MODEL: WL40W1F-DAC4A WL40W1F SPECIFICATIONS ES-9083 Rev.1 Page 1/7 http://www.m-system.co.jp/ Wireless I/O WL40F Series WIRELESS I/O UNIT Modbus-RTU Transparent 900MHz Band Wireless Device (Child Device), Built-in I/O, 2 contact Inputs, 2 NPN Transistor Outputs 60 (2.36) 155 (6.10) [260 (10.24)] mm (inch) MODEL: WL40W1F-DAC4A-[1][2]

ORDERING INFORMATION

  • Code number: WL40W1F-DAC4A-[1][2] Specify a code from below for each [1] and [2]. (e.g. WL40W1F-DAC4A-R/E/Q)
  • Specify the specification for option code /Q (e.g. /C01) I/O TYPE DAC4A: 2 contact inputs, 2 NPN transistor outputs [1] POWER INPUT DC Power S: 12 V DC (Operational voltage range 12 V ±10 %, ripple 10 %p-p max.) R: 24 V DC (Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) [2] OPTIONS (multiple selections) Antenna /S: Sleeve antenna /E: Rooftop antenna Other Options blank: none /Q: Option other than the above (specify the specification) SPECIFICATIONS OF OPTION: Q COATING (For the detail, refer to M-System's web site.) /C01: Silicone coating /C02: Polyurethane coating /C03: Rubber coating FUNCTIONS & FEATURES This unit
  • Operates as a 900MHz band wireless device (child device).
  • Incorporates the module compliant with FCC Part 15, and can be used only in the United States.
  • Connects inputs/outputs by wireless communication using Modbus-RTU protocol.

RELATED PRODUCTS

For related products of wireless device, refer to M-System's web site.

  • PC configurator software (model: W920FCFG) Downloadable at M-System’s web site. A dedicated cable is required to connect the unit to the PC. Please refer to the internet software download site or the users manual for the PC configurator software for applicable cable types. Maintenance software Maintenance console: MH920 Console International (model: MH920CI) (OKI) (Maintenance software is downloadable at M-System’s web site.) Coaxial cable
  • 7.5 m extension cable for rooftop antenna (model: CX- SAC0SAD0Q0750) (OKI) Using 7.5 m coaxial cable for extension decreases transmission distance. GENERAL SPECIFICATIONS Connection Wireless network: SMA coaxial connector Power supply: Tension clamp (Front Twinconnection) Applicable wire size: 0.2 - 2.5 mm2, stripped length 10 mm Input/output: Separable tension clamp terminal Applicable wire size: 0.2 - 1.5 mm2, stripped length 10 mm Maintenance: Mini USB type B female connector Isolation: Power input to FE1 to Contact input to Transistor output to antenna connector Indicator LED: Power WIRELESS SPECIFICATIONS Communication Standard: IEEE 802.15.4g Frequency: 900MHz band (902 - 928 MHz) Max. Transmission power: 20mW Bandwidth: 400 kHz Modulation: GFSK Baud rate: Max. 100 kbps

MODEL: WL40W1F-DAC4A WL40W1F SPECIFICATIONS ES-9083 Rev.1 Page 2/7 http://www.m-system.co.jp/ Channels: 1 to 43ch Security: 128bit AES Indicator LEDs: 920Run, 920Link, 920ERR Protocol: Modbus-RTU Communication module: Coordinator module incorporated (Oki Electric Industry Co., Ltd. ) Radio parameters setting: Configurator software Antenna

  • Sleeve antenna (Model: MH920-ANT-F (S)) Indoor use Non-waterproof Non-directional Gain: 3.0dBi max.
  • Rooftop antenna (Model: MH920-ANT-F (R)) Outdoor/indoor use Cable length: 2.5 m Waterproof performance: IPx6 (except connector) Non-directional Gain: 2.0dBi max. INPUT SPECIFICATIONS ■CONTACT INPUT (NPN/PNP) Number of input: 2 points Rated input voltage: 24 V DC: ±10 %, ripple 5 %p-p max. (for power input 24 V DC) 12 V DC: ±10 %, ripple 5 %p-p max. (for power input 12 V DC) ON voltage/ON Current: ≥ 16 V DC (between input terminal and COM)/ ≥ 3.7 mA (for power input 24 V DC) ≥ 7.5 V DC (between input terminal and COM)/ ≥ 3.7 mA (for power input 12 V DC) OFF voltage/OFF current: ≤ 5 V DC (between input terminal and COM)/ ≥ 1 mA (for power input 24 V DC) ≤ 3 V DC (between input terminal and COM)/ ≥ 1 mA (for power input 12 V DC) Input current: ≤ 5.5 mA (at 24 V DC) (for power input 24 V DC) ≤ 5.5 mA (at 12 V DC) (for power input 12 V DC) Input resistance: approx. 4.4 kΩ (for power input 24 V DC) approx. 2.2 kΩ (for power input 12 V DC) Read rate: ≤ 5 msec. ON delay time: ≤ 2.0 msec. OFF delay time: ≤ 2.0 msec. Contact input status indicator LED: lights up when the contact is ON (Dl1, Dl2). OUTPUT SPECIFICATIONS Output setting: Configurator software ■TRANSISTOR OUTPUT Number of output: 2 points Common: Negative common (NPN) Rated load voltage: 24 V DC: ±10 %, ripple 5 %p-p max. (for power input 24 V DC) 12 V DC: ±10 %, ripple 5 %p-p max. (for power input 12 V DC) Rated output current: 0.1 A Residual voltage: ≤ 1.2 V Leakage current: ≤ 0.1 mA ON delay time: ≤ 2.0 msec. OFF delay time: ≤ 2.0 msec. Overload current protection function: Limits the current value when overcurrent is detected. Overheat protection function: Turns OFF the outputs when overheat is detected. (When driving an inductive load, connect a diode in parallel with the load.) Transistor output status indicator LED: lights up when the contact is ON (DO1, DO2). INSTALLATION Current consumption:

24 V DC: ≤ 70 mA (contact I/O load charge is not included)

12 V DC: ≤ 130mA (contact I/O load charge is not included)

Operating temperature: -10 to +55°C (14 to 131°F) Storage temperature: -10 to +55°C (14 to +131°F) Operating humidity: 10 to 90 %RH (non-condensing) Atmosphere: No corrosive gas or heavy dust Mounting: DIN rail Weight Unit: Approx. 260 g (0.57 lb) Sleeve antenna (standard): 27 g (0.95 oz) Rooftop antenna: 52 g (1.83 oz) PERFORMANCE Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 1500 V AC @ 1 minute (power input to FE1 to contact input to transistor output to antenna connector) STANDARDS & APPROVALS Module conforming to FCC Part 15 incorporated

MODEL: WL40W1F-DAC4A WL40W1F SPECIFICATIONS ES-9083 Rev.1 Page 3/7 http://www.m-system.co.jp/ CONFIGURATOR SOFTWARE SETTING With configurator software, settings shown below are available. Refer to the users manual of W920FCFG for detailed operation. ■ WIRELESS SETTING ITEM SETTING RANGE DEFAULT Preferred PAN ID (group number) 0000 – FFFE (hexadecimal, 4 digits) 0000 Radio channel number 1 – 43 (selectable up to 10 channels) None Short address 0000 – FFFD (hexadecimal, 4 digits) 0000 Network name English one-byte characters within 16 characters (one-byte space, “-” , “_” , “ .” , “@” are usable.) Blank (hexadecimal, 32 digits) 0000...0 Transmitter power output 0.16mW / 1mW / 20mW 20mW Low-speed moving mode No / Y es No Device type in a network, Number of devices in a network Child (/f_i xed), 1 to 30 devices / Child (/f_i xed), 31 to 60 devices / Child (/f_i xed), 61 to 100 devices / Child (/f_i xed) + child (moving) Child (/f_i xed), 1 to 30 devices Set network quality Standard (recommended) / Frequency of route switching and delay (higher) / Frequency of route switching and delay (highest) Standard (recommended) Network join mode V3-compatible mode / Fast join mode V3-compatible mode Fixed route No / Y es No Destination short address 0000 – FFFD (hexadecimal, 4 digits) 0000 Temporary detour No / Y es Y es Packet /f_i ltering None / Y es (polling type) Y es (polling type) Modbus node address 1 – 247 1 Retry times before route switching Once / Twice / Three times Three times * For version confi rmation of communication module, refer to the users manual of W920FCFG. ■ TRANSISTOR OUTPUT SETTING ITEM SETTING RANGE DEFAULT Output status at time of 920Run communication disconnect Hold / Clear Hold EXTERNAL VIEW Power DI1 DO1 DI2 DO2 DI1A DI1B DI2A DI2B NC 920Link 920Run 920ERR CFG2 CFG1 24V DO1 DO2 NC NC NC FE1 ■ FRONT VIEW ˎ Status Indicator LED Antenna Connector Maintenance Connector Configuration Jack Connector for Power Input Contact input/Transistor output Indicator LED Contact Input Connector Transistor Output Connector ˎ Power input defers depending on the power input code you select.

MODEL: WL40W1F-DAC4A WL40W1F SPECIFICATIONS ES-9083 Rev.1 Page 4/7 http://www.m-system.co.jp/ TERMINAL ASSIGNMENTS ■ CONNECTORS FOR POWER INPUT Unit side connector: MSTBV2,5/5-GF-5,08AU (Phoenix Contact) Cable side connector: TFKC2,5/5-STF-5,08AU (Phoenix Contact)

  • Power input code: R (24 V DC) • Power input code: S (12 V DC) 24V NC NC FE1 ID FUNCTION 12V NC NC FE1 ID FUNCTION 24V Power input 24 V 12V Power input 12 V 0V Power input 0 V 0V Power input 0 V NC Not used NC Not used NC Not used NC Not used FE1 Power input earth FE1 Power input earth ■ CONTACT INPUT CONNECTOR Unit side connector: MC1,5/5-GF-3,5 (Phoenix Contact) Cable side connector: FMC1,5/5-STF-3,5 (Phoenix Contact) DI1A DI1B DI2A DI2B NC ID FUNCTION DI1A Contact input 1A DI1B Contact input 1B DI2A Contact input 2A DI2B Contact input 2B NC Not used ■ TRANSISTOR OUTPUT CONNECTOR Unit side connector: MC1,5/5-GF-3,5 (Phoenix Contact) Cable side connecto: FMC1,5/5-STF-3,5 (Phoenix Contact) DO1 DO2 NC ID FUNCTION V+ External excitation + V– External excitation – DO1 NPN transistor output 1 DO2 NPN transistor output 2 NC Not used

MODEL: WL40W1F-DAC4A WL40W1F SPECIFICATIONS ES-9083 Rev.1 Page 5/7 http://www.m-system.co.jp/ MODBUS FUNCTION CODES & SUPPORTED CODES Modbus function codes are shown below. ■ DATA AND CONTROL FUNCTION CODE NAME

01 Read Coil Status Digital output from the slave (read / write)

02 Read Input Status Status of digital inputs to the slave read only

03 Read Holding Registers General purpose register within the slave read / write

04 Read Input Registers Collected data from the /f_i eld by the slave read only

05 Force Single Coil Digital output from the slave read / write

06 Preset Single Registers General purpose register within the slave read / write

15 Force Multiple Coils Digital output from the slave read / write

16 Preset Multiple Registers General purpose register within the slave read / write

■ EXCEPTION CODE CODE NAME

01 Illegal Function Function code is not allowable for the slave

02 Illegal Data Address Address is not available within the slave

03 Illegal Data Value Data is not valid for the function

04 Slave Device Failure

05 Acknowledge

06 Slave Device Busy

07 Negative Acknowledge

Coil (0X) 1, 2 Digital Output 1, 2 3 – 16 Reserved (unused) Input (1X) 1, 2 Digital Input 1, 2 3 – 16 Reserved (unused) Input Register (3X) 1 – 16 – Reserved (unused) Holding Register (4X) 1 – 16 – Reserved (unused) Note: DO NOT access addresses other than mentioned above. Such access may cause problems such as inadequate operation. I/O DATA DESCRIPTIONS ■CONTACT INPUT DATA/TRANSISTOR OUTPUT DATA (1 BIT) Contact input data and transistor output data are indicated each by 1 bit. 0: OFF 1: ON

MODEL: WL40W1F-DAC4A WL40W1F SPECIFICATIONS ES-9083 Rev.1 Page 6/7 http://www.m-system.co.jp/ EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch) 105 (4.13) [260 (10.24)] [200 (7.87)] DIN RAIL 35mm wide approx. 2500 (98.4)27 dia. 3 (0.12) dia. 1.2 (.05) dia. 36 (1.42) 80 (3.15) 5 (.20) [155 (6.10)] DIN RAIL 35mm wide (1 .06) (.79) [R165(6.50)] 8 (.31) Hex.

  • WITH SLEEVE ANTENNA
  • WITH ROOFTOP ANTENNA

MODEL: WL40W1F-DAC4A WL40W1F SPECIFICATIONS ES-9083 Rev.1 Page 7/7 http://www.m-system.co.jp/ SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM NPN connection PNP connection

  • Output Connection Example • Input Connection Example ˎ Power input defers depending on the power input code you select. EXCITATION – EXCITATION + OUTPUT 2 OUTPUT 1 Power Input LED Control Circuit DI2A DI2B NC DI1A DI1B NC NC FE1 DO1 DO2 NC DI1A DO1 DO2 − + DI1A DI1B DI1B DI2A DI2B DI1A DI1B DI2A DI2B Control Circuit DI2A DI2B INPUT 1 INPUT 2 Control Circuit DO1 DO2 + − + − + − + − 24VˎAntenna Connector USB Connector Jack Maintenance Connector Configuration Jack Two-way wireless circuit ■ INPUT CIRCUIT ■ OUTPUT CIRCUIT Output CircuitInput Circuit Specifications are subject to change without notice.