1035427 PHOENIX | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 8
Technical content
https://www.phoenixcontact.com/us/products/1035427 12/24/2021 Page 1 / 8 I/O module - AXL F DO8/2 2A XC 1H - 1035427 Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's documentation. Our General Terms of Use for Downloads are valid (http://phoenixcontact.com/download) Axioline F XC, Digital output module, Digital outputs: 8, 24 V DC, connection technology: 2-conductor, Extreme conditions version, transmission speed in the local bus: 100 Mbps, degree of protection: IP20, including bus base module and Axioline F connectors The figure shows the standard item Product Description The module is designed for use within an Axioline F station. It is used to output digital signals. The outputs are protected against short circuit and overload. Your advantages 8 digital outputs
24 V DC, 2 A
Connection of actuators in 2-conductor technology Minimum update time of < 100 μs Device rating plate stored Can be used under extreme ambient conditions Extended temperature range of -40 °C ... +70 °C (see “Tested successfully: use under extreme ambient conditions” in the data sheet) Partially coated PCBs Key Commercial Data Packing unit 1 pc GTIN GTIN 4055626541570 Custom tariff number 85389091 Country of origin Germany
https://www.phoenixcontact.com/us/products/1035427 12/24/2021 Page 2 / 8 I/O module - AXL F DO8/2 2A XC 1H - 1035427 Technical data Dimensions Width 35 mm Height 126.1 mm Depth 54 mm Note on dimensions The depth is valid when a TH 35-7,5 DIN rail is used (according to EN 60715). Ambient conditions Ambient temperature (operation) -25 °C ... 60 °C (Standard applications and applications with UL approval) -40 °C ... 70 °C (Extended, see section “Tested successfully: use under extreme ambient conditions” in the data sheet.) Ambient temperature (storage/transport) -40 °C ... 85 °C Permissible humidity (operation) 5 % ... 95 % (non-condensing) Permissible humidity (storage/transport) 5 % ... 95 % (non-condensing) Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level) Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level) Degree of protection IP20 Connection data Designation Axioline F connector Connection method Push-in connection Note on the connection method Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual. Conductor cross section solid min. 0.5 mm² Conductor cross section solid max. 1.5 mm² Conductor cross section flexible min. 0.5 mm² Conductor cross section flexible max. 1.5 mm² Conductor cross section AWG min. 20 Conductor cross section AWG max. 16 Stripping length 8 mm General Mounting type DIN rail Color traffic grey A RAL 7042 Net weight 191.1 g Note on weight specifications with connectors and bus base module Degree of pollution 2 (IEC 60664-1, EN 60664-1) Mounting position any (no temperature derating) Interfaces Designation Axioline F local bus
https://www.phoenixcontact.com/us/products/1035427 12/24/2021 Page 3 / 8 I/O module - AXL F DO8/2 2A XC 1H - 1035427 Technical data Interfaces Number of interfaces 2 Connection method Bus base module Transmission speed 100 Mbps Axioline potentials Designation Axioline F local bus supply (UBus) Supply voltage 5 V DC (via bus base module) Current consumption max. 150 mA (up to HW 01) max. 60 mA (as of HW 02) Power consumption max. 750 mW (up to HW 01) max. 300 mW (as of HW 02) Designation Supply for digital output modules (UO) Supply voltage 24 V DC Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple) Current consumption max. 16 A (Provide external protection; if the total current of 8 A is exceeded, connect the supply at the power connector parallel via both terminal points.) Power consumption max. 480 W (of which 3.5 W are internal losses) Protective circuit Surge protection electronic (35 V, 0.5 s) Reverse polarity protection parallel diode; with external 5 A fuse (only for commissioning) Protection max. 16 A (polarity reversal protection up to 5 A) Digital outputs Output name Digital outputs Number of outputs 8 Connection method Push-in connection Connection technology 2-conductor Protective circuit Short-circuit protection, overload protection of the outputs electronic Output voltage 24 V Nominal output voltage 24 V DC Output current per channel max. 2 A Output current of the device
16 A (Provide external protection; if the total current of 8 A is exceeded,
connect the supply at the power connector parallel via both terminal points.) Nominal load, inductive max. 48 VA (1.2 H, 12 Ω, at nominal load) Nominal load, lamp max. 48 W (at nominal voltage) Nominal load, ohmic max. 48 W (12 Ω, at nominal load) Switching frequency max. 6000 per second (with nominal ohmic load, up to HW 01) Load min. 10 kΩ
https://www.phoenixcontact.com/us/products/1035427 12/24/2021 Page 4 / 8 I/O module - AXL F DO8/2 2A XC 1H - 1035427 Technical data Digital outputs Output voltage when switched off max. 1 V Output current when switched off max. 300 µA Behavior with overload Shutdown with automatic restart Behavior with inductive overload Output can be destroyed Reverse voltage resistance to short pulses limited protection up to 0.5 A for 1 s Electrical isolation Test section 5 V supply of the local bus (UBus) / 24 V supply (I/Os) 500 V AC 50 Hz 1 min.
5 V supply of the local bus (UBus) / functional ground 500 V AC 50 Hz 1
min. 24 V supply (I/O) / functional ground 500 V AC 50 Hz 1 min. Standards and Regulations Immunity to ESD Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Electrostatic discharge (ESD) EN 61000-4-2/IEC 61000-4-2 Criterion B, 6 kV contact discharge, 8 kV air discharge Immunity to EF Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Electromagnetic fields EN 61000-4-3/IEC 61000-4-3 Criterion A, Field intensity: 10 V/m Immunity to burst Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Fast transients (burst) EN 61000-4-4/IEC 61000-4-4 Criterion B, 2 kV Immunity to surge Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Transient overvoltage (surge) EN 61000-4-5/IEC 61000-4-5 Criterion B, DC supply lines: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical) Immunity to conducted interference Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Conducted interference EN 61000-4-6/IEC 61000-4-6 Criterion A, Test voltage 10 V Interference emission Noise emission test according to EN 61000-6-3/IEC 61000-6-3 Class B Mechanical tests Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g Shock in acc. with EN 60068-2-27/IEC 60068-2-27 30g Continuous shock according to EN 60068-2-27/IEC 60068-2-27 10g Protection class III (IEC 61140, EN 61140, VDE 0140-1) Overvoltage category II (IEC 60664-1, EN 60664-1) Environmental Product Compliance REACh SVHC Lead 7439-92-1 China RoHS Environmentally Friendly Use Period = 50 years For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” Drawings
https://www.phoenixcontact.com/us/products/1035427 12/24/2021 Page 5 / 8 I/O module - AXL F DO8/2 2A XC 1H - 1035427 Block diagram D UO 220302 23 2303 220200 FE FE OUT01 ... 08UO 24 V Local bus µC Output circuit UBus Internal wiring of the terminal points Connection diagram OUT 4 OUT 8 OUT 1 OUT 5 Diagram 0 0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1 1,2 1,3 0,5 1,5 2,5 3,5 = 0,5 A = 1,0 A = 1,5 A = 2,0 A Inductance [H] Energy consumption [J] Only with external free running circuit Maximum energy consumption of the outputs when switching off inductive loads with 100 % simultaneity Diagram 0 0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1 1,2 1,3 0,5 1,5 2,5 3,5 = 0,5 A = 1,0 A = 1,5 A = 2,0 A Inductance [H] Energy consumption [J] Only with external free running circuit Maximum energy consumption of the outputs when switching off inductive loads with 50 % simultaneity Dimensional drawing 35 54 122,4126,1
https://www.phoenixcontact.com/us/products/1035427 12/24/2021 Page 6 / 8 I/O module - AXL F DO8/2 2A XC 1H - 1035427 Classifications eCl@ss eCl@ss 10.0.1 27242604 eCl@ss 11.0 27242604 eCl@ss 6.0 27242600 eCl@ss 7.0 27242604 eCl@ss 9.0 27242604 ETIM ETIM 6.0 EC001599 ETIM 7.0 EC001599 UNSPSC UNSPSC 18.0 32151602 UNSPSC 19.0 32151602 UNSPSC 20.0 32151602 UNSPSC 21.0 32151602 Approvals Approvals Approvals BSH / LR / DNV GL / PRS / KR / NK / ABS / BV / cULus Listed / RINA Ex Approvals Approval details BSH 840 LR http://www.lr.org/en LR2001902TA DNV GL https://approvalfinder.dnvgl.com/ TAA00000DF
https://www.phoenixcontact.com/us/products/1035427 12/24/2021 Page 7 / 8 I/O module - AXL F DO8/2 2A XC 1H - 1035427 Approvals PRS http://www.prs.pl/ TE/1020/880590/21 KR http://www.krs.co.kr/eng/main/main.aspx HMB17372-AC002 NK http://www.classnk.or.jp/hp/en/ 14A006 ABS http://www.eagle.org/eagleExternalPortalWEB/ 20-2059154-PDA BV http://www.veristar.com/portal/veristarinfo/generalinfo/ approved/approvedProducts/equipmentAndMaterials 36433/B2 BV cULus Listed http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 238705 RINA http://www.rina.org/en ELE233820XG Accessories Accessories Device marking Insert label - EMT (35X28)R - 0801602 Insert label, Roll, white, unlabeled, can be labeled with: THERMOMARK ROLLMASTER 300/600, THERMOMARK X1.2, THERMOMARK ROLL X1, THERMOMARK ROLL 2.0, THERMOMARK ROLL, mounting type: snapped, lettering field size: 35 x 28 mm, Number of individual labels: 500 DIN rail connector
https://www.phoenixcontact.com/us/products/1035427 12/24/2021 Page 8 / 8 I/O module - AXL F DO8/2 2A XC 1H - 1035427 Accessories Bus connector - AXL F BS H - 2700992 Axioline F bus base module for housing type H Terminal marking Zack marker strip - ZB 20,3 AXL UNPRINTED - 0829579 Zack marker strip for Axioline F (device labeling), in 2 x 20.3 mm pitch, unprinted, 25-section, for individual labeling with B-STIFT 0.8, X-PEN, or CMS-P1-PLOTTER Zack Marker strip, flat - ZBF 10/5,8 AXL UNPRINTED - 0829580 Zack Marker strip, flat, Strip, white, unlabeled, can be labeled with: PLOTMARK, CMS-P1-PLOTTER, mounting type: snapped, for terminal block width: 10.15 mm, lettering field size: 4 of 10.15 x 5 mm and 1 of 5.8 x 5 mm, Number of individual labels: 50 Phoenix Contact 2021 © - all rights reserved http://www.phoenixcontact.com