QUINT-PS-100-240AC/24DC/40 102315_en_02 PHOENIX CONTACT 2 2T a b l e o f c o n t e n t s

QUINT-PS-100-240AC/24DC/40 102315_en_02 PHOENIX CONTACT 3 Description Type Order No. Pcs. / Pkt. DIN rail power supply unit 24 V DC/40 A, primary switched-mode, 1-phase. QUINT-PS-100-240AC/24DC/40 2938879 1 Accessories Type Order No. Pcs. / Pkt. Universal wall adapter UWA 182/52 2938235 1 Input data Input nominal voltage range 110 V AC ... 240 V AC AC input voltage range 85 V AC ... 264 V AC (Derating < 100 V DC: 2.5%/V) DC input voltage range 90 V DC ... 350 V DC (Derating < 110 V DC: 2.5%/V) AC frequency range 45 Hz ... 65 Hz DC frequency range 0 Hz Current consumption Approx. 12.5 A (120 V AC) Approx. 4.5 A (230 V AC) Inrush current limitation < 15 A (typical) I2t < 3.2 A2s Power failure bypass > 20 ms (120 V AC) > 20 ms (230 V AC) Typical response time < 1 s Protective circuitry Transient surge protection Varistor Input fuse, integrated 20 A (fast blow, internal) Recommended backup fuse for mains protection 16 A (characteristic B)

20 A (characteristic B)

Nominal output voltage 24 V DC ±1% Output current 40 A (-25 °C ... 60 °C) 45 A (with POWER BOOST, -25°C ... 40°C permanent) Derating From +60°C to 70°C: 2.5% per Kelvin Current limitation Approx. I BOOST = 45 A (for short circuit) Max. capacitive load Unlimited Control deviation < 1 % (change in load, static 10% ... 90%) < 2 % (change in load, dynamic 10% ... 90%) < 0.1 % (change in input voltage ±10%) Efficiency > 92 % (for 230 V AC and nominal values) Ascent time < 2 ms (U OUT (10% ... 90%)) Residual ripple < 30 mVPP (with nominal values) Peak switching voltages < 50 mV PP (20 MHz) Connection in parallel Yes, for redundancy and increased capacity Connection in series Yes Surge protection against internal surge voltages Yes, limited to approx. 35 V DC Resistance to reverse feed 35 V DC Power consumption Maximum power dissipation idling 28 W Power loss nominal load max. 80 W 3O r d e r i n g d a t a

4 Technical data

QUINT-PS-100-240AC/24DC/40 102315_en_02 PHOENIX CONTACT 4 DC OK active Output description U OUT > 0.9 x UN: High signal Voltage ≤ 24 V Current ≤ 20 mA (short circuit resistant) Status display "DC OK" LED green / UOUT < 0.9 x UN: LED flashing DC OK floating Output description Relay contact, U OUT > 0.9 x UN: Contact closed Voltage ≤ 30 V AC/DC Current ≤ 1 A Status display "DC OK" LED green / General data Insulation voltage input/output 3 kV AC (type test) 2 kV AC (routine test) Insulation voltage input / PE 3 kV AC (type test) 1.5 kV AC (routine test) Insulation voltage output / PE 500 V DC (routine test) Degree of protection IP20 Class of protection I, with PE connection MTBF > 500 000 h in acc. with IEC 61709 (SN 29500) Type of housing AluNox (AlMg1) Dimensions W / H / D (state of delivery) 240 mm / 130 mm / 125 mm Dimensions W / H / D (90° turned) 122 mm / 130 mm / 243 mm Weight 3.5 kg Ambient conditions Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C derating) Ambient temperature (storage/transport) -40 °C ... 85 °C Max. permissible relative humidity (operation) 95 % (at 25 °C, no condensation) Vibration (operation) < 15 Hz, amplitude ±2.5 mm in acc. with IEC 60068-2-6 Shock 30g in all directions in acc. with IEC 60068-2-27 Pollution degree in acc. with EN 50178 2 Climatic class 3K3 (in acc. with EN 60721) Standards Electrical Equipment for Machinery EN 60204 / Surge voltage category III Safety transformers for power supply units EN 61558-2-17 Electrical safety (of information technology equipment) EN 60950/VDE 0805 (SELV) EN 61558-2-17 Electronic equipment for use in electrical power installations EN 50178/VDE 0160 (PELV) SELV EN 60950 (SELV) EN 60204 (PELV) Safe isolation DIN VDE 0100-410 DIN VDE 0106-1010 Protection against electric shock DIN 57100-410 Protection against electric shock, basic requirements for safe isolation in electrical equipment DIN VDE 0106-101 Limitation of mains harmonic currents EN 61000-3-2 Device safety GS (tested safety) Certificate CB Scheme

QUINT-PS-100-240AC/24DC/40 102315_en_02 PHOENIX CONTACT 5 Approvals UL approvals UL/C-UL listed UL 508 UL/C-UL Recognized UL 60950 UL/C-UL Listed UL 1604 Class I, Division 2, Groups A, B, C, D Shipbuilding Germanischer Lloyd (EMC 2), ABS, DNV Conformance with EMC guideline 2004/108/EC and for low-voltage guideline 2006/95/EC Noise immunity according to EN 61000-6-2 Electrostatic discharge EN 61000-4-2 Housing Level 4 Contact discharge 8 kV Discharge in air 15 kV Comments Criterion B Electromagnetic HF field EN 61000-4-3 Housing Level 3 Frequency range 80 MHz ... 1 GHz Field intensity 10 V/m Frequency range 1.4 GHz ... 2 GHz Field intensity 10 V/m Comments Criterion A Fast transients (burst) EN 61000-4-4 Input 4 kV (level 4 - asymmetrical) Output 2 kV (Level 3 - asymmetrical) Signal 1 kV (Level 2 - asymmetrical) Comments Surge current loads (surge) EN 61000-4-5 Input 4 kV (inst. class 4 - asymmetrical: conductor to ground) 2 kV (Inst. Class 4 – symmetrical: Conductor to ground) Output 0.5 kV (level 1 - asymmetrical: conductor to ground) 0.5 kV (Level 1 - symmetrical: Conductor to ground) Signal 1 kV (level 2 - asymmetrical: conductor to ground) Comments Criterion B Conducted interference EN 61000-4-6 Input/Output/Signal Level 3 - asymmetrical Frequency range 0.15 MHz ... 80 MHz Voltage 10 V Comments Criterion A Voltage dips EN 61000-4-11 Input (mains buffering > 20 ms) Comments Criterion B Emitted interference in acc. with EN 61000-6-3 Radio interference voltage in acc. with EN 55011 EN 55011 (EN 5 5022) Class B, area of application: Industry and residential Emitted radio interference in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential Current approvals can be found for the product in the download area.

QUINT-PS-100-240AC/24DC/40 102315_en_02 PHOENIX CONTACT 6 5S t r u c t u r e

1 AC input

2 DC output

3 DC OK output active

4 DC OK output, floating

6 "DC OK" LED, green

7 DIN rail adapter

[mm2] AWG [Nm] solid stranded Torque Input 0.2 - 6 0.2 - 4 24 - 10 0.5 - 0.6 Output 0.5 - 16 0.5 - 10 20 - 6 0.5 - 0.6 S i g n a l 0 . 2-6 0 . 2-4 2 4-1 0 0 . 5-0 . 6 Input data Input nominal voltage range 110 V AC ... 240 V AC AC input voltage range 85 V AC ... 264 V AC (Derating < 100 V DC: 2.5%/V) DC input voltage range 90 V DC ... 3 50 V DC (Derating < 110 V DC: 2.5%/V) AC frequency range 45 Hz ... 65 Hz DC frequency range 0 Hz Input fuse, integrated 20 A (fast blow, internal) Recommended backup fuse for mains protection 16 A (characteristic B) Type of connection Screw connection Stripping length 7 mm Output data Nominal output voltage 24 V DC ±1% Output current 40 A (-25 °C ... 60 °C) 45 A (with POWER BOOST, -25°C ... 40°C permanent) Type of connection Screw connection Stripping length 10 mm

QUINT-PS-100-240AC/24DC/40 102315_en_02 PHOENIX CONTACT 7 6B l o c k d i a g r a m L (+) N (-) PE DC OK PFC active 7S a f e t y a n d w a r n i n g n o t e s DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area. DANGER The device contains dangerous live elements and high levels of stored energy. Never carry out work when the power is turned on. Before startup please ensure: The mains connection has been carried out by a competent person and protection against electric shock is guaranteed! The device can be disconnected outside the power supply unit in accordance with the regulations as in EN 60950 (e.g. through primary side line protection)! The ground conductor is connected! All feed lines are sufficiently protected and dimensioned! All output lines are dimensioned according to the maximum output current of the device or separately protected! Sufficient convection must be guaranteed. CAUTION The power supply units are built-in devices. The device may only be installed and put into operation by qualified personnel. The corresponding national regulations must be observed.

QUINT-PS-100-240AC/24DC/40 102315_en_02 PHOENIX CONTACT 8

8 Installation

Note: To ensure sufficient convection, we recommend the following minimum spacing be used between modules: 5 cm for vertical installation and 0 cm for horizontal installation. The power supply unit can be snapped onto all DIN rails in acc. with EN 60715. They must be mounted horizontally (connecting terminal blocks bottom).

9 Installation position

Low-profile installation: Installation depth 125 mm (+ DIN rail) Mounting position rotated 90°: Installation depth 243 mm (+ DIN rail)

QUINT-PS-100-240AC/24DC/40 102315_en_02 PHOENIX CONTACT 9

10 Mounting on DIN rails

A B B A Low-profile installation Assembly: Position the module with the DIN rail guide on the upper edge of the DIN rail, and snap it in with a downward motion. Removing: Pull the snap lever open with the aid of a screwdriver and slide the module out at the lower edge of the DIN rail. Mounting position rotated 90° For a mounting position rotated at 90° to the DIN rail, mount the DIN rail adapter (UTA 107) as shown in the figure. No

QUINT-PS-100-240AC/24DC/40 102315_en_02 PHOENIX CONTACT 10 11 Connection, network form s 100...240 V AC networks +LN −PE PE N L +LN −PE PEN L +LN −PE PEN L +LN −PE L2(N) +LN −PE PE N +LN −PE PEN +LN −PE N +LN −PE TN-S TN-C TT iT The connection for 100 V AC ... 240 V AC is established using the L, N, and P screw connections. The device can be connected to 1-phase AC networks or to two of the phase conductors of three-phase systems (TN, TT or IT systems in accordance with VDE 0100-300/IEC 60364-3) with nominal voltages of 100 V AC ... 240 V AC. The device also continues to work on short-term input voltages > 300 V AC. ATTENTION Suggestion: In AC connections, connect a maximum of one power supply unit to a fuse or a power switch. In order to comply with UL approval, use copper cables with an operating temperature of > 75°C (ambient temperature < 55°C) and > 90°C (ambient temperature < 75°C). To meet EN 60950/UL 60950, flexible cables must be fitted with ferrules. To meet GL requirements, unused terminal compartments should be closed. For reliable and safe-to-touch connections, strip the cable ends according to the table in the "Structure" section.

QUINT-PS-100-240AC/24DC/40 102315_en_02 PHOENIX CONTACT 11

12 Input

Protection of the primary side The device must be installed in acc. with the regulations as in EN 60950. It must be possible to disconnect the device using a suitable isolating facility outside the power supply. The primary side line protection, for example, is suitable. For device protection, there is an internal fuse. Additional device protection is not necessary. Permissible backup fuse for mains protection Power circuit-breaker 16 A or 25 A, characteristic B (or identical function). In DC applications, a suitable backup fuse must be wired in! CAUTION If an internal fuse is triggered, there is a device malfunction. In this case, the device must be inspected in the factory.

13 Output

The connection is established via the screw connections on the screw connection of the DC output:

24 V DC: "+" and "–"; DC OK switching output active: "DC OK"

and "–"; DC OK output floating: "13" and "14". The output voltage set upon delivery is 24 V DC. The output voltage can be set on the potentiometer. Protection of the secondary side The device is electronically protected against short-circuit and idling. In the event of a malfunction, the output voltage is limited to 35 V DC. Make sure that all output lines are dimensioned according to the maximum output current or are separately protected! The cables on the secondary side should have large cross sections in order to keep the voltage drops on the lines as low as possible. ATTENTION Make sure that all output lines are dimensioned according to the maximum output current or are separately protected. The cables on the secondary side must have sufficiently large cross sections in order to keep the voltage drops on the lines as low as possible.

QUINT-PS-100-240AC/24DC/40 102315_en_02 PHOENIX CONTACT 12

14 Signaling

The active DC OK signal output and the floating DC OK signal contact are provided to monitor the function. In addition, the DC OK LED can be used to evaluate the function of the power supply directly at the installation location (see output characteristic curve). I < IN UOUT < 0.9 x UN "DC OK" LED ON Flashing Active DC OK switching output ON OFF Floating DC OK output Closed Open Meaning Normal operation of the power supply unit (UOUT >2 1 . 5V ) Overload mode, e.g. consumer short circuit or overload +DC OK13 14 + --- DC OK Output 24 VD C max. 30 V AC/DC 1 A (60 V DC 0,5 Floating contact The floating signal contact opens and indicates that the set output voltage has been undershot by more than 10 %. Signals and ohmic loads up to a maximum of 30 V AC/DC and currents to a maximum of 1 A (or maximum of 60 V DC with a maximum of 0.5 A) can be switched. For heavily inductive loads such as a relay, a suitable protection circuit (e.g., damping diode) is necessary. DC OK +DC OK13 14 + --- Output 24 VD C

24 V DC/20 mA

The 24 V DC signal is applied between the "DC OK" and "–" connecting terminal blocks and can carry up to 40 mA. This signal output signalizes when the output voltage is more than 10% below the output voltage by switching from "active high" to "low". The DC OK signal is decoupled from the power output. It is thus not possible for parallel switched devices to provide external supply. The 24 V DC signal can be directly connected to a logic input for evaluation.

QUINT-PS-100-240AC/24DC/40 102315_en_02 PHOENIX CONTACT 13 DC OK +DC OK13 14 + --- Output 24 VD C +DC OK13 14 + --- Output 24 VD C 1 2 Signal loop Monitoring two devices: Use the active signal output of device 1 and loop in the floating signal output of device 2. In the event of malfunctioning, a common alarm is output. Any number of devices can be looped in. This signal combination saves wiring costs and logic inputs.

15 Function

I [A]OUT U [V] OUT UN IN I<I N U< 0, 9xU N I>I N IBOOST Output characteristic curve The power supply works with the static POWER BOOST power reserve as shown in the U/I characteristic curve in the figure. At ambient temperatures Tamb <+ 4 0° C , IBOOST is available continuously. At higher temperatures, it is available for a few minutes. In the event of a secondary-side short circuit or overload, the output current is limited to IBOOST. Thereby, the module does not switch off, but rather supplies a continuous output current. The secondary voltage is reduced here until the short circuit is eliminated. The U/I characteristic curve with the POWER BOOST power reserve ensures that both high inrush currents of capacitive loads as well as loads with DC/DC converters in the primary circuit can be supplied. In order to trip standard circuit breakers magnetically and therefore quickly, power supply units have to provide a multiple of the nominal current for a short time. The characteristic curve shows when I < I N, I > IN and U is < 0.9 x UN. The "signaling" table is to be consulted for the respective signaling. UN = 24 V IN = 40 A IBoost = 45 A PN = 960 W PBoost = 1080 W

QUINT-PS-100-240AC/24DC/40 102315_en_02 PHOENIX CONTACT 14 IN 20 40 60 Ambient temperature [°C] Output current [A] Thermal behavior With an ambient temperature of up to +40°C, the device supplies the continuous output current of IBOOST. The device can supply a nominal output current of IN with ambient temperatures of up to +60°C. In the case of ambient temperatures above +60°C, the output current must be reduced by 2.5% per Kelvin increase in temperature. The device does not switch off at ambient temperatures of +70°C or thermal overload. The output capacity is reduced as far as necessary to provide device protection. After it has cooled down, the output capacity is increased again. Parallel operation Devices of the same type can be connected in parallel to increase both redundancy and power. By default upon delivery, no further adjustments are required. If the output voltage is adjusted, a uniform distribution of power is guaranteed by setting all parallel operated power supply units to exactly the same output voltage. To ensure symmetrical current distribution we recommend that all cable connections from the power supply unit to the busbar are the same length and have the same cross section. Depending on the system, for parallel connection of more than two power supplies a protective circuit should be installed at each individual device output (e.g., decoupling diode, DC fuse or circuit breaker). This prevents high return currents in the event of a secondary device fault. IN − + IN Σ =I N Redundant operation Redundant circuits are suitable for the supply of systems which make especially high requirements on the operational safety. If a fault occurs in the primary circuit of the first power supply unit, the second device automatically takes over the entire power supply, without interruption, and vice versa. For this reason, the power supply units to be connected in parallel are dimensioned in such a way that the total current requirement of all consumers can be completely covered by one power supply unit. 100% redundancy makes external decoupling diodes necessary (QUINT-DIODE/40, Order No. 2938963)!

QUINT-PS-100-240AC/24DC/40 102315_en_02 15PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany • Phone: +49-(0) 5235-3-00 PHOENIX CONTACT • P.O.Box 4100 • Harrisburg • PA 17111-0100 • USA • Phone: +717-944-1300 www.phoenixcontact.com IN − + IN Σ = 2 xI N Increased performance For n parallel connected devices, the output current can be increased to n x IN. Parallel connection for increasing power is used when extending existing systems. A parallel connection is recommended if the power supply unit does not cover the current consumption of the most powerful load. Otherwise, the load should be divided between individual devices that are independent from one another.