Technical content

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein. This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof. Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein. Jan 12, 2022 Product data sheet Characteristics XPSUAB11CP Safety module, Harmony Safety Automation, Cat.1, potential free NC/NC, NO/NC, PNP/ PNP, 24v AC/DC, screw Main Range of Product Harmony Safety Automation Product or Component Type Safety module Safety module name XPSUAB Safety module application For electrical monitoring of two-hand control stations For application with safety switchover contact For emergency stop, guard and light curtain monitoring Monitoring antivalent contacts Function of module Emergency stop monitoring 1-channel wiring Guard monitoring 1-channel wiring Monitoring 1 PNP sensor Monitoring two-hand control station type IIIA Magnetic switch monitoring Light curtain monitoring RFID switch Monitoring of electro-sensitive protection equipment (ESPE) Proximity sensor monitoring Safety level Can reach PL c/category 1 ISO 13849-1 Can reach SILCL 1 IEC 62061 Can reach SIL 1 IEC 61508 Safety reliability data MTTFd >= 30 years ISO 13849-1 Dcavg < 60 % ISO 13849-1 PFHd = 1177E-09 1/h ISO 13849-1 HFT = 0 IEC 62061 PFHd = 1177E-09 1/h IEC 62061 SFF > 60% IEC 62061 HFT=0 IEC 61508-1 PFHd = 1177E-09 1/h IEC 61508-1 SFF > 60% IEC 61508-1 Type = B IEC 61508-1 Electrical circuit type NC pair PNP pair Antivalent pair OSSD pair or flexible flexible with ferrule single conductor or flexible twin conductor Removable screw terminal block, 2 x 0.25...1 mm² flexible with ferrule without cable end, with bezel flexible with ferrule with cable end, with bezel [Us] Rated Supply Voltage Complementary Synchronisation time between inputs 0.5 s 2.2 s Type of start Automatic/manual/monitored Power consumption in W 1.5 W 24 V DC Power consumption in VA 3.5 VA 24 V AC 50/60 Hz Input protection type Internal, electronic Safety outputs 1 C/O

Maximum wire resistance 500 Ohm Input compatibility Normally closed circuit ISO 14119 XC limit switch ISO 14119 Mechanical contact ISO 14119 Normally closed circuit ISO 13850 Antivalent pair ISO 14119 OSSD pair IEC 61496-1-2 Two-hand control EN 574/ISO 13851-III A 3-wire proximity sensors PNP [Ie] rated operational current 5 A AC-1

3 A AC-15

5 A DC-1

3 A DC-13

3 A AC-1

1 A AC-15

2 A DC-1

1 A DC-13

Control Outputs 2 pulsed output Input/output type Semiconductor pulsed diagnostic output Z1, 20 mA [Ith] conventional free air thermal current 3 A Associated fuse rating 6 A gG relay output IEC 60947-1 Minimum output current 10 mA relay output Minimum output voltage 15 V relay output Maximum response time on input open 20 ms [Ui] rated insulation voltage 250 V 2)EN/IEC 60947-1 [Uimp] rated impulse withstand voltage 4 kV II EN/IEC 60947-1 Local signalling For power ON LED (green) For error LED (red) For start LED (yellow) For safety status LED (yellow) For safety input S12 LED (yellow) For safety input S13 LED (yellow) Mounting Support 35 mm symmetrical DIN rail Depth 4.72 in (120 mm) Ambient air temperature for operation -13…131 °F (-25…55 °C) Height 3.94 in (100 mm) Width 0.89 in (22.5 mm) Net Weight 0.44 lb(US) (0.200 kg) Environment Standards IEC 60947-5-1 IEC 61508-1 functional safety standard IEC 61508-2 functional safety standard IEC 61508-3 functional safety standard IEC 61508-4 functional safety standard IEC 61508-5 functional safety standard IEC 61508-6 functional safety standard IEC 61508-7 functional safety standard ISO 13849-1 functional safety standard IEC 62061 functional safety standard Product Certifications TÜV cULus IP degree of protection IP20 terminals)EN/IEC 60529 IP40 housing)EN/IEC 60529 IP54 mounting area)EN/IEC 60529 Relative Humidity 5…95 % non-condensing Ordering and shipping details Category 22477 - SAFETY MODULES (PREVENTA) Discount Schedule SAF2 GTIN 3606489601577 Nbr. of units in pkg. 1 Package weight(Lbs) 8.82 oz (250 g)

Unit Type of Package 1 PCE Package 1 Height 2.56 in (6.5 cm) Package 1 width 6.10 in (15.5 cm) Package 1 Length 5.31 in (13.5 cm) Unit Type of Package 2 S03 Number of Units in Package 2 16 Package 2 Weight 10.43 lb(US) (4.73 kg) Package 2 Height 11.81 in (30 cm) Package 2 width 11.81 in (30 cm) Package 2 Length 15.75 in (40 cm) Package 3 Height 11.81 in (30 cm) Offer Sustainability Sustainable offer status Green Premium product California proposition 65 WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov REACh Regulation REACh Declaration EU RoHS Directive Pro-active compliance (Product out of EU RoHS legal scope) EU RoHS Declaration Mercury free Yes RoHS exemption information Yes China RoHS Regulation China RoHS Declaration Environmental Disclosure Product Environmental Profile Circularity Profile End Of Life Information WEEE The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins. PVC free Yes

(A) : Product drawing (B) : Screw clamp terminal (C) : Side view (1) : Removable terminal blocks, top (2) : Removable terminal blocks, bottom (3) : LED indicators (4) : Start function selector (5) : Function selector (6) : Sealable transparent cover

(1) : A1-A2 (Power supply) (2) : S11-S12-S13 (Single-channel safety input) (3) : Y1-Y2 (Start) 11-12-14 : Output B2 : Common ground terminal Z1 : Pulsed output for diagnostics, not safety-related