Technical content
Features
Electronic Reversing-Load Relay ELR W 3/9... electronic reversing-load relays are the practical and user-friendly further development of electronic load relays for 3-phase networks. These components feature high switching frequencies, virtually unlimited service life, no spark interference, and completely silent switching at zero voltage crossing. The compact, DIN rail-mountable modules meet all the requirements of an electronic reversing contactor circuit that has been designed specifically for industrial applications. Both the interlocking of control inputs and the complete wiring of the load contacts are incorporated in the device. Costly locking switches and contact wiring are thus a thing of the past. Cabling has been reduced to an absolute minimum. Only the following must be applied: – Control voltage, supply voltage input and output – 3-phase load The status is clearly indicated by separate LEDs for "right rotation", "left rotation", "operating voltage" or "impermissible control". A short circuit between two phases at the moment of switching is prevented by the integrated delay between the control pulse and the load control. RCV protective circuits on the output side reduce voltage peaks that occur in the load circuit to a safe level and prevent damage to the output electronics. Version With Flat-Ribbon Cable Connector and Motor Protection Relay ELR W 3/9-.../FLK/PLC-MS 9 are also equipped with a motor protection relay (MS 9). The nominal current of the MS 9 can be preselected linearly in the range from 6 A - 9 A. If the nominal current is exceeded due to overload or phase failure, the MS 9 disconnects the electronic load relay via alarm contacts. The error is indicated via an LED and also provided as a 24 V signal. In automatic mode, the ELR is automatically reactivated once the integrated bimetals have cooled down. In manual mode, a reset must be carried out manually. An integrated test function enables the thermal trigger mechanism to be simulated and thus permits the wiring to be checked before startup. In accordance with DIN VDE 0110 and DIN VDE 0636, a conductor cross section of 1.5 mm2 (16 AWG), which must be fitted with one fuse each (10 A slow-blow as mains protection), is required to connect the electronic load relay to the 3-phase network. Electronic Reversing-Load Relay for 3-Phase Networks With Flat-Ribbon Cable Connector and Motor Protection Relay
ELR W 3/9-.../FLK/PLC-MS 9 2 102154_00_en Technical Data Input Data (Input) Operating voltage 24 V DC +25%; -20% 1
1 The operating voltage and control voltage inputs must be operated with power supply
modules according to DIN 19240 (maximum 5% residual ripple). To prevent the inductive or capacitive coupling of disturbing pulses in long control cables, we recommend the use of shielded cables. Maximum current consumption 40 mA Control voltage right/left 24 V DC +25%; -20% 1 Input current right/left 6 mA, approximately Right rotation/left rotation switchover time (switch-on time) 20 ms Input wiring LED, diode for protection against polarity reversal, surge protection Output Data (Output) ELR W 3/9-400/FLK/PLC- MS 9 ELR W 3/9-500/FLK/PLC- MS 9 Operating voltage (conductor voltage)
50 Hz/60 Hz
400 V AC 500 V AC
Operating voltage range 110 V AC - 440 V AC 110 V AC - 550 V AC Reverse voltage 1000 V 1200 V Maximum continuous load current 3 x 9 A Load current depending on the ambient operating temperature Operating time: 100% operating factor Figure 1 Load current depending on the ambient operating temperature Ambient operating temperature [°C] Load current [A]
ELR W 3/9-.../FLK/PLC-MS 9 102154_00_en 3 Power dissipation depending on the load current Operating time: 100% operating factor Figure 2 Power dissipation depending on the load current Surge current 230 A (t = 10 ms) Minimum load current 150 mA Residual voltage at IN 1.7 V, typical Residual current in the OFF state 6 mA, typical Reversing frequency right rotation/left rotation (cos ϕ = 0.5)
10 Hz, maximum
Output wiring RCV circuit, red LED (error message) Motor protection relay Can be set from 6 A to 9 A (additional ranges available on request) Output Data (Output) (Continued) ELR W 3/9-400/FLK/PLC- MS 9 ELR W 3/9-500/FLK/PLC- MS 9 Current per phase [A] Power dissipation [W] 1.5 4.5 7.5 General Data Housing dimensions (length x width x height) 142 mm x 62 mm x 115 mm (5.591 x 2.441 x 4.528 in.) Insulating housing version Polycarbonate (PC), color: green Test voltage I/O 2.5 kV rms Ambient operating temperature range -20°C to +60°C (-4°F to +140°F) Standards/specifications EN 61000-4-4/DIN EN 61000-4-4/VDE 0847-4-4; EN 61000-4-5/DIN EN 61000-4-5/VDE 0847-4-5; IEC 60664/IEC 60664 A/DIN VDE 0110, basic insulation Degree of protection according to IEC 60529/EN 60529/DIN VDE 0470-1 IP20 Mounting position Vertical (DIN rail horizontal) Mounting Can be mounted with spacing ≥ 20 mm (0.787 in.)
ELR W 3/9-.../FLK/PLC-MS 9 102154_00_en 5 Block Diagram Figure 5 Block diagram Alarm
ELR W 3/9-.../FLK/PLC-MS 9 6 102154_00_en © PHOENIX CONTACT 01/2005 Technical modifications reserved PHOENIX CONTACT GmbH & Co. KG Flachsmarktstr. 8
32825 Blomberg
+49 - 52 35 - 30 0 +49 - 52 35 - 34 12 00 www.phoenixcontact.com Worldwide Locations: www.phoenixcontact.com/salesnetwork Ordering Data Description Order Designation Order No. Electronic reversing-load relay for directly controlling devices in a 3-phase network, with LED, protective circuit, flat-ribbon cable connector, and motor protection relay. ELR W 3/9-400/FLK/PLC-MS 9 29 64 20 9 ELR W 3/9-500/FLK/PLC-MS 9 29 64 75 9 Motor protection relay MS 9 29 41 89 5 For marking systems and assembly material, see CLIPLINE catalog. Make sure you always use the latest documentation. It can be downloaded from www.download.phoenixcontact.com.