DSE4520 DSE | Alldatasheet
Document overview
- Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
- PDF pages: 2
Technical content
AUTO MAINS FAILURE CONTROL MODULE DEEP SEA ELECTRONICS LTD UK Highfield House, Hunmanby Industrial Estate, Hunmanby YO14 0PH TELEPHONE +44 (0) 1723 890099 EMAIL sales@deepseaelectronics.com WEBSITE www.deepseaelectronics.com DEEP SEA ELECTRONICS INC USA
3230 Williams Avenue, Rockford, IL 61101-2668 USA
TELEPHONE +1 (815) 316 8706 FACSIMILE +1 (815) 316 8708 EMAIL usasales@deepseaelectronics.com WEBSITE www.deepseaelectronics.com Deep Sea Electronics Ltd maintains a policy of continuous development and reserves the right to change the details shown on this data sheet without prior notice. The contents are intended for guidance only. Registered in England & Wales No.01319649 VAT No.316923457 SPECIFICATIONS DC SUPPLY CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. LEDs and backlight will not be maintained during cranking. MAXIMUM OPERATING CURRENT 85 mA at 12 V, 96 mA at 24 V MAXIMUM STANDBY CURRENT 51 mA at 12 V, 47 mA at 24 V MAXIMUM SLEEP CURRENT 35 mA at 12 V, 32 mA at 24 V MAXIMUM DEEP SLEEP CURRENT <10 uA at 12 V, <10 uA at 24 V MAINS (UTILITY) VOLTAGE RANGE
15 V to 415 V AC (Ph to N)
26 V to 719 V AC (Ph to Ph)
3.5 Hz to 75 Hz
OUTPUT A (FUEL)
10 A short term, 5 A continuous,
OUTPUT B (START) AUXILIARY OUTPUTS C, D, E & F
2 A DC at supply voltage
4.6’’ x 3.6” MAXIMUM PANEL THICKNESS 8 mm 0.3” STORAGE TEMPERATURE RANGE -40 °C to +85 °C -40 °F to +185 °F OPERATING TEMPERATURE RANGE -30 °C to +70 °C -22 °F to +158 °F OPTIONAL PARTS PART PART NUMBER IP65 Gasket 020-282 RELATED MATERIALS TITLE PART NO. DSE4510/20 MKII Installation Instructions 053-190 DSE4510/20 MKII Operator Manual 057-260 DSE4510/20 MKII Configuration Suite PC Manual 057-258 KEY FEATURES
- Load unbalanced alarm
- Configurable for use as an auto start and AMF control module
- J1939-75 support and CAN alarm ignore functon
- Alternator frequency & CAN speed sensing in one variant
- Largest back-lit icon display in its class
- Heated display option
- Real time clock provides accurate event logging
- Fully configurable via the fascia or PC using USB communication
- Extremely efficient power save mode
- 3 phase generator sensing
- 3 phase mains (utility) sensing
- Compatible with 600 V ph to ph nominal systems
- Generator/load power monitoring (kW, kV A, kV Ar, pf)
- Accumulated power monitoring (kW h, kVA h, kVAr h)
- Generator overload protection (kW)
- Generator/load current monitoring and protection
- Fuel and start outputs (configurable when using CAN)
- 4 configurable DC outputs
- 3 configurable analogue/digital inputs
- 4 configurable digital inputs
- Configurable staged loading outputs
- 3 engine maintenance alarms
- Engine speed protection
- Engine hours counter
- Engine pre-heat
- Engine run-time scheduler
- Engine idle control for starting & stopping
- Tier 4 engine instrumentation screens
- Battery voltage monitoring
- Start on low battery voltage
- Configurable remote start input
- 1 alternative configuration
- Comprehensive warning, electrical trip or shutdown protection upon fault condition
- LCD alarm indication
- Event log (50)
- Fuel solenoid pulling circuit
- On-screen line diagram on/off functionality
- Configurable CAN instrumentation (10)
- Water in fuel digital input
- Tank bund alarm digital input
- Generator at rest output
- ECU periodic wake-up for information retrieval
- Back-light power-save mode
- Adjustable delay crank timer
- Pre/post heat functionality
- Overload protection
- Mains/generator A/C system selection
- Output timer for external audible alarm KEY BENEFITS
- Automatically transfers between mains (utility) and generator
- Hours counter provides accurate information for monitoring and maintenance periods
- User-friendly set-up and button layout for ease of use
- Multiple parameters are monitored simultaneously which are clearly displayed on the large back-lit icon display.
- The module can be configured to suit a wide range of applications
- Uses DSE Configuration Suite PC Software for simplified configuration
- Compatible with a wide range of CAN engines including Tier 4
- Licence-free PC software
- IP65 rating (with optional gasket) offers increased resistance to water ingress DSEGenset® 055-207/11/22 (4)
The DSE4520 MKII Auto Mains (Utility) Failure Control Module is suitable for a wide variety of single gen-set applications. Whilst maintaining functions included within higher end controllers, such as generator and load power monitoring, the DSE4520 MKII provides the user with an outstanding size to feature ratio. Monitoring engine speed, oil pressure, coolant temperature, frequency, voltage, current, power and fuel level, the modules will give comprehensive engine and alternator protection. This will be indicated on the largest back-lit LCD icon display in its class via an array of warning, electrical trip and shutdown alarms. The module provides electronic J1939 (CAN) and non-electronic (alternator frequency sensing) engine support for diesel, gas and petrol engines all in one variant. With a number of flexible inputs, outputs and protections, the module can be easily adapted to suit a wide range of applications. Through USB communication the module can be easily configured using the DSE Configuration Suite PC Software or can be fully configured through the module’s front panel editor. All DSE products are supported by our dedicated technical support team, which gives customers and end users access to 24 hour help and advice. COMPREHENSIVE FEATURE LIST TO SUIT A WIDE VARIETY OF GEN-SET APPLICATIONS DSE4520 MKII AUTO MAINS FAILURE CONTROL MODULE ENVIRONMENTAL TESTING STANDARDS ELECTRO-MAGNETIC COMPATIBILITY BS EN 61000-6-2 EMC Generic Immunity Standard for the Industrial Environment BS EN 61000-6-4 EMC Generic Emission Standard for the Industrial Environment ELECTRICAL SAFETY BS EN 60950 Safety of Information Technology Equipment, including Electrical Business Equipment TEMPERATURE BS EN 60068-2-1 Ab/Ae Cold Test -30 ºC BS EN 60068-2-2 Bb/Be Dry Heat +70 ºC VIBRATION BS EN 60068-2-6 Ten sweeps in each of three major axes 5 Hz to 8 Hz at +/-7.5 mm,
8 Hz to 500 Hz at 2 gn
Db Damp Heat Cyclic 20/55 ºC at 95% RH 48 Hours BS EN 60068-2-78 Cab Damp Heat Static 40 ºC at 93% RH 48 Hours SHOCK BS EN 60068-2-27 Three shocks in each of three major axes 15 gn in 11 mS DEGREES OF PROTECTION PROVIDED BY ENCLOSURES BS EN 60529 IP65 - Front of module when installed into the control panel with the optional sealing gasket. DSEGenset® PC 1ph 2ph 3ph N 1ph 2ph 3ph N 1ph 2ph 3ph 1 1 4 4 3 DSE4520 MKII DEUTZ ISUZU PERKINS CATERPILLAR MTU VOLVO CUMMINS SCANIA AVAILABLE VARIANTS 4520-05 Auto Mains Failure (Rtc) OTHER + + D + W/ L USB PORT CONFIGURABLE INPUTS DC OUTPUTS ANALOGUE SENDERS DC POWER SUPPLY 8-35V MAINS (UTILITY) SENSING DC OUTPUT DC OUTPUTGENERATOR/ LOAD CURRENT GENERATOR SENSING CHARGE ALTERNATOR FUEL & START OUTPUTS (Flexible with CAN) ELECTRONIC ENGINE CAN VOLTS VOLTS