R +24V DC R %RH T 3 4 n.c. STEGO - PRODUCT CATALOGUE SMART SENSOR CLIMATE ANALOG CSS 014 | DC 24 V TECHNICAL DATA Measuring signals analog (4-20 mA) temperature, humidity Load resistance (external) ≤ 500 Ω Connection M12 round plug connector, IEC 61076-2-101, 4-pin, A-coded, shielded Electrical protection Reverse-polarity, short circuit, overvoltage protection Mounting clip for 35 mm DIN rail, EN 60715 and screw fi xing M5 Casing plastic according to UL94 V-0, light grey Dimensions 140 x 40 x 38 mm Weight ~ 50 g Fitting position vertical, connection on top Storage temperature -40 to +85 °C (-40 to +185 °F) Operating/Storage humidity < 90 % RH (non-condensing) Protection type1/Protection class IP20 (sensor only IP57) / III (SELV) Approvals VDE, UL File No. E500143 (acc. to IEC 61010-1/DIN EN 61010-1), EAC Note other measuring ranges on request 1 The PCB (printed circuit board) is coated on both sides with a certifi ed protective lacquer to protect against corrosion and for improvement of the tracking resistance. The compact Smart Sensor CSS 014 electronically records temperature and humidity and converts the measured data into a standardized analog 4-20 mA signal. The converted value signals can be utilized or further processed by a control or monitoring unit, e.g. a PLC control. The Smart Sensor is suitable for installation inside and outside the enclosure, even in harsh environmental conditions as can be found in the wind power industry: in shielded outdoor areas and exposed to vibrations. > Analog interface > Small size > Easy clip and/or screw fi xing > Quick connection (M12 plug-in connector) > High accuracy > Large temperature and humidity range > Various application areas (IEC 61010-1/DIN EN 61010-1) Art. No. Interface Operating voltage Power consumption max. Temperature measuring range Humidity measuring range Operating temperature 01420.2-00 4-20 mA (analog) DC 24 V (DC 12-30 V): 0 Ω < R < 160 Ω: (DC 12-30 V) 160 Ω < R < 500 Ω: (DC 20-30 V)
1.8 W (typically
0.4 W) -40 to +60 °C (-40 to +140 °F) /plusminus.tnum 1 K2 (Max. reaction time t60 195 s) 0 to 100 % RH ± 4%3 (Max. reaction time t60 8 s) -40 to +70 °C (-40 to +158 °F)
2 Tolerance data measured at nominal voltage DC 24 V and 500 Ω load resistance between +5 to +60°C
3 Tolerance data measured at nominal voltage DC 24 V and 500 Ω load resistance between 20 to 80 % RH
Example of connectionPin assignment for 4-pin M12 round plug connector Protection type IP57 MEASURING 89TECHNICAL DATASHEET