Technical content

Features

102914_en_02 PHOENIX CONTACT 2 Description Type Order No. Pcs. / Pkt. Electronic monitoring relay for load monitoring in single and three-phase networks, based on the power factor cos ϕ EMD-FL-PF-400 2885809 1 Input data Input name Measuring input Measured value AC sine (10 ... 100 Hz) Nominal input voltage UN (3 N ~ 415/240 V) Input voltage range 1(N) ~ 40 V AC ... 415 V AC 3 (N) ~ 40 V AC ... 415 V AC Maximum input voltage (3 N ~ 500/289 V) Input current range 0.5 A ... 10 A (Connection terminal blocks: L1i and L1k) Overload capacity 12 A permanent Input resistance of voltage input ≥ 1 MΩ Input resistance current input 5 m Ω Maximum temperature coefficient ≤ 0.1 %/K Setting range for response delay 0.1 s ... 40 s Setting range for starting delay 1 s ... 100 s Function Underload, overload, Window Basic accuracy ± 5 % (At cos ϕ = 0.8) Setting accuracy ≤ 5 % (At cos ϕ = 0.8) Repeat accuracy ± 1.8 % Recovery time 500 ms Output data Contact type 2 floating PDT contacts Nominal insulation voltage 250 V AC (in acc. with IEC 60664-1) Interrupting rating (ohmic load) max. 750 VA (3 A/250 V AC, module aligned, ≤ 5 mm spacing)

1250 VA (5 A/250 V AC, module not aligned, ≥ 5 mm spacing)

Output fuse 5 A (fast-blow) Supply Frequency range 48 Hz ... 400 Hz Nominal power consumption 4.5 VA (1.5 W) General data Mains type 1 and 3-phase Service life mechanical Approx. 2 x 107 cycles Service life, electrical 2 x 10 5 cycles at ohmic load, 1000 VA Switching frequency max. 60 (per minute at 100 VA ohmic load) max. 6 (per minute at 1000 VA ohmic load) Operating mode 100% operating factor 2O r d e r i n g d a t a

3 Technical data

102914_en_02 PHOENIX CONTACT 3 Degree of protection IP40 (housing) / IP20 (connection terminal blocks) Pollution degree 2 (according to EN 50178) Surge voltage category III, basic insulation (as per EN 50178) Rated insulation voltage 300 V (According to EN 50178) Assembly on TS 35 profile rail acc. to EN 60715 Mounting position Any Width 22.5 mm Height 113 mm Length 90 mm Type of housing Polyamide PA, self-extinguishing Color green Weight 160 g Connection data Stripping length 8 mm Type of connection Screw connection Tightening torque 1 Nm Ambient conditions Ambient temperature (operation) -25 °C ... 55 °C -25 °C ... 40 °C (corresponds to UL 508) Ambient temperature (storage/transport) -25 °C ... 70 °C Permissible humidity (operation) 15 % ... 85 % Climatic class 3K3 (in acc. with EN 60721) Conformance / approvals Conformity CE compliant UL, USA / Canada UL/C-UL listed UL 508 Conformance with EMC directive 2004/108/EC Immunity to interference according to EN 61000-6-2 Emitted interference according to EN 61000-6-4 Conformance with LV directive 2006/95/EC Electronic equipm. for electrical power installations according to EN 50178 General data (Continued) 4B l o c k d i a g r a m L1I L1K A1 A2 16 26 15 25 18 28U = 24...240 V AC/DC

102914_en_02 PHOENIX CONTACT 4 5S a f e t y n o t e s WARNING: Risk of electric shock Never carry out work when voltage is present. 6S t r u c t u r e L1K L1 L2 L3 16 18 A2 EMD-FL-PF-400 MAX DELAY (s) U/t REL 0,1 COS /c106MIN COS /c106MAX .99 MIN 25 26 28 5 10 100 START (s) I=O Power factor monitor FUNCTION O OL UL U W WL 7 8 9 10 1 "U/t" LED: Supply voltage and starting override 2 "MAX" LED: Upper threshold value 3 "MIN" LED: Lower threshold value 4 "I=0" LED: Load switched off 5 "REL" LED: Output relay 6 "FUNCTION" rotary switch: Function selection 7 "DELAY" potentiometer: Response delay 8 "COSϕMIN" potentiometer: Lower threshold value 9 "COSϕMAX" potentiometer: Upper threshold value 10 "START" potentiometer: Starting override

11 Universal snap-on foot for EN DIN rails

7 Installation

The module can be snapped onto all 35 mm DIN rails according to EN 60715. An integrated wide-range power supply unit enables the connection of a supply voltage in the range from 24 V AC/DC to 240 V AC/DC. WARNING: Risk of electric shock Never carry out work when voltage is present.

102914_en_02 PHOENIX CONTACT 5 8D i a g n o s t i c s The LEDs indicate the following error states: "U/t" LED (Green) – LED ON: Supply voltage present "MIN" and "MAX" LEDs (Red) – LED flashes: Set delay time is running – LED ON: Delay time has elapsed – Both LEDs flash alternately: Lower set threshol d value is greater than upper threshold value "I=0" LED (Yellow) – LED ON: Load is switched off, no current flow between L1i and L1k "REL" LED (Yellow) – LED ON: Output relay has picked up – LED OFF: Output relay has dropped out

9 Connection examples

2 4V~ ~ L1K L1i 15 25 16 18 26 28 N Reset 3 ~ 400 V measuring range, without error memory,

24 V AC supply voltage, IN <1 0A

3 ~ 400 V measuring range, with error memory,

230 V AC supply voltage, IN <1 0A

102914_en_02 PHOENIX CONTACT 6 L1K L1i 15 25 16 18 26 28 N L1K L1i 15 25 16 18 26 28 N Reset 1 ~ 230 V measuring range, without error memory, 3 ~ 400 V measuring range, with error memory,

230 V AC supply voltage, IN >1 0A

10 Function

If an error is present when the monitoring module is activated, output relay "R" remains dropped out and the LED for the corresponding threshold value lights up. For all functions the "MIN" and "MAX" LEDs flash alternately if the minimum value selected is greater than the maximum value. The "FUNCTION" rotary switch is used to set the desired function: – O = Overload monitoring (OVER) – OL = Overload monitoring with error memory (OVER + LATCH) – U = Underload monitoring (UNDER) – UL = Underload monitoring with error memory (UNDER + LATCH) – W = Monitoring of the area between thresholds MIN and MAX (window function) (WIN) – WL = Monitoring of the area between thresholds MIN and MAX (window function) with error memory (WIN + LATCH)

102914_en_02 PHOENIX CONTACT 7 U LED U/t LED MAX LED MIN OL R Max Min OVER+LATCH LED REL, START DELAY DELAY START <DELAY Overload Monitoring (OVER and OVER + LATCH) If the measured power factor exceeds the value set at the "MAX" controller, the set response delay (DELAY) starts (red "MAX" LED flashes). After the delay time has elapsed (red "MAX" LED is ON), output relay "R" drops out (yellow "REL" LED is OFF). If the measured power factor falls below the value set at the "MIN" controller (red "MAX" LED is OFF), output relay "R" picks up again (yellow "REL" LED is ON). If the error memory has been activated (OVER + LATCH) and the measured power factor has exceeded the value set at the "MAX" controller for longer than the set response delay, output relay "R" does not pick up if the power factor falls below the value set at the "MIN" controller. Once the error has been reset (supply voltage interrupted, e.g., using an external button), output relay "R" picks up when the supply voltage is applied again and the measuring cycle starts again once the set starting override (START) has elapsed. U LED U/t LED MAX LED MIN UL R Max Min UNDER+LATCH LED REL, START DELAY DELAY START <DELAY Underload Monitoring (UNDER and UNDER + LATCH) If the measured power factor falls below the value set at the "MIN" controller, the set response delay (DELAY) starts (red "MIN" LED flashes). After the delay time has elapsed (red "MIN" LED is ON), output relay "R" drops out (yellow "REL" LED is OFF). If the measured power factor exceeds the value set at the "MAX" controller, output relay "R" picks up again (yellow "REL" LED is ON). If the error memory has been activated (UNDER + LATCH) and the measured power factor has fallen below the value set at the "MIN" controller for longer than the set response delay, output relay "R" does not pick up if the power factor exceeds the value set at the "MAX" controller. Once the error has been reset (supply voltage interrupted, e.g., using an external button), output relay "R" picks up when the supply voltage is applied again and the measuring cycle starts again once the set starting override (START) has elapsed. U LED U/t LED MAX LED MIN WL R Max Min WIN+LATCH LED REL, START DELAY DELAY <DELAY Window Function (WIN) Output relay "R" picks up (yellow "REL" LED is ON) if the measured power factor exceeds the value set at the "MIN" controller. If the measured power factor exceeds the value set at the "MAX" controller, the set response delay (DELAY) starts (red "MAX" LED flashes). After the delay time has elapsed (red "MAX" LED is ON), output relay "R" drops out (yellow "REL" LED is OFF). The output relay picks up again (yellow "REL" LED is ON) if the measured power factor falls below the maximum value again (red "MAX" LED is OFF). If the measured power factor falls below the value set at the "MIN" controller, the set response delay (DELAY) starts (red "MIN" LED flashes). After the delay time has elapsed (red "MIN" LED is ON), output relay "R" drops out (yellow "REL" LED is OFF).

102914_en_02 8PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany • Phone: +49-(0) 5235-3-00 PHOENIX CONTACT • P.O.Box 4100 • Harrisburg • PA 17111-0100 • USA • Phone: +717-944-1300 www.phoenixcontact.com U LED U/t LED MAX LED MIN WL R Max Min WIN+LATCH LED REL, START DELAY DELAY START START Window Function (WIN + LATCH) If the error memory has been activated (WIN + LATCH), an error that has occurred must be reset by interrupting the supply voltage (e.g., using an external button). Output relay "R" then picks up when the supply voltage is applied again and the measuring cycle starts again once the set starting override (START) has elapsed. U LED U/t LED MAX LED MIN LED I=0 R Max Min LED REL, START START <DELAY Detecting Switched Off Loads If the current flow between L1i and L1k is interrupted (yellow "I=0" LED is ON) and no stored errors are present, output relay "R" picks up or remains picked up (yellow "REL" LED is ON). When the current flow is present again, the measuring cycle starts again once the set starting override (START) has elapsed.