DATASHEET SEARCH SITE | WWW.ALLDATASHEET.COM
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 10
Technical content
Features
TRIO-DIODE/12-24DC/2X10/1X20 104278_en_00 PHOENIX CONTACT 2 2T a b l e o f c o n t e n t s 2T a b l e o f C o n t e n t s
TRIO-DIODE/12-24DC/2X10/1X20 104278_en_00 PHOENIX CONTACT 3 Description Type Order No. Pcs. / Pkt. Redundancy module with function monitoring, 12-24 V DC, 2x 10 A, 1x 20 A TRIO-DIODE/12-24DC/2X10/1X20 2866514 1 Input data/output data Input nominal voltage range 12 V DC ... 24 V DC DC input voltage range 10 V DC ... 30 V DC Voltage drop, input/output Approx. 0.5 V Nominal current 2x 10 A (-25°C to +55°C) 1x 20 A (-25°C to +55°C) Maximum current 2x 15 A (-25°C to +40°C) 1x 30 A (-25°C to +40°C) Derating From +55°C to 70°C: 2.5% per Kelvin Efficiency > 97 % Transient surge protection Varistor Protection against polarity reversal Yes, with integrated diode, < 60 V Power consumption Power loss nominal load max. Approx. 10 W Floating redundancy OK Output description Contact closed when U IN1 & UIN2 > 8 V Voltage + 60 V DC Current ≤ 100 mA (short circuit resistant) Status display LED redundancy OK / UIN1& UIN2 > 8 V: LED lights up green General data Insulation voltage input / PE 500 V Insulation voltage output / PE 500 V Degree of protection IP20 Class of protection III, without PE connection MTBF > 10000000 h Type of housing Steel sheet, zinc-plated Side element version Aluminum Dimensions W / H / D (state of delivery) 32 mm / 130 mm / 115 mm Weight 0.37 kg Ambient conditions Ambient temperature (operation) -25 °C ... 70 °C (> 55°C derating) Ambient temperature (storage/transport) -40 °C ... 85 °C Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, no condensation) Vibration (operation) < 15 Hz, amplitude ±2.5 mm Shock 15g in all directions in acc. with IEC 60068-2-27 Pollution degree in acc. with EN 50178 2 Climatic class 3K3 (in acc. with EN 60721) 3O r d e r i n g d a t a
4 Technical data
TRIO-DIODE/12-24DC/2X10/1X20 104278_en_00 PHOENIX CONTACT 4 Standards Electrical Equipment for Machinery EN 60204 Electrical safety (of information technology equipment) EN 60950/VDE 0805 (SELV) Electronic equipment for use in electrical power installations EN 50178/VDE 0160 (PELV) SELV IEC 60950 (SELV) and EN 60204 (PELV) Safe isolation DIN VDE 0100-410 DIN VDE 0106-1010 Protection against electric shock DIN 57100-410 Protection against electric shock, basic requirements for safe isolation in electrical equipment DIN VDE 0106-101 Approvals UL approvals UL/C-UL listed UL 508 UL/C-UL Recognized UL 60950 Conformance with EMC guideline 2004/108/EC and for low-voltage guideline 2006/95/EC Noise immunity according to EN 61000-6-2 Electrostatic discharge EN 61000-4-2 Housing Level 3 Contact discharge 6 kV (Contact discharge) Discharge in air 8 kV (Air discharge) Comments Criterion B Electromagnetic HF field EN 61000-4-3 Housing Level 3 Frequency range 80 MHz ... 3 GHz Field intensity 10 V/m Comments Criterion A Fast transients (burst) EN 61000-4-4 Input 2 kV (level 3 - asymmetrical: conductor to ground) Output 2 kV (level 3 - asymmetrical: conductor to ground) Comments Criterion B Surge current loads (surge) EN 61000-4-5 Input 2 kV (level 3 - asymmetrical: conductor to ground) 1 kV (Level 2 - symmetrical: Conductor to conductor) Output 2 kV (level 3 - asymmetrical: conductor to ground) 1 kV (Level 2 - symmetrical: Conductor to conductor) Comments Criterion B Conducted interference EN 61000-4-6 Input/output Level 3 Frequency range 150 kHz ... 80 MHz Voltage 10 V Comments Criterion A Emitted interference in acc. with EN 61000-6-3 Radio interference voltage in acc. with EN 55011 EN 55011 (EN 5 5022) Class B, area of application: Industry and residential Emitted radio interference in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential Current approvals can be found for the product in the download area.
TRIO-DIODE/12-24DC/2X10/1X20 104278_en_00 PHOENIX CONTACT 5 5S t r u c t u r e TRIO DIODE Redundancy Input DC 12-24 V OK 2x10 A Output DC 20 A In1+ In2+ 143
1 DC input In1/In2:
Input voltage 12 ... 24 V, IN = 2 x 10 A
2 GND signal
3 Floating relay contact
(maximum 60 V, 100 mA, short-circuit-proof) 4 "Redundancy OK" LED, green 5 DC output approximately 0.5 V < DC input
6 Universal snap-on foot for EN DIN rails
[mm2] AWG [Nm] solid stranded Torque O u t p u t 0 . 5-6 0 . 5-4 2 0-1 0 0 . 5-0 . 6 Input data Input nominal voltage range 12 V DC ... 24 V DC DC input voltage range 10 V DC ... 30 V DC Type of connection Screw connection Stripping length 9 mm Output data Nominal output voltage 0.5 V < DC input Type of connection Screw connection Stripping length 14 mm
TRIO-DIODE/12-24DC/2X10/1X20 104278_en_00 PHOENIX CONTACT 6 6B l o c k d i a g r a m +IN2+ +IN1+ 14– 2x 10 A +IN2+ +IN1+ 14– 1x 20 A 7S a f e t y a n d w a r n i n g n o t e s The redundancy modules are built-in devices. Installation and startup must only be carried out by qualified personnel. The country-specific regulations (e.g., VDE, DIN) must be observed. Danger Never carry out work when the power is turned on. Depending on the ambient temperature and the load, the housing can become very hot. CAUTION Before startup please ensure: The connection must be carried out by a competent person and protection against electric shock guaranteed. All input and output lines are dimensioned according to the maximum output current of the device or separately protected. Sufficient convection must be guaranteed.
TRIO-DIODE/12-24DC/2X10/1X20 104278_en_00 PHOENIX CONTACT 7
8 Installation
To ensure sufficient convection, we recommend the following minimum spacing be used between modules: 5 cm for vertical installation and 0 cm for horizontal installation. The redundancy module can be snapped onto all DIN rails in accordance with EN 60715 and must be mounted horizontally (connecting terminal blocks on top and bottom).
9 Installation position
Mounting position: Installation depth 115 mm (+ DIN rail)
TRIO-DIODE/12-24DC/2X10/1X20 104278_en_00 PHOENIX CONTACT 8
10 Mounting on DIN rails
A B Assembly Position the module with the DIN rail guide on the upper edge of the DIN rail, and snap it in with a downward motion. Removing Pull the snap lever open with the aid of a screwdriver and slide the module out at the lower edge of the DIN rail.
11 Input
Connection of the input is made via connection terminal blocks "In1+" and "In2+". The "-" terminal is then only connected when signaling is necessary. You can fasten the connection cables to the housing using cable binders. Make sure that the connecting cables and cable binders used are designed for the surface temperatures on the housing. When tightening the cable binders, the insulation of the connecting cables must not be damaged.
TRIO-DIODE/12-24DC/2X10/1X20 104278_en_00 PHOENIX CONTACT 9
12 Output
The output is connected via the internally connected "+" terminals.
13 Function
12 ... 24 V DC I = 10 AN Power Supply 1 + OUT+ TRIO-DIODE I = 10 AN Power Supply 2 + Input/output To decouple two parallel connected power supplies 1 and 2 with nominal currents of up to 10 A, one redundancy module is necessary. GND 12 ... 24 V DC I = 20 AN Power Supply 1 + OUT+ TRIO-DIODEIn1+ In2+ I = 20 AN Power Supply 2 + OUT+ TRIO-DIODEIn1+ In2+ One redundancy module per power supply is required to decouple power supplies with nominal currents from 10 A to 20 A. Inputs "In1+" and "In2+" of the redundancy module must be connected to the power supply unit using two conductors. This is necessary because the maximum current carrying capacity of 15 A per input must not be exceeded. For connecting the redundancy module to the power supply unit, we recommend using two identical connecting cables (cable length/cable cross sections).
TRIO-DIODE/12-24DC/2X10/1X20 104278_en_00 10PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany • Phone: +49-(0) 5235-3-00 PHOENIX CONTACT • P.O.Box 4100 • Harrisburg • PA 17111-0100 • USA • Phone: +717-944-1300 www.phoenixcontact.com TRIO-DIODE 1 TRIO-DIODE 2 max. 60 V, 100 mA TRIO-DIODE max. 60 V, 100 mA Signaling A floating relay contact and "Redundancy OK" LED are available for monitoring redundancy. In normal operation where input voltage > 8 V DC at input terminals "IN1+" and "IN2+", the relay contact (13/14) is closed and the "Redundancy OK" LED lights up. If the input voltage falls to below the value of 8 V DC at one of the input terminals, the floating relay contact opens and the "Redundancy OK" LED goes out. Floating, current-limited "Redundancy OK" signal contacts are to be connected in series for monitoring redundancy. If monitoring the redundancy is not necessary, the "GND signal" does not need to be connected. -25 40 60 70503020 I [A] T [°C] Thermal behavior The device can be operated at an ambient temperature of -25 °C to +70 °C. For ambient temperatures above +55 , the output current must be reduced by 2.5% per Kelvin increase in temperature.