Features
- Ten addressable Class B or five addressable Class A initiat- ing device circuits.
- Removable 12 AWG (3.31 mm²) to 18 AWG (0.821 mm²) plug-in terminal blocks.
- Status indicators for each point.
- Unused addresses may be disabled.
- Rotary address switches.
- Class A or Class B operation.
- FlashScan® or CLIP operation.
- Mount one or two modules in a BB-XP cabinet (optional).
- Mount up to six modules on a CHS-6 chassis in a CAB-3 Series, CAB-4 Series, EQ Cabinet Series, or BB-25 cabinet (optional).
- Mounting hardware included. Specifications Standby current: 3.5 mA (SLC current draw with all addresses used; if some addresses are disabled, the standby current decreases). Alarm current: 55 mA (assumes all ten LEDs solid ON). Temperature range: 32°F to 120°F (0°C to 49°C) for UL appli- cations; –10°C to +55°C for EN54 applications. Humidity: 10% to 85% noncondensing for UL applications; 10% to 93% noncondensing for EN54 applications. Dimensions: 6.8" (172.72 mm) high x 5.8" (147.32 mm) wide x 1.25" (31.75 mm) deep. Shipping weight: 1.1 lb. (0.499 kg) including packaging. Mounting options: CHS-6 chassis, BB-25 cabinet, BB-XP cab- inet, CAB-3 Series cabinet (see DN-3549), CAB-4 Series cabi- net (see DN-6857), or EQ Cabinet Series (see DN-60229). Wire gauge: 12 AWG (3.31 mm²) to 18 AWG (0.821 mm²). Power-limited circuits must employ type FPL, FPLR, or FPLP cable as required by Article 760 of the NEC. XP10-M is shipped in Class B position ; remove shunt for Class A operation. Maximum SLC wiring resistance: 40 or 50 ohms, panel dependent. Maximum IDC wiring resistance: 1500 ohms. Maximum IDC voltage: 12 VDC. Maximum IDC current: 1 mA. Agency Listings and Approvals The listings and approvals below apply to the XP10-M Ten-Input Monitor Module. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status.
- UL Listed: file S3705.
- ULC Listed: file S635 (XP10-MA).
- CSFM approved: file 7300-0028:219.
- FM approved.
- MEA approved: file 43-02-E.
- Maryland State Fire Marshal approved: Permit #2106. Product Line Information XP10-M: Ten-input monitor module. XP10-MA: Same as above with ULC Listing. BB-XP: Optional cabinet for one or two modules. Dimensions, DOOR: 9.234" (23.454 cm) wide (9.484" [24.089 cm] including hinges), x 12.218" (31.0337 c m) high, x 0.672" (1.7068 cm) deep; BACKBOX: 9.0" (22.860 cm) wide (9.25" [23.495 cm] including hinges), x 12.0" (30. 480 cm) high x 2.75" (6.985 cm); CHASSIS (installed): 7.150" (18.161 cm) wide overall x 7.312" (18.5725 cm) high interior overall x 2.156" (5.4762 cm) deep overall. BB-25: Optional cabinet for up to six modules mounted on CHS-6 chassis (below). Dimensions, DOOR: 24.0" (60.96 cm) wide x 12.632" (32.0852 cm) high, x 1.25" (3.175 cm) deep, hinged at bottom; BACKBOX: 24.0" (60.96 cm) wide x 12.550" (31.877 cm) high x 5.218" (13.2537 cm) deep. CHS-6: Chassis, mounts up to six modules in a CAB-3 Series (see DN-3549), CAB-4 Series (see DN-6857) cabinet, EQ Cabi- net Series (see DN-60229), or BB-25. 6923xp10.jpg