FF018_V02 STEGO | Alldatasheet
Document overview
- Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
- PDF pages: 2
Technical content
PRODUCT CATALOGUE - STEGOCOOLING Enclosure air-conditioning using a filter fan and exit filter TECHNICAL DATA Axial fan, ball bearing service life 50,000h at +25°C (+77°F), 65% RH fan body aluminium, rotor plastic Connection 2 wires with pressure clamps 2.5mm², length 100mm Casing (filter fan and exit filter) plastic according to UL94 V-0, light grey Hood (filter fan and exit filter) plastic according to UL94 V-0, light grey; UV light resistant according to UL746C (f1) Mounting frame with double-sided industrial adhesive band for fixing to the outside of enclosure; certain operating circumstances can make the additional use of screws necessary (see drilling template); a template for the enclosure cut-out is included in the delivery of the filter fans Filter mat G4 acc. to DIN EN 779, filtering degree 94% Filter material synthetic fibre with progressive construction, temperature resistant to +100°C, self-extinguishing class F1, moisture resistant to 100% RH, reusable - cleaning by washing or vacuuming Operating/Storage temperature -10 to +70°C (+14 to +158°F) / -40 to +70°C (-40 to +158°F) Operating/Storage humidity max. 90% RH (non-condensing) Protection class I (earthed) Approvals UL File No. E234324, EAC, VDE only: 230V Special features > The self-adhesive seal of the mounting frame prevents dust and water from entering the cabinet. > Functional design of the intake and exit fan hoods very effectively prevents direct intrusion of falling water and dust. The advantage is that the filter mat does not get so quickly contaminated with dirt and thus does not need to be exchanged so often. > The air channeling makes the filter fan particularly quiet in operation. > Functional and modern design enables time-saving assembly and maintenance. > The direction of air flow can easily be switched by reversing the axial fan (sizes 1 to 3). > EMC versions and other voltages on request. FIL TER FAN FF 018 | 21m³/h to 102m³/h Filter fans are used to provide an optimum climate in enclosures. The interior temperature of an enclosure can be reduced by channelling cooler filtered outside air into the enclosure thus expelling heated internal air. The resulting air flow prevents formation of localised hot pockets and protects the electronic components from overheating. These filter fans are intended for indoor use. The plastic used for the hood is highly UV light resistant. > Very low noise > Minimal depth in enclosure > Functional design > Time-saving installation > UV resistant Art. No. Operating voltage Air volume, free flow Air volume with exit filter Current consumption Power consumption Average noise level (DIN EN ISO 4871) Depth in enclosure Enclosure cut-out Weight (approx.) Protection type 01800.0-00 230VAC, 50Hz 21m³/h 16m³/h 80mA 13W 31db (A) 45mm 97 x 97mm + 0.4 0.6kg IP54 01801.0-00 230VAC, 50Hz 55m³/h 42m³/h 100mA 15W 40db (A) 58mm 125 x 125mm + 0.4 1.0kg IP54/IP551 01802.0-00 230VAC, 50Hz 102m³/h 68m³/h 100mA 15W 39db (A) 86mm 176 x 176mm + 0.4 1.3kg IP54/IP551 01800.0-01 120VAC, 60Hz 24m³/h 18m³/h 160mA 13W 31db (A) 45mm 97 x 97mm + 0.4 0.6kg IP54 01801.0-01 120VAC, 60Hz 63m³/h 48m³/h 180mA 15W 40db (A) 58mm 125 x 125mm + 0.4 1.0kg IP54/IP551 01802.0-01 120VAC, 60Hz 117m³/h 78m³/h 180mA 15W 39db (A) 86mm 176 x 176mm + 0.4 1.3kg IP54/IP551 FIL TER FAN FF 018
1 Using fine filter mats type F5/M5 increases the protection type to IP55, but reduces the air volume
STEGO - PRODUCT CATALOGUESTEGO - PRODUCT CATALOGUE COOLING Art. No. Depth in enclosure Enclosure cut-out Weight (approx.) Filter mat Protection type 11800.0-00 16mm 97 x 97mm + 0.4 0.3kg G4 acc. to DIN EN 779, filtering degree 94% IP54 11801.0-00 16mm 125 x 125mm + 0.4 0.4kg G4 acc. to DIN EN 779, filtering degree 94% IP54/IP551 11802.0-00 16mm 176 x 176mm + 0.4 0.6kg G4 acc. to DIN EN 779, filtering degree 94% IP54/IP551 Time-saving assembly and maintenance STEGO´s filter fans are easily installed by one person from outside the cabinet. 1.) Make cut-out in the cabinet wall. The cut edge of the cabinet opening should be free of dirt, filings and grease. A template for the enclosure cut-out is included in the delivery of the filter fan. 2.) Remove protective film from the sealing strips on the mounting frame. Press mounting frame into the cabinet opening. The frame stays permanently in the cabinet. (For size 176mm and up we recommend additional screw fixing.) 3.) Electrically connect the axial fan using the clip connectors. Push the unit into the mounting frame. Fix using screws. 4.) Insert the filter mat in the hood. Clip on. Finished. Changing the filter mat or fan is quickly done by one person. To change the filter mat simply remove the filter hood, insert the new mat and snap the hood back again. No tools required. Maintenance of the fan can easily be done without removing the mounting frame (2). Filter mat 89 x 89mm 118 x 118mm 168 x 168mm Size 1 TECHNICAL DRAWINGS EXIT FIL TER EF 118 FIL TER MAT FM 086/FFM 086 DRILLING TEMPLATE FOR MOUNTING FRAME Installation sketch Size 2 Size 3