© PHOENIX CONTACT - 11/2006100212_04_en CLIPLINE TCP Data Sheet
Description
The thermal circuit breaker can be switched back on again, has a compact design and is available in nine finely graded steps for nominal currents from 0.25 A to 10 A. The inte- grated ON/OFF switching function makes it possible to switch the circuit breaker back on immediately after trigger- ing thus increasing the availability of the system. The thermal circuit breaker TCP can be plugged into UK 6-FSI/C fuse base terminal blocks with screw connec- tion technology and into ST 4-FSI/C terminals with spring- cage connection technology. For both types of terminal blocks, the potential distribution can be conveniently imple- mented using bridges. Make sure you always use the latest documentation. It can be downloaded at www.download.phoenixcontact.com A conversion table is available on the Internet at This data sheet is valid for all products listed on the following page: Thermal Circuit Breaker
100212_04_en PHOENIX CONTACT 2 Ordering Data Technical Data Thermal Circuit Breaker Description Type Order No. Pcs./Pck. Thermal miniature circuit breaker, can be plugged onto UK 6-FSI/C... or ST 4-FSI/C... base terminal block Nominal current 0.25 A TCP 0,25A 0712123 20 Nominal current 0.5 A TCP 0,5A 0712152 20 Nominal current 1 A TCP 1A 0712194 20 Nominal current 2 A TCP 2A 0712217 20 Nominal current 3 A TCP 3A 0712233 20 Nominal current 4 A TCP 4A 0712259 20 Nominal current 6 A TCP 6A 0712275 20 Nominal current 8 A TCP 8A 0712291 20 Nominal current 10 A TCP 10A 0712314 20 Accessories Description Type Order No. Pcs./Pck. Zack strip, 10-section, white ZBF 5 (ordering data see CLIPLINE catalog) Technical Data in Accordance With IEC/DIN VDE Nominal voltage 250 V AC / 65 V DC Nominal current 0.25 A ... 10 A Ambient temperature -20°C ... +60°C Interrupting Capacity ICN For nominal currents of 0.25 A ... 4 A 6 x I N For nominal currents of 6 A ... 10 A 8 x IN Interrupting Capacity (UL 1077) AC 250 V 2000 A DC 65 V 200 A Service Life Cycles with 1 x IN (inductive) 3000 Cycles with 2 x IN (inductive) 500 General Data Rated surge voltage 2.5 kV Contamination class 2 Surge voltage category III Insulating material group I Insulating material PA Inflammability class in accordance with UL 94 V0 Connection data 250 V AC / 65 V DC Approvals u V
100212_04_en 3PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany www.phoenixcontact.com Time/Current Characteristic Curve Total interruption period for nominal current, ambient temperature 23°C Dimensional Drawing The time/current characteristic curve depends on the ambi- ent temperatures. To avoid a premature or late switch-off, the nominal current of the circuit breaker must be multiplied with a temperature factor. Nominal Currents and Characteristic Internal Resistances Circuit Diagram © PHOENIX CONTACT 11/2006 /G34 /G30 /G32 /G30 /G33 /G30 /G31 /G30 /G38 /G36 /G35 /G32 /G33 /G34 /G30 /G2C /G38 /G31 /G30 /G2C /G31 /G31 /G31 /G30 /G31 /G30 /G30 /G31 /G30 /G30 /G30 /G31 /G30 /G30 /G30 /G30 Multiples of the nominal current Trip time in seconds 0.25 A ... 4 A 6 A ... 10 A /G35 /G32 /G2C /G33 /G32 /G34 /G2C /G34 /G38 /G34 /G38 /G2C /G38 /G34 /G38 /G2C /G36 /G36 /G2C /G34 Ambient Temperature [°C] -20 -10 0 23 40 50 60 When aligned in a row, the nominal current of the devices can either be transmitted at only 80% or must be overdimensioned accordingly. Nominal Current [A] Internal Resistance [Ω] 0.25 14 0.5 3.4 10 . 9 20 . 2 5 30 . 1 1 40 . 0 7 6 ≤ 0.05 8 ≤ 0.05 10 ≤ 0.05 /G32 /G31