100ACMEB GAPTEC | Alldatasheet

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 3

Technical content

GAPTEC-Electronic GmbH & Co. KG sales@gaptec-electronic.com – www.gaptec-electronic.com Page 1 of 3 100ACMEB – Rev. 2017-1.0 Specifications subject to change without notice. Approval Model Power [W] Output voltage [V] Output current [mA, max] Capacitive Load [µF, max] Efficiency [@230VAC, %, typ] UL/CE 100ACMEB_12S4 100 12 6666 3000 90 UL/CE 100ACMEB_24S4 100 24 4167 1500 90 UL/CE 100ACMEB_48S4 100 48 2083 500 90 100ACMEB Series 100W - Single Output AC-DC Converter - Universal Input - Isolated & Regulated Universal input: 90~264VAC Regulated output, low ripple and noise High efficiency up to 90% Short circuit protection (SCP) Output power protection (OPP) With PFC Function >0.9 <0.3W No Load Input Power Over voltage protection (OVP) Meets EN60950, UL60950 UL / IEC / EN 60601 3.1 Edition & UL / IEC / EN 60950 AM2 Safety Approvals Meets EN60601-1, ANSI/ AAMI ES60601-1 standards (2 x MOOP) AC-DC Converter 100 Watt The 100ACMEB series is a compact size power converter offered by GAPTEC. It features universal input voltage, taking both DC and AC input voltage, low power consumption, high efficiency, high reliability, safer isolation. It offers good EMC performance, meets IEC/EN61000-4, CISPR22/EN55022, UL60950 and EN60950 standards, and is widely used in medical instrumentation and critical applications in commercial and industrial electronic equipment. Input specifications Input voltage range 90-264 VAC Input frequency 47~63Hz Input current 115VAC

  • 2A (max) 230VAC
  • 1A (max) Inrush current (<2ms) 115VAC
  • 45A (typ) 230VAC
  • 90A (typ) Leakage current < 0.1mA/264VAC (touch current) Power factor (at full load) (pending) Example: 100ACMEB_05S4 100 = 100Watt; AC = AC-DC; MEB = series; 5Vout; S = Single Output; 4 = 4kVAC Note: 1. This product is not designed for use in critical life support systems, equipment used in hazardous environment, nuclear control systems or other such applications which necessitate specific safety and regulatory standards other the ones listed in this datasheet. 2. All specifications valid at 230VAC input voltage, full load and +25°C after warm-up time unless otherwise stated. Output specifications Item Test conditions Min Typ Max Units Output voltage accuracy Full load ±2 % Line regulation ±1 % Load regulation 10% to 100% load ±1 % Ripple & noise* • 100ACMEB_12S4
  • Others 160 mV 1% of Vout Hold-up time @90% Vout/115VAC 10 ms * Measured at 20MHz of bandwidth with 0.1uF & 47uF parallel capacitor. Protection specifications Short circuit protection Protection type: Auto recovery, hiccup mode Over-voltage protection Protection type: Auto recovery, hiccup mode Over-power protection Protection type: Auto recovery, hiccup mode Over-temperature protection Protection type: Latch off

GAPTEC-Electronic GmbH & Co. KG sales@gaptec-electronic.com – www.gaptec-electronic.com Page 2 of 3 100ACMEB – Rev. 2017-1.0 Specifications subject to change without notice. 100ACMEB Series 100W - Single Output AC-DC Converter - Universal Input - Isolated & Regulated Common specifications Operating temperature range -30°C ~ +70°C (with derating) Storage temperature range -30°C ~ +85°C Case temperature range Under 115VAC 73°C, others 80°C Humidity (non-condensing) 95% MAX Cooling Free air convection Temperature coefficient ±0.05%/°C I/O-isolation voltage Input-Output: 4000VAC or 5656VDC Input-FG: 2000VAC or 2828VDC Output-FG: 1500VAC or 2121VDC Altitude during operation 5000m Atmospheric pressure 70kPa to 106kPa EMC / EMI / Conducted and radiated EMI* EN55032 Conducted & Radiated Class B EMC / EMS / ESD IEC/EN 61000-4-2 Contact ±4KV / Air ±8KV perf. Criteria B EMC / EMS / Radiated Immunity IEC/EN 61000-4-3 10V/m perf. Criteria A EMC / EMS / Fast Transient IEC/EN 61000-4-4 ±2kV perf. Criteria B EMC / EMS / Surge IEC/EN 61000-4-5 ±1KV perf. Criteria B EMC / EMS / Conducted immunity IEC/EN 61000-4-6 10Vr.m.s perf. Criteria A EMC / EMS / PFMF IEC/EN 61000-4-8 30A/m perf. Criteria A EMC / EMS / Dips IEC/EN 61000-4-11 30% / 10ms perf. Criteria B EMC / EMS / Interruption EN61000-4-11 >95% 5000ms Safety standards IEC60950, EN60950, UL60950 Safety approvals UL / IEC / EN 60601 3.1rd Edition & UL / IEC / EN 60950 AM2 Case material UL94V-0 MTBF >250,000 h @ 25°C (MIL-HDBK-217F, Notice 1) Vibration 10~500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes. Package 83.9 x 58.5 x 35.0 mm Weight 253 g * Please secure the power supply unit to your metal case by using the four screw holes in the corners for either Class I or Class II equipment. Typical characteristics Derating graphs Power derating

GAPTEC-Electronic GmbH & Co. KG sales@gaptec-electronic.com – www.gaptec-electronic.com Page 3 of 3 100ACMEB – Rev. 2017-1.0 Specifications subject to change without notice. 100ACMEB Series 100W - Single Output AC-DC Converter - Universal Input - Isolated & Regulated Block diagram Mechanical dimensions Note: Unit: mm[inch] General tolerances: ±0.50mm [±0.020inch] PIN ø Single 1 1.2±0.1%mm PE 2 1.2±0.1%mm AC IN (L) 3 1.2±0.1%mm AC IN (N) 4 1.2±0.1%mm ON / OFF (Provide +5Vdc Controlled) 5 1.8±0.1%mm +DC OUT 6 1.8±0.1%mm -DC OUT 7 1.8±0.1%mm Trim Note: Please reserve the pin 4 hole on PCB. If the remote on/off function is not required, please connect the pin 4 circuit layout with pin6, or keep pin 4 floating.