XB4BK134M5 SCHNEIDER | Alldatasheet

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 5

Technical content

Harmony XB4, Illuminated selector switch, metal, red, Ø22, 3 positions, stay put, 230...240 V AC, 1 NO + 1 NC Main Range of product Harmony XB4 Product or Component Type Illuminated selector switch Device short name XB4 Bezel material Chromium plated metal Fixing collar material Zamak Head type Standard Mounting diameter 0.87 in (22 mm) Sale per indivisible quantity 1 Shape of signaling unit head Round Type of operator stay put Operator profile Red standard handle Operator position information 3 positions +/- 45° Contacts type and composition 1 NO + 1 NC Contact operation Slow-break Connections - terminals Screw clamp terminals, <= 2 x 1.5 mm² with cable end conforming to EN/IEC 60947-1 Screw clamp terminals, >= 1 x 0.22 mm² without cable end EN/IEC 60947-1 Light source Protected LED Bulb base Integral LED [Us] rated supply voltage 230...240 V AC at 50/60 Hz Complementary Resistance to high pressure washer 1015.26 psi (7000000 Pa) 131 °F (55 °C) 0.1 m Contacts usage Standard contacts Positive opening With EN/IEC 60947-5-1 appendix K Operating torque 1.24 lbf.in (0.14 N.m) NO changing electrical state Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications Sep 29, 2021

Mechanical durability 1000000 cycles Shape of screw head Cross compatible with Philips no 1 screwdriver Cross compatible with pozidriv No 1 screwdriver Slotted compatible with flat Ø 4 mm screwdriver Slotted compatible with flat Ø 5.5 mm screwdriver Contacts material Silver alloy (Ag/Ni) Short-circuit protection 10 A cartridge fuse gG EN/IEC 60947-5-1 [Ith] conventional free air thermal current

10 A EN/IEC 60947-5-1

[Ui] rated insulation voltage 600 V 3)EN 60947-1 [Uimp] rated impulse withstand voltage 6 kV EN 60947-1 [Ie] rated operational current 3 A 240 V, AC-15, A600 EN/IEC 60947-5-1

6 A 120 V, AC-15, A600 EN/IEC 60947-5-1

0.1 A 600 V, DC-13, Q600 EN/IEC 60947-5-1

0.27 A 250 V, DC-13, Q600 EN/IEC 60947-5-1

0.55 A 125 V, DC-13, Q600 EN/IEC 60947-5-1

1.2 A 600 V, AC-15, A600 EN/IEC 60947-5-1

Electrical durability 1000000 cycles, AC-15, 2 A 230 V 3600 cyc/h 0.5 EN 60947-5-1 appendix C 1000000 cycles, AC-15, 3 A 120 V 3600 cyc/h 0.5 EN 60947-5-1 appendix C 1000000 cycles, AC-15, 4 A 24 V 3600 cyc/h 0.5 EN 60947-5-1 appendix C 1000000 cycles, DC-13, 0.2 A 110 V 3600 cyc/h 0.5 EN 60947-5-1 appendix C 1000000 cycles, DC-13, 0.5 A 24 V 3600 cyc/h 0.5 EN 60947-5-1 appendix C Electrical reliability Λ < 10exp(-6) 5 V 1 mA in clean environment EN/IEC 60947-5-4 Λ < 10exp(-8) 17 V 5 mA in clean environment EN/IEC 60947-5-4 Signalling type Steady Supply voltage limits 195…264 V AC Current Consumption 14 mA Service life 100000 h at rated voltage and 25 °C Surge withstand 1 kV IEC 61000-4-5 Device presentation Complete product Environment Protective treatment TH Ambient Air Temperature for Storage -40…158 °F (-40…70 °C) Ambient Air Temperature for Operation Electrical shock protection class Class I IEC 60536 IP degree of protection IP66 conforming to IEC 60529 IP67 IP69 IP69K NEMA degree of protection NEMA 13 NEMA 4X IK degree of protection IK06 conforming to IEC 50102 Standards EN/IEC 60947-1 EN/IEC 60947-5-4 EN/IEC 60947-5-1 EN/IEC 60947-5-5 CSA C22.2 No 14 JIS C8201-5-1 UL 508 JIS C8201-1 Product Certifications DNV GL CSA BV UL LROS (Lloyds register of shipping) Vibration resistance 5 gn 2…500 Hz)IEC 60068-2-6 Shock resistance 30 gn 18 ms) half sine wave acceleration IEC 60068-2-27 50 gn 11 ms) half sine wave acceleration IEC 60068-2-27

Resistance to fast transients 2 kV IEC 61000-4-4 Resistance to electromagnetic fields 9.14 V/m (10 V/m) IEC 61000-4-3 Resistance to electrostatic discharge 6 kV on contact (on metal parts) IEC 61000-4-2 8 kV in free air (in insulating parts) IEC 61000-4-2 Electromagnetic emission Class B conforming to IEC 55011 Ordering and shipping details GTIN 3389118223257 Nbr. of units in pkg. 1 Package weight(Lbs) 3.88 oz (110 g) Packing Units Unit Type of Package 1 PCE Package 1 Height 1.34 in (3.4 cm) Package 1 width 2.09 in (5.3 cm) Package 1 Length 3.43 in (8.7 cm) Unit Type of Package 2 S02 Number of Units in Package 2 50 Package 2 Weight 13.13 lb(US) (5.955 kg) Package 2 Height 5.91 in (15 cm) Package 2 width 11.81 in (30 cm) Package 2 Length 15.75 in (40 cm) Offer Sustainability Sustainable offer status Green Premium product California proposition 65 WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov REACh Regulation REACh Declaration REACh free of SVHC Yes EU RoHS Directive Pro-active compliance (Product out of EU RoHS legal scope) EU RoHS Declaration Mercury free Yes RoHS exemption information Yes China RoHS Regulation China RoHS declaration Environmental Disclosure Product Environmental Profile Circularity Profile End of Life Information WEEE The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins. Contractual warranty Warranty 18 months

e : clamping thickness: 1 to 6 mm / 0.04 to 0.24 in.

Panel Cut-out for Pushbuttons, Switches and Pilot Lights (Finished Holes, Ready for Installation) Connection by Screw Clamp Terminals or Plug-in Connectors or on Printed Circuit Board Connection by Faston Connectors (1) Diameter on finished panel or support (2) 40 mm min. / 1.57 in. min. (3) 30 mm min. / 1.18 in. min. (4) Ø 22.5 mm / 0.89 in. recommended (Ø 22.3 mm 0 +0.4 / 0.88 in. 0 +0.016) (5) 45 mm min. / 1.78 in. min. (6) 32 mm min. / 1.26 in. min.