Technical content
Features
– Contact extension module – Basic insulation – Safe isolation (input/output) – Housing width 40 mm – Structure height 56 mm – Four N/O contacts – Two N/C contacts Observe the safety instructions on page 4. Make sure you always use the latest documentation. It can be downloaded at www.download.phoenixcontact.com. A conversion table is available on the Internet at This data sheet is valid for all products listed on the following page: Universal Safety Relay With Positively Driven Contacts
PSR-.../URM/4X1/2X2 102381_02_en PHOENIX CONTACT 2 Ordering Data Technical Data Safety Relays Description Type Order No. Pcs./Pkt.
24 V AC/DC
Universal safety relay with positive-action contacts, screw connection,
4 N/O contacts, 2 N/C contacts, width: 40 mm
PSR-SCF- 24UC/URM/4X1/2X2 2981444 1 Universal safety relay with positive-action contacts, spring-cage connection, PSR-SPF- 24UC/URM/4X1/2X2 2981457 1
120 V AC/DC
Universal safety relay with positive-action contacts, screw connection, PSR-SCF-120UC/URM/4X1/2X2 2981460 1 Universal safety relay with positive-action contacts, spring-cage connection, PSR-SPF-120UC/URM/4X1/2X2 2981473 1 Documentation Description Type Order No. Pcs./Pkt. Application manual for PSR safety relays UM EN SAFETY RELAY APPLICATION 2888712 1 Input Data 24 V AC/DC 120 V AC/DC Nominal input voltage UN 24 V AC/DC 120 V AC/DC Permissible range 0.8 - 1.1 x UN 0.8 - 1.1 x UN Typical current consumption at UN 52 mA 12 mA Typical response time at UN 10 ms 10 ms Typical release time at UN 10 ms 10 ms Output Data Contact type: positive-action contacts class A according to EN 50205 4 N/O contacts, 2 N/C contacts Contact material Silver tin oxide (AgSnO2) Maximum switching voltage 250 V AC/DC Minimum switching voltage 15 V AC/DC Limiting continuous current 1 N/O contact N/C contact 6 A 6 A Maximum inrush current N/O contact N/C contact 6 A 6 A Minimum switching current 25 mA Maximum shutdown power
24 V DC
48 V DC
110 V DC
220 V DC
250 V AC
Ohmic load τ = 0 ms 144 W 288 W 77 W 88 W
1500 VA (750 VA)
Inductive load τ = 40 ms 48 W 40 W 35 W 33 W Minimum switching power 0.4 W Mechanical service life 107 cycles, approx.
PSR-.../URM/4X1/2X2 102381_02_en PHOENIX CONTACT 3 Structure Figure 1 Structure
1 A1, A2: Supply voltage connection
2 13-14, 23-24, 33-34, 43-44: N/O contacts 3 51-52, 61-62: N/C contacts Switching capacity according to DIN EN 60947-5-1/VDE 0660-200 Cycles DC13 AC15 360/h: 24 V: 6 A –
230 V: – 5 A
3600/h: 24 V: 3 A –
230 V: – 3 A
Short-circuit protection of the output circuits, external Enable current paths Signaling current paths NEOZED 10 A gL/gK NEOZED 4 A gL/gK 1 Total current on request. Output Data (Continued) General Data Permissible ambient operating temperature -20 °C ... +55 °C Nominal operating mode 100 % ED Degree of protection according to VDE 0470-1 Housing Connection terminal blocks Installation location IP20 IP20 IP54, minimum Mounting position Any Air and creepage distances between circuits Basic insulation According to DIN EN 50178:1998-04 1 Impulse voltage withstand level 4 kV 1 Pollution degree 2 Surge voltage category III Dimensions (W x H x D) 40 mm x 56 mm x 111 mm Stripping length Screw connection Spring-cage connection 7 mm 10 mm Housing material Polyamide PA, not reinforced 1 Safe isolation, reinforced insulation, and 6 kV between the input circuit and the output contact paths. Tests/Approvals UL applied for
PSR-.../URM/4X1/2X2 102381_02_en PHOENIX CONTACT 4 Safety Instructions Block Diagram Figure 2 Block diagram Connection Notes In order to comply with UL approval, use copper cables that are designed for operating temperatures > 75°C. For reliable and safe-to-touch contacts, strip the cable ends as follows: Screw connection (PSR-SCF-.../URM/4X1/2X2): 7m m Spring-cage connection (PSR-SPF-.../URM/4X1/2X2): 10 mm © PHOENIX CONTACT 05/2006 – During operation, parts of electrical switching devices carry hazardous voltages. – Before working on the device, disconnect the power. – Please observe the safety regulations of electrical engineering and industrial safety and liability associations. Disregarding these safety regulations may result in death, serious personal injury or damage to equipment. – Startup, assembly, modifications, and upgrades may only be carried out by a skilled electrical engineer. – In the event of an error, replace the device immediately. – Repairs, especially if the housing must be opened, may only be carried out by the manufacturer or authorized persons. Otherwise the warranty is invalidated. – According to EN 50205, only one N/O contact and one N/C contact may be used as positively driven contacts. When operating relay modules the operator must meet the requirements for noise emission for electrical and electronic equipment (EN 61000-6-4) on the contact side and, if required, take appropriate measures. /G41 /G31 /G41 /G31 /G41 /G32 /G41 /G32 /G31 /G33 /G31 /G34 /G32 /G33 /G32 /G34 /G33 /G33 /G33 /G34 /G34 /G33 /G34 /G34 /G35 /G31 /G35 /G32 /G36 /G31 /G36 /G32