CONTACT 4 PROFINET HCS GI fiber cables, duplex 200/230 µm, increased bandwidth for Ethernet applications in particular. Robust PUR outer sheath. Heavy version suitable for drag chains and indoor installation, sold by the meter without plugs FL FOC PN-C-HCS-GI-200/230 2313410 1 RJ45 connector, IP20, CAT5e, 8-pos., with QUICKON fast connection technology, for 26 ... 23 AWG 1-wire and 7-wire conductors, VS-08-RJ45-5-Q/IP20 1656725 1 B-FOC (ST) connector set for standard PROFINET HCS fiber cables with 2.2 mm diameter of the individual elements. Consisting of 4 quick mounting connectors with bend protection for self-assembly. PSM-SET-B-FOC/4-HCS/PN 2313782 1 Accessories Type Order No. Pcs. / Pkt.

4 Technical data

Power supply 18 V DC ... 30 V DC (Screw connection) 18 V DC ... 30 V DC (as an alternative or redundant, via backplane bus contact and system current supply) Typical current consumption < 100 mA (24 V DC) Protective circuit Protection against polarity reversal Electrical isolation (VCC // FE // Ethernet) Test voltage data interface/power supply 1.5 kV rms (50 Hz, 1 min.) Ethernet interface, 10/100BASE-T(X) in acc. with IEEE 802.3u Connection method RJ45 socket, shielded Transmission speed 10/100 MBit/s Transmission length 100 m (twisted pair, shielded) Transmission medium Copper Auto-negotiation modes Auto Link through Link fault pass through MDI-/MDI-X switchover Auto-MDI(X) FO interface Data rate 100 Mbps Connection method B-FOC (ST®) Wavelength 1300 nm Laser protection Class 1 according to DIN EN 60825-1 Transmission length incl. 3 dB system reserve 6.4 km (with F-G 50/125 0,7 dB/km F 1000) 2.8 km (with F-G 50/125 1,6 dB/km F 800) 10 km (with F-G 62,5/125 0,7 dB/km F 1000) 3 km (with F-G 62.5/125 2.6 dB/km F 600) 2 km (with 2GK200/230 GI-HCS) Transmit capacity, minimum ≥ -23.5 dBm ((50/125 µm) dynamic in link mode (average)) ≥ -20 dBm ((62,5/125 µm) dynamic in link mode (average)) Transmit capacity, maximum ≤ -14 dBm ((50/125 µm) dynamic in link mode (average)) ≤ -14 dBm ((62,5/125 µm) dynamic in link mode (average)) Minimum receiver sensitivity -31 dBm (dynamic in link mode (average)) Maximum receiver sensitivity -14 dBm (dynamic in link mode (average))

104914_en_02 PHOENIX CONTACT 5 General data Basic functions Store-and-forward media converter Degree of protection IP20 Dimensions (W/H/D) 22.5 mm x 99 mm x 114.5 mm Weight 120 g Housing material PA 6.6-F R green Free fall in acc. with IEC 60068-2-32 1 m Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5 g, 150 Hz, 2.5 h, in XYZ direction Shock in acc. with EN 60068-2-27/IEC 60068-2-27 25 g, 11 ms period, half-sine shock pulse MTTF (mean time to failure) SN 29500 standard, temperature 25°C, operating cycle 21% (5 days a week, 8 hours a day)

1400 Years

MTTF (mean time to failure) SN 29500 standard, temperature 40°C, operating cycle 34.25% (5 days a week, 12 hours a day)

599 Years

MTTF (mean time to failure) SN 29500 standard, temperature 40°C, operating cycle 100% (7 days a week, 24 hours a day)

101 Years

Ambient temperature (operation) -40 °C ... 65 °C Ambient temperature (storage/transport) -40 °C ... 85 °C Permissible humidity (operation) 30 % ... 95 % (no condensation) Permissible humidity (storage/transport) 30 % ... 95 % (no condensation) Certification / Approvals Conformance CE-compliant Free from substances that could impair the application of coating according to P-VW 3.10.7 57 65 0 VW-AUDI-Seat central standard ATEX  II 3 G Ex nA IIC T4 Gc X  II (2) D [Ex op is Db] IIIC (PTB 06 ATEX 2042 U)  II (2) G [Ex op is Gb] IIC (PTB 06 ATEX 2042 U) UL, USA / Canada cULus listed UL 508 Class I, Zone 2, AEx nA IIC T4 Class I, Zone 2, Ex nA IIC T4 Gc X Class I, Div. 2, Groups A, B, C, D Standards/regulations EN 60950-1

104914_en_02 PHOENIX CONTACT 6

4.1 UL Notes

Conformance with EMC Directive 2004/108/EC Noise immunity according to EN 61000-6-2 Electrostatic discharge EN 61000-4-2 Contact discharge ± 6 kV (Test intensity 3) Discharge in air ± 8 kV (Test intensity 3) Comments Criterion B Electromagnetic HF field EN 61000-4-3 Frequency range 80 MHz ... 3 GHz (Test intensity 3) Field intensity 10 V/m Comments Criterion A Fast transients (burst) EN 61000-4-4 Input ± 2 kV (Test intensity 3) Signal ± 2 kV (Test intensity 3) Comments Criterion B Surge current loads (surge) EN 61000-4-5 Input ± 0.5 kV (DC supply) Signal ± 1 kV (Data line, asymmetrical) Comments Criterion B Conducted interference EN 61000-4-6 Frequency range 0.15 MHz ... 80 MHz Voltage 10 V Comments Criterion A Emitted interference in acc. with EN 61000-6-4 Noise emission EN 55022 Class A, industrial applications Criterion A Normal operating behavior within the specified limits Criterion B Temporary impairment of operating be havior that is corrected by the device itself  INDUSTRIAL CONTROL EQUIPMENT 11AE Wire Range: 24-14 AWG Torque: 5-7 (Lbs-Ins) Environmental designation: "Open Type Device" "Pollution Degree 2 Installation Environment" PROCESS CONTROL EQUIPMENT FOR HAZARDOUS LOCATIONS 31ZN A This equipment is suitable for use in Class I, Zone 2, AEx nA IIC T4; Ex nA IIC T4 Gc X or Class I, Division 2, Groups A, B, C, D or non-hazardous locations only. B Provision shall be made to prevent transient distur bances of more than 140% of the rated supply voltage. C The device must be installed in a Class I, Zone 2 certif ied overall enclosure rated IP54 with tool-accessible only cover or door and in pollution degree 2 environment only. D Unit shall be supplied by Limited Energy circuit according to clause 9.4 of UL 61010-1 3rd edition of Limited Power Source according to clause 2.5 of UL 60950-1 or NEC Class 2. E Conductor temperature rating must be 72°C or higher. F Maximum relative humidity 80% for temperatures up to 31 °C decreasing linearly to 50% relative humidity at 40°C.

104914_en_02 PHOENIX CONTACT 7

5 Safety regulations and installation

5.1 Installation and operation

  • The category 3 device is suitable for installation in po- tentially explosive area zone 2. It fulfills the require- ments of EN 60079-0:2009 and EN 60079-15:2010.
  • Suitable category 2 devices approved for the applica- tion may be connected to the fiber optic interface.
  • Installation, operation, and maintenance may only be carried out by qualified electricians. Follow the installa- tion instructions as described.
  • When installing and operating the device, the applica- ble regulations and safety directives (including national safety directives), as well as general technical regula- tions, must be observed. The technical data is provided in the package slip and on the certificates (conformity assessment, additional approvals where applicable).
  • The device must not be opened or modified apart from the configuration of the DIP switches. Do not repair the device yourself but replace it with an equivalent device. Repairs may only be carried out by the manufacturer. The manufacturer is not liable for damage resulting from a failure to comply.
  • The IP20 protection (IEC 60529/EN 60529) of the de- vice is intended for use in a clean and dry environment. The device must not be subject to mechanical strain and/or thermal loads, which exceed the limits de- scribed.
  • The device is not designed for use in atmospheres with a danger of dust explosions.
  • If dust is present, it is necessary to install into a suitable approved housing, whereby the surface temperature of the housing must be taken into consideration.
  • The switches of the device that can be accessed may only be actuated when the power supply to the device is disconnected.
  • Provisions shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 140%.

5.2 Safety regulations for installation in potentially

  • Observe the specified conditions for use in potentially explosive areas.
  • At the time of installation, use an approved housing (minimum protection IP54), which meets the require- ments of EN 60079-15. Within this context, observe the requirements of IEC 60079-14/EN 60079-14.
  • In zone 2, only connect devices to the supply and signal circuits that are suitable for operation in the Ex zone 2 and the conditions at the installation location.
  • In potentially explosive areas, terminals may only be snapped onto or off the DIN rail connector and wires may only be connected or disconnected when the pow- er is switched off.
  • The device must be stopped and immediately removed from the Ex area if it is damaged, was subject to an im- permissible load, stored incorrectly or if it malfunctions.
  • For reliable operation, the RJ connection must be equipped with a fully functional locking clip. Repair any damaged plug plugs immediately. CAUTION: Observe the following safety notes when us- ing the FO converter. WARNING: Explosion hazard when used in potentially explosive areas Please make sure that the following notes and instructions are observed.

104914_en_02 PHOENIX CONTACT 8

6 Structure

6.1 Dimensions

Figure 1 Housing dimensions

6.2 Block diagram

114 22,5 6145100161451001 VCC FL MC EF 1300 MM ST Ord.-No.: 29 02 854 FEF LINK VCC DC DC GND TD+(1) RD+(3) TD-(2) RD-(6) US2+ US1+ GNDVCC FO TD RD 10/100 B ASE-T(X) µC MBit/s T-Bus

104914_en_02 PHOENIX CONTACT 9

6.3 Function elements

Figure 3 Function elements

6.4 Diagnostics and status indicators

Far End Fault signal (FEF) If in the case of a FO converter the fiber optic connection for transmission fails, the FO converter on the opposite side sends the “No light” signal. This Far End Fault signal is re- ceived by the FO converter with the transmission fault via the receive cable and indicated with the red FEF LED. If the copper connection is interrupted at one of the FO con- verters, data communication for both FO converters in both the optical and copper segment is disabled by the link fault pass through function. In this case, all Link LEDs go out. However, in order that error diagnostics can be carried out, the red FEF LED lights up on the FO converter where the copper segment is interrupted. 1 24 V DC supply voltage 2 24 V DC supply voltage ( Redundancy)

3 Fiber optic (FO) receiver

4 Fiber optic (FO) transmitter

5 RJ45 Ethernet port 10/100 Base-T(X)

6 LED Link/Activity/10/100

7 LED HD/FD

8 LED LINK

9 LED FEF

10 LED VCC

11 Functional earth ground

12 DIP switch

/10 US1 US2 GND GND 211 VCC FL MC EF 1300 MM ST Ord.-No. 29 02 854 FL MC EF 1300 MM ST Ord.-No. 29 02 854 FEF LINK ON Ethernet interface (TP port)

6 Link/Activity/10/100

Flashing 10 Mbps link - active data transmission Green ON 100 Mbps link Flashing 100 Mbps link - active data transmission

7 HD/FD Green OFF Half duplex transmission

ON Full duplex transmission Fiber optics interface (FO port)

8 LINK Yellow ON Fiber optics link avail-

able, no data communi- cation Flashing Data transmission at FO port

9 FEF Red ON Far end fault has

occurred. Remote station reports: "no light". Supply voltage

10 VCC Green ON Supply voltage OK

104914_en_02 PHOENIX CONTACT 10

7 Configuration via DIP switches

Figure 4 Opening the housing

  • Disengage the housing cover with a screwdriver (A).
  • Then carefully pull the PCB out of the housing as far as possible (B). By default, all DIP switches are in the “OFF” position. The copper side of the device operates in “Auto negotiation” mode. Figure 5 DIP switches

7.1 Setting data transmission (DIP 1, DIP 2, and

DIP 3) DIP 1 = OFF: the connected end devices negotiate 10/100 Mbps transmission speed and half/full transmission mode directly. The entire path behaves like a directly con- nected copper cable. DIP 1 = ON: you set the transmission speed and mode man- ually with DIP switches 2 and 3. NOTE: electrostatic discharge! The device contains components that can be damaged or destroyed by electrostatic dis- charge. When handling the device, observe the necessary safety precautions against electrostatic discharge (ESD) according to EN 61340-5-1 and IEC 61340-5-1. Only select the mode of operation when the power is disconnected! The change is activat- ed after renewed power up. Us1 US2 GND GND A A VCC FEF LINK TD RD B DIP ON OFF (default setting)

6 LFP deactivated (local) L FP activated (global)

5 Not used

4 Pass pause frame Drop pause frame

3 Half duplex transmission Full duplex transmission

1 Fixed transmission

DIP 1 OFF Auto negotiation DIP 1 ON DIP 2 OFF 100 Mbps ON 10 Mbps DIP 3 OFF Full duplex transmission ON Half duplex transmission If DIP switch 1 is in the “OFF” position, the po- sition of DIP switch 2 and 3 is not queried. FL MC EF 1300 ONDIP Local Link not used Pass Pause Frame Half Duplex

10 MBit/s

100 MBit/s

OFF (DEFAULT) LED GN - VCC RD - FEF YE - LINK GN - RJ45 GN/YE - RJ45 Device ON Far End Fault Link FO Full Duplex 100/10 MBit/s permanent flashing Activity FO Activity CU ON

104914_en_02 PHOENIX CONTACT 11

7.2 Pause frame (DIP 4)

A pause frame signal can request an Ethernet device to tem- porarily interrupt data transmission. This avoids overloading the partner when, for example, communication takes place with different transmission speeds. DIP 4 = OFF: the device does not respond to an incoming pause frame signal. It is also not forwarded. A pause frame signal cannot be generated by the device itself. The transmission of pause frame signals is negotiated in sections. DIP 4 = ON: the device responds to pause frame signals or forwards them. A pause frame signal can be generated by the device itself.

7.3 Link fault pass through (DIP 6)

The LFP (link fault pass through) function provides perma- nent connection monitoring. The link on the fiber optic con- nection switches off if the connection is lost on the copper side of a FO converter. The FO converter on the other side registers the aborted link via the fiber optic path and likewise interrupts the connection for its twisted pair segment. The entire connection over the optical path is therefore as transparent as it would be were communication purely cop- per-based. Both sides of the network connection can there- fore detect a lost link immediately and respond accordingly. In the event of an error, this keeps the network load low and ensures that redundancy mechanisms can be activated. DIP 6 = OFF: the LFP function is activated. In the event of a fault, the entire connection is disabled (global). DIP 6 = ON: the LFP function is deactivated. In the event of a fault, only the interrupted segment is dis- abled (local). This is useful during startup and in the event of an error.

104914_en_02 PHOENIX CONTACT 12

8 Assembly

8.1 Mounting on a DIN rail

Figure 6 Mounting on a DIN rail

  • To avoid contact resistance, only use clean, corrosion- free 35 mm DIN rails according to DIN EN 60715.
  • Install an end clamp next to the left-hand module to pre- vent the modules from slipping.
  • Place the module onto the DIN rail from above.
  • Push the front of the device toward the mounting sur- face until it audibly snaps into place.
  • The other modules to be contacted are snapped onto the DIN rail next to each other.

8.2 Combined assembly

Figure 7 Combined assembly The DIN rail connector is used to bridge the power supply and communication.

  • Connect the DIN rail connectors (TBUS) (Order No. 2707437, 1 pc. per device) together for a connection station.
  • Push the connected DIN rail connectors into the DIN rail.
  • Place the module onto the DIN rail from above.
  • Push the front of the device toward the mounting sur- face until it audibly snaps into place. A connection station must not consist of more than ten de- vices.

8.3 Removal

  • Push down the locking tab with a screwdriver, needle- nose pliers or similar.
  • Pull the bottom edge of the module away from the mounting surface.
  • Pull the module diagonally upwards away from the DIN rail. CAUTION: Electric shock The device is only intended for operation with SELV according to IEC 60950/EN 60950/ VDE 0805. NOTE: Malfunction Connect the DIN rail to protective earth ground using a grounding terminal block. The devices are grounded when they are snapped onto the DIN rail (installation according to PELV). This ensures that the shielding is effective. Connect protective earth ground with low im- pedance. In this case, it is vital to observe the mounting direction of the module and DIN rail connec- tor: snap-on foot at the bottom and connector on the left! A CB

104914_en_02 PHOENIX CONTACT 13

9 Supply voltage

The device is operated using a 24 V DC SELV.

9.1 Operation as a single device

  • Supply voltage to the device via terminal blocks 1 (24 V) and 2 (0 V).
  • Optional: connect an additional power supply unit to ter- minal blocks 3 and 4 to provide a redundant power sup- ply.

9.2 Combined operation with a system power

  • Connect a system power supply to two DIN rail connec- tors on the left of the group. (MINI-SYS-PS-100-240AC/24DC/1.5, Order No. 2866983 or MINI-PS100-240AC/24DC/1.5/EX, Order No. 2866653 and two DIN rail connectors, Order No. 2709561)
  • A second power supply unit can be used to create a re- dundant supply concept.

10 Twisted pair interface (TP port)

One Ethernet interface in RJ45 format is on the front of the device, which can only be connected to twisted pair cables with an impedance of 100 . The data transmission speed is 10/100 Mbps Figure 8 Pin assignment

  • Push the Ethernet cable with the crimped RJ45 plug into the TP interface until the plug engages with a click. Ob- serve the plug coding. 1 24 V DC supply voltage 2 0 V DC supply voltage 3 24 V DC supply voltage ( Redundancy) 4 0 V DC supply voltage ( Redundancy) VCC FL MC EF 1300 MM ST Ord.-No.: 29 02 054 TD RD FEF LINK 12 34 NOTE: Interference Only use shielded twisted pair cables and cor- responding shielded RJ45 connectors. RD + RD - TD+ TD - n.c. n.c. n.c. n.c. RJ45

104914_en_02 PHOENIX CONTACT 14

11 Fiber optic interface (FO port)

Figure 9 Connect B-FOC (ST R) plug

  • Remove the dust protection cap.
  • Connect the fiber optic cable to the B-FOC (STR)con- nector for the transmit and receive channel. Make sure the coding is in the correct position.
  • Push theconnector spring mechanism downwards.
  • Secure the connection with a quarter turn to the right (B). Figure 10 Signal direction for the fiber connection When connecting two FO converters, note the signal direc- tion of the fiber optics. – Fiber connection “TD” (transmitter) at device 1 – Fiber connection “ RD” (receiver) at device 2 WARNING: Risk of eye injury During operation, do not look directly into transmitter diodes or use visual aids to look into the glass fibers. The infrared light is not visible. Avoid contamination. Remove the dust protection caps just before the connectors are connected! When using fiber optics, observe the fiber op- tic installation guidelines, DB GB IBS SYS FOC ASSEMBLY, Order No. 9423439. VCC FEF LIN K TD RD A B Please note the transmit and receive channel crossover! VCC FL MC EF 1300 MM ST Ord.-No.: 29 02 054 TD RD FEF LINK VCC FL MC EF 1300 MM ST Ord.-No.: 29 02 054 TD RD FEF LINK

104914_en_02 PHOENIX CONTACT 15

12 Error localization

12.1 Normal operation

Figure 11 Diagnostics indicators in normal operation

12.2 Fault on the copper cable

The diagnostics indicator depends on DIP 6. LFP activated, global (DIP 6 = OFF, default setting) Figure 12 LAN fault with LFP activated, global DIP 6 = OFF: by default, all Link LEDs go out in the event of a fault in a twisted pair segment. The red FEF LED indicates the FO converter where the twisted pair segment failed. LFP deactivated, local (DIP 6 = ON) Figure 13 LAN fault with LFP deactivated, local DIP 6 = ON: in the “LFP deactivated, local” setting, only the Link LEDs of the corresponding port go out in the event of a fault in a twisted pair segment. The Link LEDs at the copper port on the other media converter and for the fiber optic con- nection are on. The “LFP deactivated, local” setting there- fore enables more precise diagnostics. US1 US2 GND GND VCCVCC FL MC EF 1300 MM ST Ord.-No. 29 02 854 FL MC EF 1300 MM S T Ord.-No. 2 9 02 854 FEFFEF LINKLINK US1 US2 GND GND VCCVCC FL MC EF 1 300 MM ST Ord .-No. 29 02 854 FL MC EF 1300 MM ST Ord.-N o. 29 02 854 FEFFEF LINKLINK LAN LAN LWL/FO ... VCC FEF LINK VCC VCC FEF LINK VCC US1 US2 GND GND VCCVCC FL M C EF 130

0 MM S

T Ord.-No. 29 02 854 FL M C EF 1 300 MM ST Ord.-N o. 29 02 854 FEFFEF LINKLINK US1 US2 GND GND VCCVCC FL MC E F 1300 MM S T Ord.-No . 29 02 854 FL MC E F 1300 MM ST Ord.-No. 29 02 85 FEFFEF LINKLINK LAN LAN LWL/FO ... VCC FEF LINK VCC VCC FEF LINK VCC x US1 US2 GND GND VCCVCC FL M C EF 1300 MM ST Ord.-No . 29 02 854 FL MC EF 1300 MM ST Ord.-No. 29 02 854 FEFFEF LINKLINK US1 US2 GND GND VCCVCC FL M C EF 1300 M M ST Ord.-N o. 29 02 854FL MC EF 1300 MM ST Ord.-No. 29 02 854 FEFFEF LINKLINK LAN LAN LWL/FO ... VCC FEF LINK VCC VCC FEF LINK VCC x

104914_en_02 16PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany phoenixcontact.com

12.3 Fault on the fiber optic cable

The diagnostics indicator depends on DIP 6. LFP activated, global (DIP 6 = OFF, default setting) Figure 14 Fiber optic fault with LFP activated, global If just one of the optical fibers is interrupted, you can deter- mine which is the affected fiber via the FEF LEDs. If the FEF LED at a media converter lights up, the fiber connected to the transmit port (TD) is interrupted. The entire connection is disabled. LFP deactivated, local (DIP 6 = ON) Figure 15 Fiber optic fault with LFP deactivated, local The red FEF LED lights up if the optical fiber at the transmit port of the device is interrupted. Only the affected segment is disabled, the copper port connections remain. US1 US2 GND GND VCCVCC FL MC EF 1300 MM ST Ord.-No. 29 02 854 FL MC EF 1300 MM ST Ord.-No. 29 02 854 FEFFEF LINKLINK US1 US2 GND GND VCCVCC FL MC EF 1300 MM S T Ord.-No. 29 02 854 FL MC EF

1300 MM ST

.-No. 29 02 854 FEFFEF LINKLINK LAN LAN LWL/FO ... VCC FEF LINK VCC VCC FEF LINK VCC x US1 US2 GND GND VCCVCC FL MC EF 1300 MM S T Ord.-No . 29 02 8 FL MC EF 1300 MM ST Ord.-No. 29 02 854 FEFFEF LINKLINK US1 US2 GND GND VCCVCC FL MC EF 1300 MM ST Ord .-No. 29 02 8 FL MC EF 1300 MM ST Ord.-No. 29 02 854 FEFFEF LINKLINK LAN LAN ... VCC FEF LINK VCC VCC FEF LINK VCC x LWL/FO