102149 PHOENIX | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 4
Technical content
Features
Electronic load relays with motor management (ELR-MM) combine fast, wear-resistant, semiconductor switches and modern measurement and evaluation electronics. The active-power input of electrical drives is calculated every 6.6 ms from three currents, voltages, and the phase angle. This enables continuous status monitoring. Freely parameterizable signaling and switching thresholds for detecting under/overloads provide functions that far exceed standard motor protection. All relevant electrical values such as apparent power, active power, reactive power, currents, voltages, and phase angles, as well as the values of the internal cycle counter and elapsed-time meter can be requested via the display. Actuators and variable-speed drives, pumps, and tools are switched using the ELR-MM load relay and at the same time monitored and protected against dirt or wear. As an option, the devices can be coupled to fieldbus systems via a defined interface for online monitoring. Technical Data Input Data ELR W 3/9-400 MM ELR W 3/2-400 MM ELR W 3/9-500 MM Operating voltage UB 24 V DC ±20% Maximum current consumption 80 mA Control voltage right/left 24 V DC ±20% Input current right/left 7 mA 5 mA 7 mA Input wiring LED, diode for protection against polarity reversal, surge protection Output Data Confirmation Contacts O1 - O4 With 1 signal U B - 1 V/50 mA, maximum Output Data Load Side ELR W 3/9-400 MM ELR W 3/2-400 MM ELR W 3/9-500 MM Operating voltage (conductor voltage)
50 Hz/60 Hz
110 V AC -
435 V AC
110 V AC - 550 V AC
Reverse voltage 1000 V 1500 V Load current (see derating curve on page 2) 3 x 8 A (100% operating factor) 3 x 1.8 A (100% operating factor) 3 x 8 A (100% operating factor) Electronic Reversing-Load Relay With Motor Management
ELR W 3/x-... MM 2 102149_00_en Load current depending on the ambient operating temperature Operating time: 100% operating factor Figure 1 Load current depending on the ambient operating temperature Surge current 360 A (t = 10 ms) Minimum load current 150 mA Residual voltage at I N 1.4 V, typical Residual current in the OFF state 4 mA, typical Reversing frequency right rotation/left rotation (cos ϕ = 0.5)
2.5 Hz, maximum
Shutdown time when overload or underload occurs 45 ms, typical (worst case 70 ms) Output wiring RCV circuit Output Data Load Side (Continued) ELR W 3/9-400 MM ELR W 3/2-400 MM ELR W 3/9-500 MM Ambient operating temperature [°C] Load current [A] General Data Housing dimensions (length x width x height) 94 mm x 62 mm x 122 mm (3.701 x 2.441 x 4.803 in.) Insulating housing version Polycarbonate (PC), color: green Test voltage I/O 2.5 kV rms Ambient operating temperature range -20°C to +60°C (-4°F to +140°F) Standards/specifications EN 61000-4-2/DIN EN 61000-4-2/VDE 0847-4-2; EN 61000-4-3/DIN EN 61000-4-3/VDE 0847-4-3; EN 61000-4-4/DIN EN 61000-4-4/VDE 0847-4-4; EN 61000-4-5/DIN EN 61000-4-5/VDE 0847-4-5; EN 61000-4-6/DIN EN 61000-4-6/VDE 0847-4-6; IEC 60664/IEC 60664 A/DIN VDE 0110 Safe isolation input/output DIN EN 50178 (VDE 0160) Degree of protection according to IEC 60529/EN 60529/DIN VDE 0470-1 IP20 Mounting position Vertical (DIN rail horizontal) Mounting Can be mounted with spacing ≥ 20 mm (0.787 in.)
ELR W 3/x-... MM 102149_00_en 3 Connection Data Figure 2 Connection data The following cable cross sections can be connected: Block Diagram Figure 3 Block diagram Solid [mm 2] Stranded [mm 2] AWG Stripping Length L [mm] 0.2 - 6 0.2 - 4 25 - 10 8 mm (0.31 in.) Logic µP Parameterization Memory Confirmation
24 V DC
SerialV.24 (RS-232)
ELR W 3/x-... MM 4 102149_00_en © PHOENIX CONTACT 01/2005 Technical modifications reserved PHOENIX CONTACT GmbH & Co. KG Flachsmarktstr. 8
32825 Blomberg
+49 - 52 35 - 30 0 +49 - 52 35 - 34 12 00 www.phoenixcontact.com Worldwide Locations: www.phoenixcontact.com/salesnetwork Ordering Data Description Order Designation Order No. Electronic reversing-load relay with motor management. ELR W 3/9-400 MM 29 63 51 4 ELR W 3/2-500 MM 29 82 62 1 ELR W 3/9-500 MM 29 63 54 3 For marking systems and assembly material, see CLIPLINE catalog. Make sure you always use the latest documentation. It can be downloaded from www.download.phoenixcontact.com.