WM22-DIN ETC2 | Alldatasheet

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 10

Technical content

Specifications are subject to change without notice WM22-DINDS1003 1 Product description Three-phase power analyzer with built-in configuration key-pad; Particularly indicated for the analysis of main, secondary and energy metering electri- cal variables. Housing for DIN-rail or wall- mounting, IP40 (front) pro- tection degree. Completely sealable housing. In case of dir ect connection up to 90A, the measuring input terminals are suitable for cables with a cross-sec- tion area from 6 to 35 mm The special design of the instrument’s housing allows to add at any time the inter - face modules, even when the instrument is alr eady installed. The following modules are available: - for all versions: pulses out - put; - only for the versions with auxiliary power supply: analogue output, RS485 port or alarm output. Energy Management Power Analyzer with plug-in Output Modules Type WM22-DIN Type selection Power supply For all versions A: 24VAC -15+10%, 50-60Hz B: 48VAC -15+10%, 50-60Hz C: 115VAC -15+10%, 50-60Hz D: 230VAC -15+10%, 50-60Hz 4: 18 to 60VDC 5: 77 to 143VDC AV2, AV8 and AV9 only X: Self Power Supply 400VL-L (-20+15%, 50-60Hz) 208VL-L (-20+15%, 50-60Hz) 220VL-L (-10+15%, 50-60Hz) Range Code Auxiliary Power Supply: AV0: 208VL-L/20(90)AAC [3] AV1: 400VL-L/20(90)AAC [1] AV3: 660VL-L/20(90)AAC [2] AV4: 208VL-L/5(10)AAC [3] AV5: 400VL-L/5(10)AAC [1] AV6: 100VL-L/5(10)AAC [3] AV7: 660VL-L/5(10)AAC [2] Self Power Supply: AV2: 220VL-L/20(90)AAC [4] AV8: 208VL-L/20(90)AAC [1] AV9: 400VL-L/20(90)AAC [1] Slot A (retransmission) X: None O: AO2900 module Dual open collector out- put Three operating modes:

  • two pulse outputs (kWh and kvarh);
  • one alarm output and one pulse output (kWh or kvarh)
  • one output which is remotely controlled by a serial port and one pulse output (kWh or kvarh) R: AO2910 module. One relay output + one open collector output. Operation modes like module AO2900. Slot B (retransmission) Only with A-B-C-D-4 power supply XX: None A1: AO2920 module 0-20mADC analogue output V1: AO2921 module 0-10VDC analogue output S0: AR2950 module RS422/485 serial port Model Range code System Power supply Slot A Slot B How to order WM22-DIN AV5 3 X X XX System 3 : Three-phase, unbalanced load with or without neutral
  • Class 0.5 (current/voltage)
  • Three-phase power analyzer
  • Back-lighted LCD
  • 4 x 31/2 DGT instantaneous variables read out
  • 71/2 DGT energy read-out
  • Measurements of system and phase variables: W, Wdmd, var, VA, VAdmd, PF (cosϕ), V, A, Hz, THD-A, THD-V
  • Measurements of total energies: kWh, kvarh
  • Measurements of partial energies: kWh, kvarh
  • Energy measurements according to EN61036 and EN61268
  • TRMS measurements of distorted wave forms (voltages/currents)
  • Two basic models: direct connection 20(90)AAC, CT 5(10)AAC and VT connection
  • Maximum value indication of W dmd and VA dmd (only 5A version); maximum value indication of A (only 90A version)
  • Self power supply (available for some models only) or auxiliary power supply: 24V, 48V, 115V, 230V, 50-60Hz; 18 to 60VDC, 77 to 143VDC
  • Degree of protection (front): IP 40
  • Front dimensions: 9 DIN modules
  • Analogue output by means of optional module (20mA or 10VDC)
  • RS 422/485 Serial port by means of optional module
  • Alarm output by means of optional module
  • Dual pulse output by means of optional module
  • Control of phase asymmetry Important note:
  • The models from AV0 to AV7 can be equipped with any type of available modules (slot A and B).
  • The models AV8 and AV9 can be equipped only with the “O” and “R” type modules.
  • The AV8 and AV9 models can measure all the parameters even if the three phase system being connected is missing one phase.
  • The Av2 model is suitable only for three-phase unbalanced sys- tem without neutral.

2 Specifications are subject to change without notice WM22-DINDS1003

the following ranges: 0 and 20mADC, 0 and 10VDC Response time System variables V, W, VA, var, PF (cosϕ) FFT off, filter off 900ms FFT on, filter on 1.4s variables THD-V, THD-A Filter off 3s Ripple ≤ 1% according to IEC 60688-1, EN 60688-1 Load 20 mADC ≤ 500 Ω

10 VDC ≥ 10 kΩ

Insulation By means of optocouplers,

2000 VRMS between output

Analogue outputs (on request) Number of outputs 1 Range 0 to 20 mADC (AO2920 module slot B, only for versions with auxiliary power supply) 0 to 10VDC (AO2921 module slot B, only for versions with auxiliary power supply) Accuracy ±0.5% F .S. Temperature drift ≤ 300 ppm/ °C Scaling factor Programmable within the whole range of retransmission; it allows the retransmission of all the values included in Number of inputs Current 3 Voltage 4 Accuracy (display, RS485) Ib: 5A, Imax: 10A Ib: 20A, Imax:90A Un: see previous page “Range code” Current from 0.003Ib to 0.2Ib: ±(0.5%RDG +3DGT) from 0.2Ib to Imax: ±(0.5%RDG +1DGT) Voltage in the range Un: ±(0,5% RDG + 1DGT) Frequency ±0.1% RDG (50 to 60 Hz) Active power 0.1Ib to Imax, in the Un range; PF 0.5L, PF 0.8C, 0.2Ib to Imax, in the Un range Reactive power (@ 25°C ± 5°C, R.H. ≤ 90%) ±(2% RDG +1DGT). sin ϕ 1, 0.05Ib to Imax, in the Un range; sinϕ 0.5L, sinϕ 0.5C, 0.1Ib to Imax, in the Un range Apparent power 0.1Ib to Imax, in the Un range Energies (@ 25°C ± 5°C, R.H. ≤ 90%) Class 1 acc. to EN61036 Class 2 acc. to EN61268 Ib: 5A, Imax: 10A 0.1Ib: 500mA, Start up corrent: 20mA Un: see table “range code” Ib: 20A, Imax: 90A 0.1Ib: 2A, Start up current: 80mA Un: see table “range code” Harmonic distortion ±3% f.s. (f.s.: 100%) (@ 25°C ± 5°C, R.H. ≤ 90%) up to the 7 th harmonic; Un: see table “range code” Ib 5A Imin: 500mA; Imax: 15Ap; Ib 20A Imin: 2A; Imax: 127Ap; Additional errors Acc. to EN61036, EN61268 Wave form <1% (3 rd harmonic: 10%) Voltage asymmetry < 0.5% (referred to Un) Magnetic induction 0 (up to 0.5 mT) HF Electromagnetic fields < 1% Operation of accessories 0 Temperature drift ≤ 200ppm/°C Sampling rate 1000 samplings/s @ 50Hz Display Type Back-lighted LCD Instantan. variables read-out 4x3 1/2 DGT Energies Total:1x7 1/2 DGT Partial: 1x71/2 DGT Max. and Min. indication Max. 1999 (19999999), Min. 0 Measurements Current, voltage, power, energy, power factor, frequen- cy, harmonic distortion (see display specs). TRMS measurements of distorted wave forms. Coupling type Direct Crest factor Ib 5A ≤3 (15A max. peak) Ib 20A ≤6 (127A max. peak) Current overload 5(10) A, for 10ms 300 A max, @ 50Hz 5(10) A, for 500ms 200 A max, @ 50Hz 5(10) A, permanent 10A, @ 50Hz 20(90) A, for 10ms 2700A max, @ 50Hz 20(90) A, permanent 90A, @ 50Hz Voltage overload Permanent 1.2 Un For 1s 2 Un Input impedance 400VL-L(AV1-AV5-AV9) > 720K Ω 208VL-L(AV0-AV4-AV8-AV2) > 720K Ω 660VL-L(AV3-AV7) > 1.97M Ω 100VL-L(AV6) > 400K Ω 5(10) A (AV4-AV5-AV6-AV7) < 0.3VA 20(90) A (AV0-AV1-AV3-AV8-AV9) < 4VA 20(90) A (AV2) < 4VA Frequency 50 to 60 Hz Interface module specifications Input specifications WM22-DIN

Specifications are subject to change without notice WM22-DINDS1003 3 RS422/RS485 (on request) AR2950 module Type Multidrop bidirectional (static and and dynamic variables) Connections 2 or 4 wires, max. distance 1200m, termination directly on the module Addresses 255, selectable by key-pad Protocol MODBUS/JBUS Data (bidirectional) Dynamic (reading only) Phase and system variables: see table “Display pages” Static (writing only ) All the programming data, reset of energy, activation of static output. Stored energy (EEPROM) max. 19.999.999 kWh/kvarh Data format 1 start bit, 8 data bit, no parity, 1 stop bit Baud-rate 9600 bit/s Insulation By means of optocouplers, 2000 V RMS output to measuring inputs 2000 V RMS output to supply input Digital outputs (on request) AO2900 module To be used as alarm, energy retransmission, or remote static outputs. Three working modes are selectable:

  • two pulse outputs (kWh and kvarh);
  • one alarm output and one pulse output (kWh or kvarh)
  • one output remotely con- trolled by means of the serial port and one pulse output (kWh or kvarh) Pulse outputs Number of outputs 2 Number of pulses From 0.01 to 100 pulses programmable according to the selected CT and VT ratios Output type Open collector (transistor NPN) VON 1.2 VDC / max. 100 mA VOFF 30 VDC max. Pulse duration 220 ms (ON), ≥ 220 ms (OFF) According to DIN43864 Insulation By means of optocouplers,

2000 VRMS outputs to

measuring inputs,

2000 VRMS output to

supply input. Insulation between the two outputs: functional Alarm output Number of outputs 1 Alarm type Up alarm, down alarm phase asymmetry, phase loss. Setpoint adjustment 0 to 100% of the electrical scale Hysteresis 0 to 100% of the electrical scale On-time delay 0 to 255 seconds Response time system variables V, W, VA, var, PF (cos FFT off, filter off 700ms FFT on, filter on 1.2s variables THD-V, THD-A Filter off 3s Output type Open collector (transistor NPN) VON 1.2 VDC / max. 100 mA VOFF 30 VDC max. Insulation By means of optocouplers, measuring input, 2000 V RMS output to supply input. Insulation between the two outputs: functional AO2910 module Relay + open collector output. Working mode like AO2900. Pulse output One static output+one relay output, other characteristics like AO2900. Alarm output Only relay output, other characteristics like AO2900. Output type Static type like module AO2900; Relay type: SPDT, AC1, AC15: 1AAC @250VAC Insulation By means of optocouplers, 2000 V RMS outputs to measuring inputs, supply input. Insulation between the two outputs: 2000 V RMS Interface module specifications (cont.) WM22-DIN

4 Specifications are subject to change without notice WM22-DINDS1003

Pulse voltage (1.2/50µs) 8kV (EN61000-4-5) Standards Safety IEC664-1 Metrology Energy measurements: EN61036, EN61268. Pulse output DIN43864 Approvals CE Connections 5(10) A Screw-type, Cable cross-section area 4 mm 2 Connections 20(90) A Screw-type, Min./Max. cable cross-section area6 mm2 / 35 mm2 Min./Max. screws tightening torque 2 Nm / 6 Nm Housing Dimensions 162.5 x 90 x 63 mm Material ABS, NORYL, PC self-extinguishing: UL 94 V-0 Mounting DIN-rail and wall Degree of protection Front: IP40 Connections: IP20 Weight 800 g approx. (packing included) Operating 0 to +55°C temperature (R.H. < 90% non-condensing 40°C) Storage -20 to +60°C temperature (R.H. < 90% non-condensing 40°C) Installation category Cat. III (IEC 664) Insulation 2000 VRMSbetween all inputs / outputs to earth Dielectric strength 4000 VRMS for 1 minute Noise rejection CMRR 100 dB, 48 to 62 Hz EMC Burst 4kV/level 4 (EN61000-4-4) Immunity to irradiated electromagnetic fields 10V/m 26-1000MHz (EN61000-4-3) Electrostatic discharges 15kV (EN61000-4-2) Radio frequency emissions according to CISPR 14 and CISPR 22 Electrical range Programmable within the whole measuring range. Filter Filter operating range 0 to 99.9% of the input electrical scale. Filter coefficient 1 to 16 Filter action Alarm, analogue and serial output (fundamental variables: V, A, W and their derived ones). Display Up to 4 variables per page System variables Page 1: W-var-PF (cosϕ) Page 2: W dmd - VA dmd - Hz Single phase variables Page 3: THD-V Page 4: THD-A System variables Page 5: kWh total Page 6: kvarh total Page 7: kWh partial Page 8: kvarh partial Single phase variables Page 9: VL-N Page 10: A 20(90) A Page 11a: A MAX 5(10) A Page 11b: W dmd MAX VA dmd MAX Page 12: W Page 13: VA Page 14: var Page 15: PF (cosϕ) Password Numeric code of max. 3 digits 2 protection levels of the programming data 1st level Password “0”, no protection 2nd level Password from 1 to 1000, all data are protected System selection Three-phase with neutral Three-phase without neutral Transformer ratio CT 1 to 5000 VT 1.0 to 199.9 and 200 to 1999 Note: The CT ratio* VT ratio must never exceed the value 5000. The current measuring inputs can manage CT’s with a secondary of 1A and 5A (the accuracy always refer to 5A) Scaling factor Operating mode Compression/expansion of the measuring range to be connected to the analogue output. General Specifications Self supplied version 400VL-L -20% +15%, 50-60Hz 208VL-L 220VL-L Auxiliary power supply 230VAC -15 +10%, 50-60Hz 115VAC -15 +10%, 50-60Hz 48VAC -15 +10%, 50-60Hz 24VAC -15 +10%, 50-60Hz 18 to 60VDC 77 to 143VDC Energy consumption ≤ 7VA Supply specifications Software functions WM22-DIN

Specifications are subject to change without notice WM22-DINDS1003 5 Function description Figure A The sign of measured quantity and output quantity remains the same. The output quantity is proportional to the mea- sured quantity. Input and output scaling capability Working examples of the analogue output (Y) versus the input variable (x) - (input/output scaling possibilities). Figure C The sign of measured quantity and output quantity remains the same. On the range X0...X1, the output quantity is zero. The range X1...X2 is deli- neated on the entire output range Y0=Y1...Y2 and thus presented in strongly expan- ded form. Figure B The sign of measured quantity and output quantity remains the same. With the measured quantity being zero, the output quantity already has the value Y1 = 0.2 Y2. Live zero output. 0 50 A 100 A 0 10 mA 20 mA

80 V 100 V 120 V

Waveform of the signals that can be measured Figure D Sine wave, undistorted Fundamental content 100% Harmonic content 0% A rms = 1.1107 | A | Figure E Sine wave, indented Fundamental content 10...100% Harmonic contents 0...90% Frequency spectrum: 3rd to the 16th harmonic Additional error: <1% rdg Figure F Sine wave, distorted Fundamental content 70...90% Harmonic content 10...30% Frequency spectrum: 3rd to the 16th harmonic Additional error: <0.5% rdg Mode of Operation WM22-DIN Anaysis principle FFT Harmonic measurement Current Up to the 7th harmonic Voltage Up to the 7 th harmonic Type of harmonics THD (VL1), THD (VL2), THD (VL3), THD (AL1) THD (AL2), THD (AL3) Read-out THD % System The harmonic distortion can be measured in 3-wire or 4-wire systems. Harmonic distortion analysis

6 Specifications are subject to change without notice WM22-DINDS1003

Variables that can be displayed No 1st variable 2 nd variable 3 rd variable 4 th variable Notes

1 W sys PF sys Var sys sys = system

2 W dmd Hz VA dmd dmd = demand

(integration time from 1 to 30 minutes) 3V L1 THD V L2 THD V L3 THD THD = tot. harmonic distortion 4 AL1 THD A L2 THD A L3 THD THD = tot. harmonic distortion 5 kWh total energy 6 kvarh total energy 7 kWh partial energy 8 kvarh partial energy 9V L1 VL2 VL-3 VL-L sys sys = system

10 A L1 AL2 AL3 Err Err = in case of negative power

11a W dmd MAX VA dmd MAX Only version 1-5A, dmd = demand 11b A L1 MAX A L2 MAX A L3 MAX Only version 90A

12 WL1 WL2 WL3 W sys sys = system

13 VA L1 VAL2 VAL3 VA sys The system value remains always 0

14 VarL1 VarL2 VarL3 Var sys if the neutral is not connected

15 PF L1 PFL2 PFL3 PF sys

(TPF) Total harmonic distortion Used calculation formulas Phase variables Instantaneous effective voltage Instantaneous active power Instantaneous power factor (TPF) Instantaneous effective current Instantaneous apparent power Instantaneous reactive power Display pages WM22-DIN N° Variable Notes

1 V sys sys = system

2 W sys sys = system

3 var sys sys = system

4 VA sys sys = system

5 PF sys sys = system

List of the of the variables that can be connected to the analogue and alarm output N° Variable Notes 6 THD-V Max. THD value among the three phases 7 THD-A Max. THD value among the three phases

8 VA dmd Power demand in the selected

9 W dmd integration time

10 ASY Phase asymmetry

Note: i = phase (L1, L2 or L3) T = variable (V or I) n = harmonic order Consumption recording Note: i = phase (L1, L2 or L3) P = active power Q = reactive power t1, t2 = starting and ending time points of consumption recording n = time unit ∆t = time interval of consumption recording n1,n2 =starting and ending discrete time points of consumption recording

Specifications are subject to change without notice WM22-DINDS1003 7 Type Inputs Power supply Ordering code WM22-DIN AV9.3.X. 400V L-L, 20(90)A Self power supply AF2100 WM22-DIN AV8.3.X. 208V L-L, 20(90)A Self power-supply AF2101 WM22-DIN AV2.3.D. 220V L-L, 20(90)A Self power-supply AF2144 WM22-DIN AV1.3.D. 400V L-L, 20(90)A 230VAC, 50-60Hz AF2102 WM22-DIN AV0.3.D. 208V L-L, 20(90)A 230VAC, 50-60Hz AF2103 WM22-DIN AV3.3.D. 660V L-L, 20(90)A 230VAC, 50-60Hz AF2104 WM22-DIN AV1.3.C. 400V L-L, 20(90)A 115VAC, 50-60Hz AF2105 WM22-DIN AV0.3.C. 208V L-L, 20(90)A 115VAC, 50-60Hz AF2106 WM22-DIN AV3.3.C. 660V L-L, 20(90)A 115VAC, 50-60Hz AF2107 WM22-DIN AV1.3.B. 400V L-L, 20(90)A 48VAC, 50-60Hz AF2108 WM22-DIN AV0.3.B. 208V L-L, 20(90)A 48VAC, 50-60Hz AF2109 WM22-DIN AV3.3.B. 660V L-L, 20(90)A 48VAC, 50-60Hz AF2110 WM22-DIN AV1.3.A. 400V L-L, 20(90)A 24VAC, 50-60Hz AF2111 WM22-DIN AV0.3.A. 208V L-L, 20(90)A 24VAC, 50-60Hz AF2112 WM22-DIN AV3.3.A. 660V L-L, 20(90)A 24VAC, 50-60Hz AF2113 WM22-DIN AV5.3.D. 400VL-L, 5(10)A 230VAC, 50-60Hz AF2114 WM22-DIN AV4.3.D. 208V L-L, 5(10)A 230VAC, 50-60Hz AF2115 WM22-DIN AV7.3.D. 660VL-L, 5(10)A 230VAC, 50-60Hz AF2116 WM22-DIN AV5.3.C. 400V L-L, 5(10)A 115VAC, 50-60Hz AF2117 WM22-DIN AV4.3.C. 208V L-L, 5(10)A 115VAC, 50-60Hz AF2118 WM22-DIN AV7.3.C. 660V L-L, 5(10)A 115VAC, 50-60Hz AF2119 WM22-DIN AV5.3.B. 400VL-L, 5(10)A 48VAC, 50-60Hz AF2120 WM22-DIN AV4.3.B. 208V L-L, 5(10)A 48VAC, 50-60Hz AF2121 WM22-DIN AV7.3.B. 660V L-L, 5(10)A 48VAC, 50-60Hz AF2122 WM22-DIN AV5.3.A. 400VL-L, 5(10)A 24VAC, 50-60Hz AF2123 WM22-DIN AV4.3.A. 208V L-L, 5(10)A 24VAC, 50-60Hz AF2124 WM22-DIN AV7.3.A. 660V L-L, 5(10)A 24VAC, 50-60Hz AF2125 WM22-DIN AV6.3.D. 100V L-L, 5(10)A 230VAC, 50-60Hz AF2126 WM22-DIN AV6.3.C. 100V L-L, 5(10)A 115VAC, 50-60Hz AF2127 WM22-DIN AV6.3.B. 100V L-L, 5(10)A 48VAC, 50-60Hz AF2128 WM22-DIN AV6.3.A. 100V L-L, 5(10)A 24VAC, 50-60Hz AF2129 WM22-DIN AV1.3.4 / [5] 400VL-L, 20(90)A 18-60VDC [77-143VDC] AF2130 [AF2137] WM22-DIN AV0.3.4 / [5] 208V L-L, 20(90)A 18-60VDC [77-143VDC] AF2131 [AF2138] WM22-DIN AV3.3.4 / [5] 660V L-L, 20(90)A 18-60VDC [77-143VDC] AF2132 [AF2139] WM22-DIN AV5.3.4 / [5] 400V L-L, 5(10)A 18-60VDC [77-143VDC] AF2133 [AF2140] WM22-DIN AV4.3.4 / [5] 208V L-L, 5(10)A 18-60VDC [77-143VDC] AF2134 [AF2141] WM22-DIN AV7.3.4 / [5] 660VL-L, 5(10)A 18-60VDC [77-143VDC] AF2135 [AF2142] WM22-DIN AV6.3.4 / [5] 100V L-L, 5(10)A 18-60VDC [77-143VDC] AF2136 [AF2143] Available models Possible module combinations Available modules Power supply Self p.s. Auxiliary p.s. Basic unit Slot A Slot B Slot A Slot B Analogue output RS485 Serial Output (*) AV2 only Type Channels Code Open collector output 2 AO2900 0-20mADC analogue output 1 AO2920 Relay + open c. output 2 AO2910 Power supply Self p.s. Auxiliary p.s. Basic unit Slot A Slot B Slot A Slot B Open collector output Relay + open c. output Type Channels Code 0-10VDC Analogue Output 1 AO2921 RS485 Serial Output 1 AR2950 WM22-DIN (*) (*)

8 Specifications are subject to change without notice WM22-DINDS1003

20(90)A model: three-phase unbalanced load Direct connection (3-phase system)Direct connection (3-phase system)Direct connection (3-phase system+N) Self-power supply Fig. 3 5(10)A model: three-phase unbalanced load Direct connection (3-phase system + N) Direct connection (3-phase system with or without neutral) CT connection (3-phase system+N) Self-power supply Fig. 4 5(10)A model: three-phase unbalanced load VT and CT connection (3-phase system + N) WM22-DIN 20(90)A model: three-phase unbalanced load Auxiliary power supply Fig. 2Auxiliary power supply Fig. 1 Auxiliary power supply Fig. 5 Auxiliary power supply Fig. 6 Auxiliary power supply Fig. 9 AC power supply AC power supply AC power supply AC power supply AC power supply LOAD LOAD LOAD LOAD LOAD LOADLOAD CT ARON connection (3-phase system) VT and CT ARON connection (3-phase system) Auxiliary power supply Fig. 8Auxiliary power supply Fig. 7 AC power supply AC power supply LOAD LOAD

Specifications are subject to change without notice WM22-DINDS1003 9 Keys for: - value programming; - function selection; - displaying the measuring pages. 2. Display LCD with alphanumeric indications to: - display configuration parameters; - display all the measured variables. 3. Removable label Label to write the instrument ID number. 4. Hidden dip-switch Enable/ disable the access to the programming procedure. Front panel description 1. Key-pad To program configuration parameters and to display variables. S-key to enter programming and confirm selections; Wiring diagrams (optional modules) Only open collector outputs: the grounds of the outputs are separated, and therefore it’s possible to carry out, for the same module, two different connections. The load resistance (Rc) must be designed so that the closed contact current is lower than 100mA; the VDC voltage must be lower than or equal to 30V. VDC: power supply voltage output. Vo+: positive output contact (open collector transistor). GND: ground output contact (open collector transistor). Current and voltage 4-wire connection 2-wire connection Open collector output Fig.10 Analogue output Fig. 12 RS485 Serial output Fig. 13 RS485 Serial output Fig. 14 WM22-DIN VDC max 30V Relay + open collector output Fig. 11

10 Specifications are subject to change without notice WM22-DINDS1003

Dimensions and panel cut-out Dual output open collector module RS485 serial output module AAOO 22992200:: 0-20 mA AAOO 22992211: 0-10 V AAOO 22990000 Relay output module + open collector output AAOO 22991100 AARR 22995500 WM22-DIN