Technical content
Features
–E m e r g e n c y s t o p a n d s afety door monitoring – suitable up to category 4, PL e (EN ISO 13849-1), SIL 3 (IEC 61508) – Single-channel or two-channel wiring with cross-circuit detection – Three undelayed and two delayed enable contacts – Fixed delay time of 0.5 to 30 s – Automatic or manual start circuit – Choice of screw or spring-cage terminal blocks WARNING: Risk of electric shock Observe the safety instructions in the corresponding section. Make sure you always use the latest documentation. It can be downloaded from the product at phoenixcontact.net/products. This data sheet is valid for all products listed on the following page: 102100_en_01 2013-05-13
102100_en_01 PHOENIX CONTACT 2 2T a b l e o f c o n t e n t s
102100_en_01 PHOENIX CONTACT 3 Description Type Order No. Pcs. / Pkt. Safety relay for emergency stop and safety door monitoring up to SIL 3 or Cat. 4, PL e according to EN ISO 13849, automatic or manual activation, 3 N/O contacts, 1 N/C contact, 2 N/O contacts with fixed 10 s dropout delay, plug-in screw connection terminal blocks PSR-SCP- 24DC/ESD/5X1/1X2/ T10 2981088 1 Safety relay for emergency stop and safety door monitoring up to SIL 3 or Cat. 4, PL e according to EN ISO 13849, automatic or manual activation, 3 N/O contacts, 1 N/C contact, 2 N/O contacts with fixed 0.5 s dropout delay, plug-in screw connection terminal blocks PSR-SCP- 24DC/ESD/5X1/1X2/0T 5 2981101 1 Safety relay for emergency stop and safety door monitoring up to SIL 3 or Cat. 4, PL e according to EN ISO 13849, automatic or manual activation, 3 N/O contacts, 1 N/C contact, 2 N/O contacts with fixed 2 s dropout delay, plug-in screw connection terminal blocks PSR-SCP- 24DC/ESD/5X1/1X2/ T 2 2981125 1 Safety relay for emergency stop and safety door monitoring up to SIL 3 or Cat. 4, PL e according to EN ISO 13849, automatic or manual activation, 3 N/O contacts, 1 N/C contact, 2 N/O contacts with fixed 0.5 s dropout delay, plug-in spring-cage connection terminal blocks PSR-SPP- 24DC/ESD/5X1/1X2/0T 5 2981130 1 Safety relay for emergency stop and safety door monitoring up to SIL 3 or Cat. 4, PL e according to EN ISO 13849, automatic or manual activation, 3 N/O contacts, 1 N/C contact, 2 N/O contacts with fixed 1.0 s dropout delay, plug-in screw connection terminal blocks PSR-SCP- 24DC/ESD/5X1/1X2/ T 1 2981143 1 Safety relay for emergency stop and safety door monitoring up to SIL 3 or Cat. 4, PL e according to EN ISO 13849, automatic or manual activation, 3 N/O contacts, 1 N/C contact, 2 N/O contacts with fixed 1.0 s dropout delay, plug-in spring-cage connection terminal blocks PSR-SPP- 24DC/ESD/5X1/1X2/ T 1 2981156 1 Safety relay for emergency stop and safety door monitoring up to SIL 3 or Cat. 4, PL e according to EN ISO 13849, automatic or manual activation, 3 N/O contacts, 1 N/C contact, 2 N/O contacts with fixed 1.5 s dropout delay, plug-in screw connection terminal blocks PSR-SCP- 24DC/ESD/5X1/1X2/1T 5 2981169 1 Safety relay for emergency stop and safety door monitoring up to SIL 3 or Cat. 4, PL e according to EN ISO 13849, automatic or manual activation, 3 N/O contacts, 1 N/C contact, 2 N/O contacts with fixed 1.5 s dropout delay, plug-in spring-cage connection terminal blocks PSR-SPP- 24DC/ESD/5X1/1X2/1T 5 2981172 1 Safety relay for emergency stop and safety door monitoring up to SIL 3 or Cat. 4, PL e according to EN ISO 13849, automatic or manual activation, 3 N/O contacts, 1 N/C contact, 2 N/O contacts with fixed 2 s dropout delay, plug-in spring-cage connection terminal blocks PSR-SPP- 24DC/ESD/5X1/1X2/ T 2 2981198 1 Safety relay for emergency stop and safety door monitoring up to SIL 3 or Cat. 4, PL e according to EN ISO 13849, automatic or manual activation, 3 N/O contacts, 1 N/C contact, 2 N/O contacts with fixed 2.5 s dropout delay, plug-in screw connection terminal blocks PSR-SCP- 24DC/ESD/5X1/1X2/2T 5 2981208 1 Safety relay for emergency stop and safety door monitoring up to SIL 3 or Cat. 4, PL e according to EN ISO 13849, automatic or manual activation, 3 N/O contacts, 1 N/C contact, 2 N/O contacts with fixed 2.5 s dropout delay, plug-in spring-cage connection terminal blocks PSR-SPP- 24DC/ESD/5X1/1X2/2T 5 2981211 1 Safety relay for emergency stop and safety door monitoring up to SIL 3 or Cat. 4, PL e according to EN ISO 13849, automatic or manual activation, 3 N/O contacts, 1 N/C contact, 2 N/O contacts with fixed 3.0 s dropout delay, plug-in screw connection terminal blocks PSR-SCP- 24DC/ESD/5X1/1X2/ T 3 2981224 1 Safety relay for emergency stop and safety door monitoring up to SIL 3 or Cat. 4, PL e according to EN ISO 13849, automatic or manual activation, 3 N/O contacts, 1 N/C contact, 2 N/O contacts with fixed 3.0 s dropout delay, plug-in spring-cage connection terminal blocks PSR-SPP- 24DC/ESD/5X1/1X2/ T 3 2981237 1 Safety relay for emergency stop and safety door monitoring up to SIL 3 or Cat. 4, PL e according to EN ISO 13849, automatic or manual activation, 3 N/O contacts, 1 N/C contact, 2 N/O contacts with fixed 4.0 s dropout delay, plug-in screw connection terminal blocks PSR-SCP- 24DC/ESD/5X1/1X2/ T 4 2981240 1 Safety relay for emergency stop and safety door monitoring up to SIL 3 or Cat. 4, PL e according to EN ISO 13849, automatic or manual activation, 3 N/O contacts, 1 N/C contact, 2 N/O contacts with fixed 4.0 s dropout delay, plug-in spring-cage connection terminal blocks PSR-SPP- 24DC/ESD/5X1/1X2/ T 4 2981253 1 3O r d e r i n g d a t a
102100_en_01 PHOENIX CONTACT 4 Safety relay for emergency stop and safety door monitoring up to SIL 3 or Cat. 4, PL e according to EN ISO 13849, automatic or manual activation, 3 N/O contacts, 1 N/C contact, 2 N/O contacts with fixed 5.0 s dropout delay, plug-in screw connection terminal blocks PSR-SCP- 24DC/ESD/5X1/1X2/ T 5 2981266 1 Safety relay for emergency stop and safety door monitoring up to SIL 3 or Cat. 4, PL e according to EN ISO 13849, automatic or manual activation, 3 N/O contacts, 1 N/C contact, 2 N/O contacts with fixed 5.0 s dropout delay, plug-in spring-cage connection terminal blocks PSR-SPP- 24DC/ESD/5X1/1X2/ T 5 2981279 1 Safety relay for emergency stop and safety door monitoring up to SIL 3 or Cat. 4, PL e according to EN ISO 13849, automatic or manual activation, 3 N/O contacts, 1 N/C contact, 2 N/O contacts with fixed 6.0 s dropout delay, plug-in screw connection terminal blocks PSR-SCP- 24DC/ESD/5X1/1X2/ T 6 2981282 1 Safety relay for emergency stop and safety door monitoring up to SIL 3 or Cat. 4, PL e according to EN ISO 13849, automatic or manual activation, 3 N/O contacts, 1 N/C contact, 2 N/O contacts with fixed 6.0 s dropout delay, plug-in spring-cage connection terminal blocks PSR-SPP- 24DC/ESD/5X1/1X2/ T 6 2981295 1 Safety relay for emergency stop and safety door monitoring up to SIL 3 or Cat. 4, PL e according to EN ISO 13849, automatic or manual activation, 3 N/O contacts, 1 N/C contact, 2 N/O contacts with fixed 15.0 s dropout de- lay, plug-in screw connection terminal blocks PSR-SCP- 24DC/ESD/5X1/1X2/ T15 2981305 1 Safety relay for emergency stop and safety door monitoring up to SIL 3 or Cat. 4, PL e according to EN ISO 13849, automatic or manual activation, 3 N/O contacts, 1 N/C contact, 2 N/O contacts with fixed 15.0 s dropout de- lay, plug-in spring-cage connection terminal blocks PSR-SPP- 24DC/ESD/5X1/1X2/ T15 2981318 1 Safety relay for emergency stop and safety door monitoring up to SIL 3 or Cat. 4, PL e according to EN ISO 13849, automatic or manual activation, 3 N/O contacts, 1 N/C contact, 2 N/O contacts with fixed 20.0 s dropout de- lay, plug-in screw connection terminal blocks PSR-SCP- 24DC/ESD/5X1/1X2/ T20 2981321 1 Safety relay for emergency stop and safety door monitoring up to SIL 3 or Cat. 4, PL e according to EN ISO 13849, automatic or manual activation, 3 N/O contacts, 1 N/C contact, 2 N/O contacts with fixed 20.0 s dropout de- lay, plug-in spring-cage connection terminal blocks PSR-SPP- 24DC/ESD/5X1/1X2/ T20 2981334 1 Safety relay for emergency stop and safety door monitoring up to SIL 3 or Cat. 4, PL e according to EN ISO 13849, automatic or manual activation, 3 N/O contacts, 1 N/C contact, 2 N/O contacts with fixed 30.0 s dropout de- lay, plug-in screw connection terminal blocks PSR-SCP- 24DC/ESD/5X1/1X2/ T30 2981347 1 Safety relay for emergency stop and safety door monitoring up to SIL 3 or Cat. 4, PL e according to EN ISO 13849, automatic or manual activation, 3 N/O contacts, 1 N/C contact, 2 N/O contacts with fixed 30.0 s dropout de- lay, plug-in spring-cage connection terminal blocks PSR-SPP- 24DC/ESD/5X1/1X2/ T30 2981350 1 Safety relay for emergency stop and safety door monitoring up to SIL 3 or Cat. 4, PL e according to EN ISO 13849, automatic or manual activation, 3 N/O contacts, 1 N/C contact, 2 N/O contacts with fixed 10.0 s dropout de- lay, plug-in spring-cage connection terminal blocks PSR-SPP- 24DC/ESD/5X1/1X2/T10S 2981509 1 Safety relay for emergency stop and safety door monitoring up to SIL 3 or Cat. 4, PL e according to EN ISO 13849, automatic or manual activation, 3 N/O contacts, 1 N/C contact, 2 N/O contacts with fixed 10 s dropout delay, plug-in spring-cage connection terminal blocks PSR-SPP- 24DC/ESD/5X1/1X2/ T10 2981091 1 Description Type Order No. Pcs. / Pkt. Documentation Type Order No. Pcs. / Pkt. User manual, English, for applications for PSR safety relay UM EN SAFETY RELAY APPLICA- TION 2888712 1
4 Technical data
Nominal input voltage UN 24 V DC Typical input current 150 mA DC Voltage at input/start and feedback circuit approx. 23 V DC
102100_en_01 PHOENIX CONTACT 5 Max. permissible overall conductor resistance (Input and reset circuit at UN) 11 Ω (Input and start circuits at UN) Typical response time 70 ms (manual start) 600 ms (automatic start) Typical release time 20 ms (undelayed contacts) Recovery time 1 s Input data Output data Contact type 3 enabling current paths undelayed 2 enabling current paths delayed 1 signaling current path undelayed Contact material AgSnO2 Minimum switching voltage 15 V AC/DC Maximum switching voltage 250 V AC/DC Limiting continuous current 6 A (N/O contact) Maximum inrush current 6 A Inrush current, minimum 25 mA Interrupting rating (ohmic load) max. 144 W (24 V DC, τ = 0 ms)
288 W (48 V DC, τ = 0 ms)
110 W (110 V DC, τ = 0 ms)
88 W (220 V DC, τ = 0 ms)
1500 VA (250 V AC, τ = 0 ms)
Maximum interrupting rating (inductive load) 42 W (24 V DC, τ = 40 ms)
42 W (48 V DC, τ = 40 ms)
42 W (110 V DC, τ = 40 ms)
42 W (220 V DC, τ = 40 ms)
Switching capacity min. 0.4 W Mechanical service life Approx. 10 7 cycles Switching capacity (360/h cycles) 4 A (24 V DC)
4 A (230 V AC)
Switching capacity (3600/h cycles) 2.5 A (24 V (DC13))
3 A (230 V (AC 15))
Output fuse 6 A fast blow (undelayed) C6 (24 V AC/DC) automatic device (undelayed)
10 A gL/gG NEOZED (delayed)
Relay type Electromechanically forcibly guided relay. Nominal operating mode 100% operating factor Degree of protection IP20 Min. degree of protection of inst. location IP54 Mounting position Any Air and creepage distances between the power circuits DIN EN 50178/VDE 0160 Rated surge voltage / insulation 4 kV / basic isolation, (saf e isolation, reinforced insulation and 6 kV between the enabling current paths (13/14, 23/24, 33/34) and the remaining current paths and between 13/14, 23/24, 33/34 between each other.) Dimensions Screw connection Spring-cage conn. W x H x D 45 x 99 x 114.5 mm 45 x 112 x 114.5 mm Connection data Screw connection Spring-cage conn. Stripping length 7 mm 8 mm
102100_en_01 PHOENIX CONTACT 6 Ambient conditions Ambient temperature (operation) -20 °C ... 55 °C Ambient temperature (storage/transport) -40 °C ... 70 °C Max. permissible relative humidity (operation) 75 % Max. permissible humidity (storage/transport) 75 % Certification / Approvals Approvals Safety data Stop category according to IEC 60204 0 , 1 Safety parameters for IEC 61508 - High demand SIL 3 PFHd 1.67 x 10-9 Diagnostic coverage (DC) 96.76 % MTTFd 68276 Years Proof test interval 240 Months Safety characteristic data according to EN ISO 13849 Category 4 (Undelayed contacts) 3 (delayed contacts) Performance level e (Undelayed contacts) d (delayed contacts) DCavg 96.76 % CCF Passed B10d 400000 (At 3 A AC15) dop 365.25 Days hop 24 h tCycle 3600 s
102100_en_01 PHOENIX CONTACT 7
5 Basic circuit diagram
Key: 6D e r a t i n g Figure 2 Derating curve Designa- tion Explanation A1/A2 Safety relay input voltage Y1/Y2 Feedback circuit S10, S11, S12 Safety sensor/switch 1 input circuit S10, S21, S22 Safety sensor/switch 2 input circuit 13/14, 23/ 24, 33/34 Undelayed enabling current paths 41/42 Signaling current path 57/58, 67/ Delayed enabling current paths S33/S34 Manual start S33/S35 Automatic start /c187 A1 Y1 Y2 S10S11 S12 13 23 33 41 57 Logic A2 S33S34 S35 S21 S22 14 24 34 42 58 68 T[A °C] I[ A ]TH 0 1 02 03 0 4 0 50 60 45 55
102100_en_01 PHOENIX CONTACT 8 7S a f e t y n o t e s WARNING: Risk of electric shock During operation, parts of electrical switching devices carry hazardous voltages. Before working on the switching device, dis- connect the power. Please observe the safety regulations of elec- trical engineering and industrial safety and lia- bility associations. Disregarding these safety regulations may re- sult in death, serious personal injury or dam- age to equipment. Startup, mounting, modifications, and up- grades should only be carried out by a skilled electrical engineer! WARNING: Risk of automatic machine re- start! For emergency stop applications, the ma- chine must be prevented from restarting auto- matically by a higher-level control system. Protective covers must not be removed when operating electrical switching devices. WARNING: Danger due to faulty devices! The devices may be damaged following an er- ror and correct operation can no longer be en- sured. In the event of an error, replace the device im- mediately. Repairs to the device, especially if the hous- ing must be opened, may only be carried out by the manufacturer or authorized persons. Otherwise the warranty is invalidated. NOTE: Risk of damage to equipment due to incorrect installation For reliable operation, the safety relay must be installed in housing protected from dust and humidity (IP54). Carry out wiring according to the application. Use the Application Examples section for this purpose. NOTE: Risk of damage to equipment due to noise emissions When operating relay modules the operator must meet the requirements for noise emis- sion for electrical and electronic equipment (EN 61000-6-4) on the contact side and, if re- quired, take appropriate measures.
102100_en_01 PHOENIX CONTACT 9 8O p e r a t i n g a n d d i s p l a y u n i t Key: 9D i a g n o s t i c s The diagnostic descriptions can be found in Section 7 of the application manual for PSR safety relays. PSR-SCP- 24DC/ESD/5X1/1X2/T10Order N o.: 29 81 08 8 APPROVALS Serial No. 13 23 33 41 57 58 14 24 34 42 58 68 S12 S34 S33 S35 33 34 23 24 PSR-ESD-T A1 S21 S22 A2 S10 S11 S11 S12 Y1 Y2 58 68 42 57 67 41 Power K3(t) K4(t) 57 58 41 58 68 42 23 24 33 34 1011 PSR-SPP- 24DC/ESD/5X1/1X2/T10Order No .: 2 9 81 09 1 APPROVALS Serial No. 13 23 33 41 57 58 14 24 34 42 58 68 S12 S34 S33 S35 33 34 23 24 PSR-ESD-T A1 S21 S22 A2 S10 S11 S11 S12 Y1 Y2 58 68 42 57 67 41 Power K3(t) K4(t) 58 68 42 57 67 41 14 33 34 13 23 24 S10 S11 S11 S12 Y1 Y2 1011 Designa- tion Explanation
1 Metal lock for mounting on the DIN rail
2 COMBICON plug-in screw terminal blocks
3 COMBICON plug-in spring-cage terminal
4 13/14, 23/24, 33/34 - undelayed enabling current paths 5 41/42 - alarm contact 6 57/58, 67/68 - dela yed enabling current paths
7 S10, S11, S12 - input circuits
8 S33, S34, S35 - start circuit (activating cir-
cuit)
9 S21, S22 - input circuits
10 A1, A2 - supply voltage connection
11 Y1/Y2 - feedback circuit
102100_en_01 10PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany www.phoenixcontact.com
10.1 Two-channel emergency stop circuit with
– Manual activation via monitored reset button at S33/ S34 – Automatic activation with jumper at S33-S35 – suitable up to category 4, PL e (EN ISO 13849-1), SIL 3 (IEC 61508) Figure 4 Two-channel emergency stop circuit with cross-circuit detection
10.2 Single-channel emer gency stop circuit
– Manual activation via monitored reset button at S33/ S34 – Automatic activation with jumper at S33-S35 – Suitable up to category 1, PL c (EN ISO 13849-1), SIL 1 (IEC 61508) Figure 5 Single-channel emergency stop circuit
10.3 Two-channel monitoring with semiconductor
– Manual activation via monitored reset button at S33/ S34 – Automatic activation with jumper at S33-S35 – suitable up to category 4, PL e (EN ISO 13849-1), SIL 3 (IEC 61508) Figure 6 Two-channel monitoring24VD C GND 14 24A1 A2 23S34S10 S11S12 S21S22 S33 PSR -E SD S35 ResetArrêtd'u rge nce 24VD C GND 14A1 A2 S35S34S10 S11S12 S21S22 S33 PSR -E SD ResetEm erge ncys to p 24VD C GND GND + 24 VD C OUT1 OUT2 14A1 A2 S35S34S10 S11S12 S21S22 S33 PSR -E SD Reset Semiconductor output