© PHOENIX CONTACT 2009-11-17100464_en_05 CLIPLINE ECP… Data sheet 1D e s c r i p t i o n The ECP… electronic circuit breaker, which has a design width of just 12.5 mm, selectively protects all 24 V DC load circuits. This is achieved using a combination of active electronic current limitation and proven circuit breaker technology including electrical isolation. The ECP… can be plugged onto the proven TMCP SOCKET M base, which ensures quick and easy mounting. The ECP… can be used in a pplications that cover all aspects of the switched-mode power supply unit. In the event of an overload, switched-mode power supply units reduce the output voltage, which means that all the connected loads are no longer sufficiently supplied. This means that if an error occurs in one load of a system, the voltage will be affected in all load circuits. The ECP… solves this problem by always limiting the maximum possible current to 1.8 times (or 1.5 times) the value of the set nominal current. Capacitive loads can thus be switched on and loads are only switched off in the event of an overload or short circuit. An LED and integrated signal contacts indicate the operating and error states.

1.1 Properties

– Selective load protection with electrical isolation in the event of an error – All load types can be connect ed (small DC motors, etc. on request) – Active current limitation is typically 1.8 x I N (or typically 1.5 x IN at IN = 8 A or 10 A) when capacitive loads up to 20,000 µF are switched on and in the event of overload/ short circuit – Electronic shutdown characteristic curve – Safe overload shutdown from 1.1 x I N, even for long load cables or low cable cross-sections – Nominal current can be selected in fixed current strengths from 1 A ... 10 A or set to two levels (1 A/2 A or 3 A/6 A) using switches on the device – Manual on/off switch (push/push actuation) – Clear indication – Design width of just 12.5 mm per channel – Can be plugged into a modular base NOTE: Make sure that the cable cross-section of the relevant load circuit is adapted to the nominal current of the ECP… used. Make sure you always use the latest documentation. It can be downloaded at www.phoenixcontact.net/download This data sheet is valid for all products listed on the following page: Selective circuit breaker

ECP… 100464_en_05 PHOENIX CONTACT 2 2O r d e r i n g d a t a

3 Technical data

Description Type Order No. Pcs./Pkt. Selective circuit breaker, can be plugged into a TMCP base, indication by means of two-color LED, floating signal contact, on/off pushbutton

1 A/2 A nominal current ECP 1-2 0912018 5

2 A nominal current ECP 2 0911034 5

3 A/6 A nominal current ECP 3-6 0916536 5

3 A nominal current ECP 3 0911047 5

6 A nominal current ECP 6 0912033 5

8 A nominal current ECP 8 0912019 5

10 A nominal current ECP 10 0912020 5

Description Type Order No. Pcs./Pkt. Modular base, 2-pos., designed to accommodate two 1-pos. circuit breakers, width of 12.5 mm per position TMCP SOCKET M 0916589 10 Base termination elements, can be plugged into both the left and right-hand side, contain the connections for the reset inputs/group query TMCP CONNECT LR 0916592 3 Spring lock, for mechanical locking if mounted overhead, 1-pos. ECP-LOCK 0912021 10 Zack marker strip, 10-section, for labeling the center of the terminal block ZB 6 See CLIPLINE catalog Fixed bridge, plug-in, not insulated, 500 mm long, can be cut to length, for distribution of the supply potential in the base, Imax = 50 A FBST 500 TMCP 0916615 20 Continuous plug-in bridge, 500 m long, can be cut to length, for potential distribution, Imax = 32 A, red FBST 500-PLC RD 2966786 20 Continuous plug-in bridge, 500 m long, can be cut to length, for potential distribution, Imax = 32 A, blue FBST 500-PLC BU 2966692 20 Signal bridge, plug-in, for bridging group indication when there is a free slot on the TMCP SOCKET M base, Imax = 1 A TCMP SB 0916602 6 Operating data Nominal voltage 24 V DC DC supply voltage 18 V DC ... 32 V DC Nominal current IN Depending on the selected item version: Fixed current strength: 2 A, 3 A, 4 A, 6 A, 8 A, 10 A Adjustable: 1 A/2 A or 3 A/6 A Current consumption I0 13 mA, typical Tripping current (bimetal) 0.3 A, typical (only in th e event of an error, until electrically shut down) Indication of the operating state – Two-color LED Green: Device switched on/Power MOSFET controlled Orange: In the event of overload or short circuit until electrically isolated OFF: OFF position of pushbutton – Floating signal contact – OFF position of pushbutton Protection against polarity reversal of U B Internal bimetal (failsafe element) triggered, pushbutton moves to OFF position Load circuit Load output Power MOSFET output (positive switching) Short circuit current IK Active current limitation, 1.8 x IN or 1.5 x IN, maximum (See "Time-current characteristic" on page 5)

ECP… 100464_en_05 PHOENIX CONTACT 3 Shutdown time 5 s at IL > 1.1 x IN, typical See "Voltage drop, current limitation, maximum load current" on page 4 Ri when plugged in = 50 mΩ Temperature shutdown Internal temperature monitoring with electrical isolation Undervoltage monitoring of load output With hysteresis, no reset required: OFF at UB < 8 V ON at UB > 16 V Switch-on delay tStart 0.3 s, typical after each switch-on and after applying UB Electrical isolation of the load circuit Single-pos . (switch contact) – By push/push actuation of the blue pushbutton – After electronic error shutdown (overload, short circuit) – In the event of polarity reversal Free running circuit External free-wheeling diode recommended on inductive load Parallel connection of multiple load outputs Not permitted Auxiliary contacts Pin 11 (GND) Pin 12 (individual indication) Pin 13/14 (group query) Switching capacity I CN Active current limitation Load circuit (continued) Error message, signal output Error message F Floating signal contact, switches simultaneously with electrical isolation, 30 V DC/0.5 A, maximum; 10 V/ 0 mA, minimum Group indication Pushbutton ON: Signal contact SC-S0 is closed (SC-SI is open) OFF: Signal contact SC-S0 is open (SC-SI is closed) Optical indication LED lights up orange (until electrically isolated) General data Width x length 12.5 mm x 60 mm Weight 65 g Service life at 1 x IN 10,000 Height On NS 35/7.5... DIN rail On NS 35/15... DIN rail 144 mm 151.5 mm Ambient temperature 0°C ... +50°C (no condensation, see EN 60204-1) Storage temperature -20°C ... +70°C Insulation material PA-F Inflammability class according to UL 94 V0 Backup fuse Not required, since a redundant failsafe element is integrated. If the failsafe element has been triggered, the pushbutton is in the OFF position. Housing fixing Can be plugged into TMCP SOCKET M modular base Slip-on connections 6.3 mm according to DIN 46244-A6.3-0.8 Humid heat 96 h/95% relative humidity/40°C according to IEC 60068-2-78, Test Cab climatic class 3K3 according to EN 60721 Degree of protection Ho using: IP30, DIN 40050 Terminal blocks: IP00, DIN 40050

ECP… 100464_en_05 PHOENIX CONTACT 4

3.1 Block diagram

Conformance with EMC Directive 2004/108/EC Noise emission: EN 50081-1 Noise immunity: EN 61000-6-2 Isolation coordination (IEC 60934) 0.5 kV/pollution degree 2, increased isolation in the actuation area Dielectric strength Actuation area: 1000 V AC test voltage Installation area: 500 V AC test voltage Load circuit signal contact: 500 V AC test voltage Insulation resistance (OFF state) > 100 MΩ (500 V DC) between LINE (+) - LOAD (+) Vibration resistance 3g, test according to IEC 60068-2-6 Test Fc Approvals u UL 1077, File E140459 Supplementary Protectors for Use in Electrical Equipment c Voltage drop, current limitation, maximum load current Nominal current IN Typical voltage drop UON at IN Active current limitation (typical) Maximum load current at 100% operating factor, TA = 40°C Maximum load current at 100% operating factor, TA = 50°C 2 A 180 mV 1.8 x IN 2 A 2 A 3 A 140 mV 1.8 x I N 3 A 3 A 4 A 190 mV 1.8 x IN 4 A 4 A 6 A 280 mV 1.8 x I N 6 A 5 A 8 A 220 mV 1.5 x IN 8 A 7 A 10 A 280 mV 1.5 x I N 10 A 9 A 1 A/2 A 140 mV/280 mV 1.8 x IN 1 A/2 A 1 A/2 A 3 A/6 A 140 mV/280 mV 1.8 x I N 3 A/6 A 3 A/5 A When mounted in rows without convection cooling, due to the thermal effect during continuous operation (100% operating factor) the nominal device current must only be led to a maximum of 80%. LINE (+) SO SI SC LOAD (L+) GND (-) On/Off 2 12 14 13 11 1LINE LOAD Control Unit

ECP… 100464_en_05 PHOENIX CONTACT 5

3.2 Dimensions

Figure 2 Dimensions (in mm)

3.3 Time-current characteristic (T A = 25°C)

Figure 3 Time-current characteristic time is 5 s. – The electronic current limit ation is typically activated from 1.8 x IN*. This means that under all overload conditions (regardless of the current supply and load circuit resistance), 1.8 times the nominal current* typically flows until shutdown. The shutdown time ranges from 100 ms (short circuit (I K) to 5 s (in the event of overload with high cable attenuation)). – Without the current limitation typically activated at 1.8 x IN*, a significantly higher overcurrent would flow in the event of an overload or short circuit. – If the ECP... has detected an overload or short-circuit condition, the LED changes from green to orange. When the circuit breaker trips, the LED goes out. – The circuit breaker cannot be reset until the integrated bimetal has cooled down (approximately 10 s). Typical current limitation 1.5 x IN at IN = 8 A or 10 A Snap-on lock Actuation area Installation area ON

105 OFF

typ. 1,1 xl 1,8 x l Switchi ng tim e [s] Multiples of IN N N 0,01 0,1 10 23 IK

ECP… 100464_en_05 PHOENIX CONTACT 6

3.4 Safe shutdown

Safe shutdown of the ECP… for various su pply line lengths and cable cross-sections Specific electrical resistance of electrolytic copper ρ0 = 0.0178 (Ω x mm²)/m UB = 19.2 V DC (80% of 24 V DC) The voltage drop at the ECP… and the tolerance of the shutdown point ECP… nominal current setting I N (in A) → 3 A 6 A Rmax in Ohm = (UB/Ioff) - 0.050 Ω1 →

1 Internal resistance of miniature circuit breakers

5.07 Ω 2.51 Ω ECP… safely trips from 0 Ω up to maximum circuit resistance Rmax Distance L in meters (= single length) 0 Total cable resistance in Ohm = (R0 x 2 x L)/A 0000000 Example 1: Maximum permissible distance for 1.5 mm² and 3 A → Approximately 200 m2 2 Shutdown current Ioff = 3 A x 1.25 A = 3.75 A Maximum circuit resistance Rmax = UB/Ioff - 0.050 Ω (internal resistance of miniature circuit breakers) Rmax = (19.2 V/3.75 A) - 0.050 Ω = 5.07 Ω In the table, the calculated value of 5.07 Ω lies between 200 m and 225 m (4.75 Ω and 5.34 Ω). Therefore a distance of around 200 m can be covered. Example 2: Maximum permissible distance for 1.5 mm² and 6 A → Approximately 100 m Example 3: Mixed wiring: (Control cabinet --- sensor/actuator level) R1 = 40 m in 1.5 mm² and R2 = 5 m in 0.25 mm² R1 = 0.95 Ohm, R2 = 0.71 Ohm Total (R1 + R2) = 1.66 Ohm

ECP… 100464_en_05 PHOENIX CONTACT 7

4 Mounting on a modular base

The TMCP SOCKET M base is snapped onto a DIN rail and can accommodate two ECP… devices. The two-channel bases are modular, which means that larger distribution systems can be created. A connection element is inserted at both the start and end of the system. Current distribution on the individual channels with a common supply (positive pole) is achieved by inserting a power rail in the slot provided on the connection side of the modules. All electrical connections are established using spring-cage terminal blocks. The reference potential for the ECP... (GND pin 11) is also looped through and led to the side connection elements. By connecting together the individual bases, all the internal wiring is established for the ground potential and group error message. The ECP… has an integrated signal contact (PDT). The SC-S0 contact is used for the group error message. The contacts for this indication are already connected in series in the bases and are connected to the side connection elements via two connections (13, 14). In each base, the series circuit can be contacted using a test socket and any interruptions can thus be determined.

4.1 Technical data

4.2 Dimensions with base

Figure 4 Dimensions (in mm) TMCP SOCKET M Test contact for testing group indication on a cable interrupt ø = 2 mm Nominal voltage (without ECP…) 433 V AC; 65 V DC Nominal current (without ECP…) LINE supply (1) LOAD output (2) Reference potential GND (11) Individual indication (12) Group indication (13-14) 50 A 25 A 10 A 1.0 A (with ECP…: 0.5 A) 1.0 A (with ECP…: 0.5 A) Internal resistance (without ECP…) LINE-LOAD (1-2) Indication (13-14) for each module 5 mΩ 8 mΩ/each position plus each additional aligned module: +5 mΩ Supply rail for current distribution Uninsulated power rail I max 50 A (the uninsulated power rail is inserted fully and is therefore safe to touch) Dielectric strength of base (without ECP….) Between main circuits (without power rail) Main circuit to signal circuit Signal circuit to signal circuit 1500 V 1500 V 1500 V Weight Central part Connection elements (pair) 85 g, approximately 30 g, approximately Approval Meets standard UL 60950

ECP… 100464_en_05 PHOENIX CONTACT 8

4.3 Assembly

To assemble, proceed as follows:

  • Snap TMCP SOCKET M base onto an NS 35 DIN rail according to EN 60751.
  • Push bases together.
  • Snap on TMCP CONNECT LR base termination elements to the left and right-hand side.
  • Cut FBST 500... power rails to length as required and insert in bases.
  • Insert connecting cables in the spring-cage terminal blocks (see "Connecting spring-cage terminal blocks" on page 8 and "Pin assignment on base" on page 8).
  • Insert ECP….
  • If necessary, secure the ECP… and base using a clamp (see "Locking the base and ECP…" on page 9).

4.4 Connecting spring-cage terminal blocks

Spring-cage terminal blocks for solid wires and stranded cables with and without ferrules. Use the specified screwdriver size (SD) to release the spring cage.

4.5 Pin assignment on base

Figure 6 Connection diagram Figure 7 Pin assignment Base termination element Modular bases Base termination element Selective circuit breaker Connection Spring-cage terminal blocks for Screwdriver size (SD) Reference potential GND or group indication connections (11 or 13, 14) Individual indication connection (12) PIN Assignment

11 GND

13, 14 Group indication connection Side supply TMCP CONNECT LR TMCP CONNECT LR TMCP SB FBST 500 ... ECP… TMCP SOCKET M TMCP SOCKET M ECP… TMCP SOCKET M

ECP… 100464_en_05 9PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany • Phone: +49 - 52 35 - 30 0 PHOENIX CONTACT • P.O.Box 4100 • Harrisburg • PA 17111-0100 • USA • Phone: +717-944-1300 www.phoenixcontact.com

4.6 Locking the base and ECP…

If mounted overhead, the ECP… must be connected to the base using the ECP-LOCK clamp. Figure 8 Mounting the ECP-LOCK Figure 9 Removing the ECP-LOCK