MODEL: WL40MW1TH WL40MW1TH SPECIFICATIONS ES-9116 Rev.0 Page 1/6 http://www.m-system.co.jp/ Wireless I/O WL40TH Series WIRELESS GATEWAY (Modbus-RTU Transparent 920MHz Band Wireless Device (child device) for Thailand) 60 (2.36) 155 (6.10) [260 (10.24)] mm (inch) MODEL: WL40MW1TH-[1][2]
ORDERING INFORMATION
- Code number: WL40MW1TH-[1][2] Specify a code from below for each of [1] and [2]. (e.g. WL40MW1TH-R/E/Q)
- Specify the specification for option code /Q (e.g. /C01) [1] POWER INPUT DC Power S: 12 V DC (Operational voltage range 12 V ±10 %, ripple 10 %p-p max.) R: 24 V DC (Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) [2] OPTIONS (multiple selections) Antenna /S: Sleeve antenna /E: Rooftop antenna Other Options blank: none /Q: Option other than the above (specify the specification) SPECIFICATIONS OF OPTION: Q COATING (For the detail, refer to M-System's web site.) /C01: Silicone coating /C02: Polyurethane coating /C03: Rubber coating FUNCTIONS & FEATURES This unit
- Incorporates 920MHz band wireless module.
- Works as a gateway between wireless and RS-485 using Modbus-RTU protocol.
- For use in Thailand only.
RELATED PRODUCTS
For related products of wireless device, refer to M-System's web site.
- PC configurator software (model: W920FCFG) Downloadable at M-System’s web site. A dedicated cable is required to connect the unit to the PC. Please refer to the internet software download site or the users manual for the PC configurator software for applicable cable types. Maintenance software Maintenance console: MH920 Console International (model: MH920CI) (OKI) (Maintenance software is downloadable at M-System’s web site.) Coaxial cable
- 7.5 m extension cable for rooftop antenna (model: CX- SAC0SAD0Q0750) (OKI) Using 7.5 m coaxial cable for extension decreases transmission distance. PACKAGE INCLUDES...
- Terminating resistor (110 Ω, 0.25 W) GENERAL SPECIFICATIONS Connection Wireless network: SMA coaxial connector RS-485: Tension clamp (Front Twinconnection) Applicable wire size: 0.2 - 1.5 mm2, stripped length 10 mm Power supply: Tension clamp (Front Twinconnection) Applicable wire size: 0.2 - 2.5 mm2, stripped length 10 mm Maintenance: Mini USB type B female connector Isolation: Power input to Modbus to FE1 to antenna connector Indicator LED: Power MODBUS COMMUNICATION Protocol: Modbus-RTU Configuration: Bus type multi-drop Standard: Conforms to TIA/EIA-485-A Communication: Half-duplex, asynchronous, no procedure Transmission distance: 500 meters max. Transmission media: Shielded twisted-pair cable (CPEV-S 0.9 dia.)
MODEL: WL40MW1TH WL40MW1TH SPECIFICATIONS ES-9116 Rev.0 Page 2/6 http://www.m-system.co.jp/ Status indicator LED: ERR, RD, SD Max. no. of connections at once: 31 Transmission setting: PC configurator software Data: RTU (Binary) Baud rate: 4800, 9600, 19.2k, 38.4 k (bps) Parity: None, even or odd Stop bit: 1 or 2 WIRELESS SPECIFICATIONS Communication Standard: IEEE 802.15.4g Frequency: 920MHz band (920.2 - 924.8 MHz) Max. Transmission power: 20mW Bandwidth: 400 kHz Modulation: GFSK Baud rate: Max. 100 kbps Channels: 1 to 8ch Security: 128bit AES Indicator LEDs: 920Run, 920Link, 920ERR Protocol: Modbus-RTU Communication module: Router module incorporated (Oki Electric Industry Co., Ltd. ) Radio parameters setting: by PC configurator software Antenna
- Sleeve antenna (Model: MH920-ANT-F (S)) Indoor use Non-waterproof Non-directional Gain: 3.0dBi max.
- Rooftop antenna (Model: MH920-ANT-F (R)) Outdoor/indoor use Cable length: 2.5 m Waterproof performance: IPx6 (except connector) Non-directional Gain: 2.0dBi max. INSTALLATION Current consumption:
24 V DC: ≤ 70 mA
12 V DC: ≤130 mA
Operating temperature: -20 to +60°C (-4 to +140°F) Operating humidity: 10 to 90 %RH (non-condensing) Atmosphere: No corrosive gas or heavy dust Mounting: DIN rail Weight Unit: Approx. 260 g (0.57 lb) Sleeve antenna (standard): 27 g (0.95 oz) Rooftop antenna: 52 g (1.83 oz) PERFORMANCE Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 1500 V AC @ 1 minute (power input to Modbus to FE1 to antenna connector) STANDARDS & APPROVALS NBTC, Thailand Radio Waves Act
MODEL: WL40MW1TH WL40MW1TH SPECIFICATIONS ES-9116 Rev.0 Page 3/6 http://www.m-system.co.jp/ CONFIGURATOR SOFTWARE SETTING With configurator software, settings shown below are available. Refer to the users manual of W920FCFG for detailed operation. ■ WIRELESS SETTING ITEM SETTING RANGE DEFAULT Preferred PAN ID (group number) 0000 – FFFE (hexadecimal, 4 digits) 0000 Radio channel number 1 – 8 (selectable up to 8 channels) None Short address 0000 – FFFD (hexadecimal, 4 digits) 0000 Network name English one-byte characters within 16 characters (one-byte space, “-” Blank (hexadecimal, 32 digits) 0000...0 Monitoring unit time of 1% duty (sec.) 10 – 3600 (sec.) 600 (sec.) Transmitter power output 0.16mW / 1mW / 20mW 20mW Low-speed moving mode No / Y es No Device type in a network, Number of devices in a network Child (/f_i xed), 1 to 30 devices / Child (/f_i xed), 31 to 60 devices / Child (/f_i xed), 61 to 100 devices / Child (/f_i xed) + child (moving) Child (/f_i xed), 1 to 30 devices Set network quality Standard (recommended) / Frequency of route switching and delay (higher) / Frequency of route switching and delay (highest) Standard (recommended) Network join mode V3-compatible mode / Fast join mode V3-compatible mode Fixed route No / Y es No Destination short address 0000 – FFFD (hexadecimal, 4 digits) 0000 Temporary detour No / Y es Y es Packet /f_i ltering None / Y es (polling type) Y es (polling type) Retry times before route switching Once / Twice / Three times Three times Note: For version con/f_i rmation of communication module, refer to the users manual of W920FCFG. ■ MODBUS SETTING ITEM SETTING RANGE DEFAULT Transfer rate 38400 / 19200 / 9600 / 4800 bps 38400 bps Parity bit Odd / Even / None Odd Stop bit 1 bit / 2 bits 1 bit EXTERNAL VIEW ■ FRONT VIEW Power RD SD DA DB DG SLD FE 920Link 920Run 920ERR ERR CFG2 CFG1 24V NC NC FE1 Status Indicator LED Connector for RS-485 Communication *Power input defers depending on the power input code you select. Status Indicator LED Antenna Connector Maintenance Connector Configuration Jack Connector for Power Input *
MODEL: WL40MW1TH WL40MW1TH SPECIFICATIONS ES-9116 Rev.0 Page 4/6 http://www.m-system.co.jp/ COMMUNICATION CABLE CONNECTIONS ■ WIRING CONNECTION WITH SLAVE DEVICES DA DB DG SLD FE WL40MW1TH DA DB DG SLD FE REMOTE UNIT DA DB DG SLD FE REMOTE UNIT TERMINATOR TERMINATOR Note: Be sure to connect the terminating resistor included in the product package to the unit at both ends of communication line. The terminator must be connected across “DA” and “DB”. * Connect SLD and FE for reducing noise interference if necessary. TERMINAL ASSIGNMENTS ■ CONNECTORS FOR POWER INPUT Unit side connector: MSTBV2,5/5-GF-5,08AU (Phoenix Contact) Cable side connector: TFKC2,5/5-STF-5,08AU (Phoenix Contact)
- Power input code: R (24 V DC) • Power input code: S (12 V DC) 24V NC NC FE1 ID FUNCTION 12V NC NC FE1 ID FUNCTION 24V Power input 24 V 12V Power input 12 V 0V Power input 0 V 0V Power input 0 V NC Not used NC Not used NC Not used NC Not used FE1 Power input earth FE1 Power input earth ■ CONNECTOR FOR RS-485 COMMUNICATION Unit side connector: MC1,5/5-GF-3,5 (Phoenix Contact) Cable side connector: TFMC1,5/5-STF-3,5 (Phoenix Contact) DA DB DG SLD FE ID FUNCTION DA DA DB DB DG DG SLD Shield FE Functional earth MODBUS FUNCTION CODES & SUPPORTED CODES Modbus function codes are shown below. ■ DATA AND CONTROL FUNCTION CODE NAME
01 Read Coil Status Digital output from the slave (read/write)
02 Read Input Status Status of digital inputs to the slave (read only)
03 Read Holding Registers General purpose register within the slave (read/write)
04 Read Input Registers Collected data from the /f_i eld by the slave (read only)
05 Force Single Coil Digital output from the slave (read/write)
06 Preset Single Register General purpose register within the slave (read/write)
08 Diagnostics
15 Force Multiple Coils Digital output from the slave (read/write)
16 Preset Multiple Registers General purpose register within the slave (read/write)
MODEL: WL40MW1TH WL40MW1TH SPECIFICATIONS ES-9116 Rev.0 Page 5/6 http://www.m-system.co.jp/ ■ EXCEPTION CODE CODE NAME
01 Illegal Function Function code is not allowable for the slave
02 Illegal Data Address Address is not available within the slave
03 Illegal Data Value Data is not valid for the function
04 Slave Device Failure
05 Acknowledge
06 Slave Device Busy
07 Negative Acknowledge
EXTERNAL DIMENSIONS unit: mm (inch) 105 (4.13) [260 (10.24)] 107 (4.21) 3 (.12) 3 (.12) 45 (1.77) [200 (7.87)] (.79) approx. 2500 (98.4)ø27 (1.06) ø3 (.12) ø1.2 (.05) 36 (1.42) 80 (3.15) 5 (.20) [155 (6.10)] [R165 (6.50)]
- With sleeve antenna
- With rooftop antenna DIN RAIL 35mm wide DIN RAIL 35mm wide 8 (.31) Hex.
MODEL: WL40MW1TH WL40MW1TH SPECIFICATIONS ES-9116 Rev.0 Page 6/6 http://www.m-system.co.jp/ SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM Two-way wireless circuit Control Circuit LED Power Input NC NC FE1 Maintenance Connector Configuration Jack To Other Modbus Devices DA DB DG SLD FE Jack USB Connector Antenna Connector * Power input defers depending on the power input code you select. 24V* Isolation SYSTEM CONFIGURATION EXAMPLES LAN cable (STP cable) PC Modbus/Master Wireless gateway (model: WL40EW2TH) Wireless gateway (model: WL40MW1TH) Slave Device Slave Device Slave Device MAX. 31 RS-485 PC side as Modbus/Master communicates with child devices via wireless module using Modbus/TCP and RTU protocol, and also communicates with slave devices in multi drop connection (RS-485). Specifications are subject to change without notice.