https://www.phoenixcontact.com/us/products/0916178 08/01/2016 Page 1 / 4 Thermomagnetic device circuit breaker - TMCP 2 M1 300 6,0A - 0916178 Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's documentation. Our General Terms of Use for Downloads are valid (http://phoenixcontact.com/download) Thermomagnetic circuit breaker, 2-pos., normal blow, 1 N/O contact and 1 N/C contact The illustration shows version TMCP

1 F1 300 2,0A

Weight per Piece (excluding packing) 90.0 g Custom tariff number 85362010 Country of origin Germany Technical data General Mounting type On base element Color black Number of positions 2 Overvoltage category II Insulating material PA66 Flammability rating according to UL 94 V-2 Electrical data Fuse type Automatic device Rated surge voltage 2.5 kV Rated voltage 250 V AC

65 V DC

Insulation resistance Riso > 100 MΩ (500 V DC) Rated short-circuit switching capacity Icn 800 A

2500 A (32 V DC)

Short-circuit switching capacity Ik 5000 A UL 1077: 277 V AC/480 V AC

https://www.phoenixcontact.com/us/products/0916178 08/01/2016 Page 2 / 4 Thermomagnetic device circuit breaker - TMCP 2 M1 300 6,0A - 0916178 Technical data Electrical data

2000 A UL 1077: 65 V DC

Dielectric strength 3000 V AC (Actuation area)

1500 V AC (Main to auxiliary circuit)

1000 V AC (Auxiliary circuit 11 - 12 to 23 - 24)

1500 V (Position to position)

Switching cycles, max. 10000 (At 1 x In, inductive) Degree of pollution 2 Overvoltage category II Insulating material group II Dimensions Height 50 mm Width 25 mm Depth 78.5 mm Complete module height 115 mm Complete module width 38 mm Complete module depth 121 mm Ambient conditions Degree of protection IP30 (Actuation area) IP00 (Connection area) Ambient temperature (operation) -30 °C ... 60 °C Connection data Connection method pluggable Standards and Regulations Standards/specifications EN 60934 UL 1077 Classifications eCl@ss eCl@ss 4.0 27141116 eCl@ss 4.1 27141116 eCl@ss 5.0 27141116 eCl@ss 5.1 27141116 eCl@ss 6.0 27141116 eCl@ss 7.0 27141116

https://www.phoenixcontact.com/us/products/0916178 08/01/2016 Page 3 / 4 Thermomagnetic device circuit breaker - TMCP 2 M1 300 6,0A - 0916178 Classifications eCl@ss eCl@ss 8.0 27141116 eCl@ss 9.0 27141116 ETIM ETIM 2.0 EC000899 ETIM 3.0 EC000899 ETIM 4.0 EC000899 ETIM 5.0 EC000899 UNSPSC UNSPSC 6.01 30211812 UNSPSC 7.0901 39121411 UNSPSC 11 39121411 UNSPSC 12.01 39121411 UNSPSC 13.2 39121411 Approvals Approvals Approvals CSA / UL Recognized / EAC / VDE Zeichengenehmigung Ex Approvals Approvals submitted Approval details CSA UL Recognized

https://www.phoenixcontact.com/us/products/0916178 08/01/2016 Page 4 / 4 Thermomagnetic device circuit breaker - TMCP 2 M1 300 6,0A - 0916178 Approvals EAC VDE Zeichengenehmigung Accessories Additional products Box mounting base - TMCP SOCKET M - 0916589 Modular socket element, 2-position, for holding two circuit breakers, each with a single position End cover - TMCP CONNECT LR - 0916592 End cover, Length: 115 mm, Width: 6 mm, Color: black Phoenix Contact 2016 © - all rights reserved http://www.phoenixcontact.com