Technical content
Features
Ordering information
- Dual PID auto tuning function: High-speed response of PID control to reach to the desired value fast, low-speed of response of PID control to minimize the overshoot even though response is a little bit slow.
- High display accuracy: ±0.3%(by F.S. value of each input)
- 2-Steps auto tuning control function
- Multi-input function (13 kinds of multi-input selection function): Temperature sensor, voltage and current selection function.
- Various sub output function: Includes in LBA, SBA, 7kinds of alarm output and 4 kinds of alarm option function, PV transmission output(DC4-20mA), RS485 communication output
- Display the decimal point for analog input TZ4SP/TZN4S TZN4 TZ4 TZ4/TZN4 Item Digit Size Auxiliary output Power supply Control output TZ4ST Etc.
4 M 1 4 RTZ
S SSR drive voltage output C Current output(DC4-20mA) 2 24VAC/24-48VDC 4 100-240VAC 50/60Hz
1 Event 1 output
2 Event 1 + Event 2 output
R Event 1 + PV transmission output(DC4-20mA) R Event 1 + PV transmission output(DC4-20mA) A Event 1 + Event 2 + PV transmission output(DC4-20mA) T Event 1 + RS485 communication output B Event 1 + Event 2+RS485 communication output S DIN W48×H48mm(terminal type) SP DIN W48×H48mm(plug type) ST DIN W48×H48mm(terminal type) M DIN W72×H72mm W DIN W96×H48mm H DIN W48×H96mm L DIN W96×H96mm 4 9999(4 digit) TZ Temperature dontroller(PID) TZN Temperature dontroller (PID New type)
(A) Photo electric sensor (B) Fiber optic sensor (C) Door/Area sensor (D) Proximity sensor (E) Pressure sensor (F) Rotary encoder (G) Connector/ Socket (H) Temp. controller (I) SSR/ Power controller (J) Counter (K) Timer (L) Panel meter (M) Tacho/ Speed/ Pulse meter (N) Display unit (O) Sensor controller (P) Switching mode power supply (Q) Stepper motor& Driver&Controller (R) Graphic/ Logic panel (S) Field network device (T) Software (U) Other Dual PID Auto Tuning Control ※1. AC/DC power type is only for TZ4SP, TZ4ST, TZN4M, TZ4L Series. ※Environment resistance is rated at no freezing or condensation. Specifications Series TZ4SP TZN4S TZ4ST TZ4M TZN4M TZ4W TZN4W TZ4H TZN4H TZ4L TZN4L Power supply AC Power 100-240VAC 50/60Hz AC/DC Power 24VAC 50/60Hz / 24-48VDC Allowable voltage range 90 to 110% of rated voltage Power con- sumption AC Power Max. 5VA(100-240VAC 50/60Hz) Max. 6VA(100-240VAC 50/60Hz) AC/DC Power Max. 8VA(24VAC 50/60Hz), Max. 7W(24-48VDC) Display accuracy 7 Segment (PV: red, SV: green) LED method Character size(W×H) TZ4SP: 4.8×7.8mm TZN4S: PV:7.8×11.0mm SV:5.8×8.0mm 4.8×7.8mm TZ4M: PV:9.8×14.2mm SV:8.0×10.0mm TZN4M: PV:8.0×13.0mm SV:5.0×9.0mm 8.0×10.0mm TZ4H: 3.8×7.6mm TZN4H: PV:7.8×11.0mm SV:5.8×8.0mm PV:9.8×14.2mm SV:8.0×10.0mm Input type RTD DPt100Ω, JPt100Ω, 3wire (allowable line resistance max. 5Ω per a wire) Thermocouple K(CA), J(IC), R(PR), E(CR), T(CC), S(PR), N(NN), W(TT) (allowable line resistance max. 100Ω) Analog 1-5VDC, 0-10VDC, DC4-20mA Control output Relay 250VAC 3A 1c SSR 12VDC ±3V 30mA Max. Current DC4-20mA (load 600Ω Max.) Sub output PV transmission - DC4-20mA (load 600Ω Max.) EVENT1 250VAC 1A 1a EVENT2 - 250VAC 1A 1a Communication - - RS485(PV/SV transmission, SV setting) Control type ON/OFF, P, PI, PD, PIDF, PIDS control Display accuracy F.S. ±0.3% or 3℃, select the higher one Setting method Front push buttons Hysteresis 1~100℃(0.1 to 100.0℃) variable(ON/OFF control) ALARM output Adjustable ON/OFF 1 to 100 (0.1 to 100.0)℃ of alarm output Proportional band (P) 0.0 to 100.0% Integral time (I) 0 to 3600 sec. Derivative time (D) 0 to 3600 sec. Control period (T) 1 to 120 sec. Sampling period 0.5 sec. LBA setting 1 to 999 sec. RAMP setting Ramp Up, Ramp Down at 1 to 99min. Dielectric strength 2,000VAC 50/60Hz for 1min. (between power source terminal and input terminal) Vibration 0.75mm amplitude at frequency of 10 to 55Hz(for 1min.) in each of X, Y, Z direction for 2 hours Relay life cycle Main output Mechanical: Min. 10,000,000 operations, Electrical: Min. 100,000 operations(250VAC 3A resistive load) Sub output Mechanical: Min. 20,000,000 operations, Electrical: Min. 500,000 operations(250VAC 1A resistive load) Insulation resistance Min. 100MΩ (at 500VDC megger) Noise resistance ±2kV the square wave noise (pulse width: 1us) by the noise simulator Memory retention Approx. 10 years (when using non-volatile semiconductor memory type) Environ- ment Ambient temperature-10 to 50℃, storage: -20 to 60℃ Ambient humidity 35 to 85%RH, storage: 35 to 85%RH Approval Unit weight TZ4SP: Approx. 136g TZN4S: Approx. 150g Approx. 136g Approx. 270g TZ4W: Approx. 270g TZN4W: Approx. 259g Approx. 259g Approx. 360g
※RTD: DPt100Ω(3-wire type), JPt100Ω(3-wire type) ※T.C(Thermocouple): K, J, R, E, T, S, W, N ※In case of Analog input, please use T.C(Thermocouple) terminal and be careful about polarity. TZN4S TZN4M TZ4SP TZ4ST TZ4M Connections EV-1 OUT 250VAC 1A 1a SV2 IN Max.5VDC 250㎂ MAIN OUT 250VAC 3A 1c Resistive load SOURCE 100-240VAC 50/60Hz 6VA 24VAC 50/60Hz 8VA 24-48VDC 7W H C L RTD T.C SENSOR B A 2 10 1 11
76 MAIN OUT
12VDC ±3V 30mA Max. DC4-20mA Load 600Ω Max. 9 9 10 10 mAV MAIN OUT SSR Current 12VDC ±3V 30mA Max. DC4-20mA Load 600Ω Max. mAV SV2 IN Max.5VDC 250㎂ MAIN OUT 250VAC 3A 1c Resistive load RTD T.C SENSOR B A H C L RS485 (A+) (B-) PV OUT DC4-20mA (Transmission output) SOURCE: 100-240VAC 50/60Hz 6VA EV1 OUT 250VAC 1A EV2 OUT 250VAC 1A 14 15 16 EV-1 OUT 250VAC 1A SV2 IN Max.5VDC 250㎂ MAIN OUT 250VAC 3A 1c Resistive load PV OUT DC4-20mA (Transmission output) EV-2 OUT: 250VAC 1A SOURCE 100-240VAC 50/60Hz 6VA 24VAC 50/60Hz 8VA 24-48VDC 7W H C L RTD T.C SENSOR B A MAIN OUT SUB OUT SSR Current PV transmission output 12VDC ±3V 30mA Max. DC4-20mA Load 600Ω Max. DC4-20mA Load 600Ω Max. mA mAV MAIN OUT SSR Current 12VDC ±3V 30mA Max. DC4-20mA Load 600Ω Max. mAV3
2 MAIN OUT
12VDC ±3V 30mA Max. DC4-20mA Load 600Ω Max. mAV EV1 OUT 250VAC 1A EV2 OUT 250VAC 1A SV2 IN Max.5VDC 250㎂ MAIN OUT 250VAC 3A 1c Resistive load PV OUT DC4-20mA (Transmission output) SOURCE 100-240VAC 50/60Hz 6VA 24VAC 50/60Hz 8VA 24-48VDC 7W N.O. N.O. H RS485 (A+) (B-) C L RTD T.C SENSOR B A SOURCE: 100-240VAC 50/60Hz 5VA EV1 OUT 250VAC SV2 IN Max.5VDC 250㎂ MAIN OUT 250VAC 3A 1c Resistive load RTD T.C SENSOR B A H C L
(A) Photo electric sensor (B) Fiber optic sensor (C) Door/Area sensor (D) Proximity sensor (E) Pressure sensor (F) Rotary encoder (G) Connector/ Socket (H) Temp. controller (I) SSR/ Power controller (J) Counter (K) Timer (L) Panel meter (M) Tacho/ Speed/ Pulse meter (N) Display unit (O) Sensor controller (P) Switching mode power supply (Q) Stepper motor& Driver&Controller (R) Graphic/ Logic panel (S) Field network device (T) Software (U) Other Dual PID Auto Tuning Control Dimensions
- Panel cut-out TZN4S TZN4M TZ4L / TZN4L TZ4H / TZN4H TZ4W/TZN4W (unit: mm) 10 90 44.8 Min. 55 Min. 62 +0.6 +0.6 72 10 73 Min. 91 Min. 91 +0.7 +0.7
- Panel cut-out <Bracket> MAIN OUT SSR Current 12VDC ±3V 30mA Max. DC4-20mA Load 600Ω Max. mAV 15 SOURCE: 100-240VAC 50/60Hz 5VA EV1 OUT 250VAC EV2 OUT 250VAC SV2 IN Max.5VDC 250㎂ MAIN OUT 250VAC 3A 1c Resistive load PV OUT DC4-20mA (Transmission output) RTD T.C SENSOR B A H C L RS485 (A+) RS485 (B-) N.O. N.O. 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 MAIN OUT SSR Current 12VDC ±3V 30mA Max. DC4-20mA Load 600Ω Max. mAV15 SOURCE: 100-240VAC 50/60Hz 6VA EV1 OUT 250VAC 1A EV2 OUT 250VAC 1A SV2 IN Max.5VDC 250㎂ MAIN OUT 250VAC 3A 1c Resistive load PV OUT DC4-20mA (Transmission output) T.C RTD SENSOR B A H C L RS485 (A+) (B-) N.O. N.O. EV1 OUT 250VAC 1A EV2 OUT 250VAC 1A SV2 IN Max.5VDC 250㎂ MAIN OUT 250VAC 3A 1c Resistive load PV OUT DC4-20mA (Transmission output) T.C RTD SENSOR B A H C L RS485 (A+) (B-) N.O. N.O. ※Only for TZ4L. SOURCE 100-240VAC 50/60Hz 6VA 24VAC 50/60Hz 8VA 24-48VDC 7W MAIN OUT SSR Current 12VDC ±3V 30mA Max. DC4-20mA Load 600Ω Max. mAV15
※Since TZ4SP uses same identification plate with TZ4ST, the lamp does not work even though it has a EV2 output signal lamp. 1512 80 44.8 Min. 55 Min. 62 45 +0.6 +0.6 Min. 74 Min. 90 +0.7 +0.7 12 95 44.8 10013
- Panel cut-out
- Panel cut-out TZ4H TZN4H 108 108 9013 Min. 50 Min. 112 +0.6 +0.8
- Panel cut-out TZ4W TZN4W 108 108 10013 44.8 Min. 112 Min. 50 92 +0.8 +0.6
- Panel cut-out (unit: mm) <Bracket>
(A) Photo electric sensor (B) Fiber optic sensor (C) Door/Area sensor (D) Proximity sensor (E) Pressure sensor (F) Rotary encoder (G) Connector/ Socket (H) Temp. controller (I) SSR/ Power controller (J) Counter (K) Timer (L) Panel meter (M) Tacho/ Speed/ Pulse meter (N) Display unit (O) Sensor controller (P) Switching mode power supply (Q) Stepper motor& Driver&Controller (R) Graphic/ Logic panel (S) Field network device (T) Software (U) Other Dual PID Auto Tuning Control 1: Display Processing value(PV) (Red) 5: Mode key 9: Indicate EVENT 1 output 2: Display Setting value(SV) (Green) 6: Autotuning operation key 10: Indicate EVENT 2 output 3: Indicate SV2 operation 7: Setting keys 11: Procedure of setting key 4: Indicate Auto-tuning operation 8: Indicate control output operation ※Since TZ4SP uses same identification plate with TZ4ST, the lamp does not work even though it has a EV2 output signal lamp. ※There are no ( , ) Key in TZ4SP/TZ4ST/TZ4H/TZ4W and TZN4S/TZN4H/TZN4W. ※Control output indicator(OUT) does not work when it is used as current output type. ※Above explanations are the example of TZ4M. In case of TZ Series. Use the Key in brackets for setting(changing). There are no ,( )Key in TZN4S, TZ4SP and TZ4ST. It is not used for setting or changing the setting value. 96 96 10013 108 108 Parts description SV setting TZ4L TZN4L 1 1 2 2 4 4 5 5 TZN4S TZ4ST/TZ4SP TZN4M TZ4M Min. 98 Min. 106 +0.8 +0.8
- Panel cut-out (unit: mm) Press ( ) key to move the desired digit. (10 →10 →10 →10 →10 Press key to save the value and it controls with this set value.
3 Press ( ), ( ) key to move
the desired number (1 → 5).
1 Press any key among ( )key in
RUN mode, the right digit at SV display flashes and it enters to SV setting. 6 7 6 7
Set alarm temperature in SV2. Set range: Within the rated using range of each sensor. Set alarm temperature in EV-1. Set range: Within the rated using range of each sensor. Set alarm temperature in EV-2. Set range: Within the rated using range of each sensor. If press MD key for 3sec., it will go to parameter 1 group. Set monitoring time of loop break alarm. Set range: 0 to 999 sec. Set interval between ON and OFF for alarm output. Set range: 1 to 100℃ (0.1 to 100.0℃) ※It is only displayed for temperature alarm output. Set proportional band. / Set range: 0.0 to 100.0%. ※If setting value P as 0.0, it will be ON/OFF control. Set integral time. / Set range: 0 to 3600 sec. ※If setting value I as 0 sec., this function will be OFF. ※It is not displayed when P is 0.0. (ON/OFF control) Set derivative time. / Set range: 0 to 3600 sec. ※If setting value D as 0 sec., this function will be OFF. ※It is not displayed when P is 0.0. (ON/OFF control) Set control period cycle. / Set range: 1 to 120 sec. ※In case of SSR output, this value should be small.(Ex: 2sec.) ※It is not displayed when P is 0.0. (ON/OFF control) Set hysteresis. / Set range: 1 to 100℃ (0.1 to 100.0℃) ※It is only displayed for ON/OFF control. Correct the error in input sensor. Set range: -49 to 50℃ (-50.0 to 50.0℃) Set manual reset value. / Set range: 0.0 to 100.0% ※It is only displayed for P control. Set ramp rising-time. / Set range: 1 to 99 min. ※It displayed only when selecting Ramp function in setting 2 group. Set ramp falling-time. / Set range: 1 to 99 min. ※It is displayed when selecting Ramp function at parameter 2 group. Cancel the lock function for OFF. This function is for locking the setting value.(available to operate AT Key) Select ON1, changing setting value in the parameter 1 group and AT key in the front panel cannot be changed. SV2 (Setting value 2) AL1 setting value AL2 setting value Loop break alarm Alarm hysteresis Proportional band Integral time Derivative time Control time Hysteresis Input correction Manual reset RAMP rising RAMP-up time RAMP falling RAMP-down time Lock Flow chart for parameter 1 group ※ Press ( ) key and the right digit of SV display part flashes. Press ( ) or ( ) key and move to the desired digit. Press ( ), ( ) keys to change SV and press MD key to complete the set. Press MD key again and it moves to next parameter. ※After completing setting at each parameter, press MD key for 3 sec. and it returns to RUN mode. ※If no key touched for 60sec., it will return to RUN mode automatically. ※ This parameter [ AL1, AL2, LBA, I, D, T, HYS, REST, RAPU, RAPD ] might not be displayed depending on other parameter settings. Factory defaults(Parameter 1 group) Parameter Factory default Parameter Factory default Parameter Factory default Parameter Factory default SU-2 0 AHYS 2 T 20 RAPU 10 AL1 10 P #0 HYS 2 RAPD 10 AL2 10 I 0 IN-B 0 LOC OFF LBA 600 D 0 REST )0 Run mode MD MD MD MD MD MD MD MD MD MD MD MD MD MD MD AL1 10 I 0 LBA 999 T 20 RAPU 10 AL2 10 D 0 REST )0 AHYS 2 HYS 2 RAPD 10 ON ON1 SU-2 0 P #0 IN-B 0 LOC OFF MD 3sec.
(A) Photo electric sensor (B) Fiber optic sensor (C) Door/Area sensor (D) Proximity sensor (E) Pressure sensor (F) Rotary encoder (G) Connector/ Socket (H) Temp. controller (I) SSR/ Power controller (J) Counter (K) Timer (L) Panel meter (M) Tacho/ Speed/ Pulse meter (N) Display unit (O) Sensor controller (P) Switching mode power supply (Q) Stepper motor& Driver&Controller (R) Graphic/ Logic panel (S) Field network device (T) Software (U) Other Dual PID Auto Tuning Control Parameter 2 group Parameter Factory default Parameter Factory default Parameter Factory default Parameter Factory default IN-T KCaH AL-T AL-A PIDT PIdS H-SC 1300 EU-1 AL-1 AtT TVN1 O-FT HEAT L-SC -100 EU-2 AL-2 RAMP OFF UNIT ?C LOC OFF ※ Press ( ) key and the right digit of SV display part flashes. Press ( ) or ( ) key and move to the desired digit. Press ( ), ( ) keys to change SV and press MD key to complete the set. Press MD key again and it moves to next parameter. ※After completing setting at each parameter, press MD key for 3 sec. and it returns to RUN mode. ※If no key touched for 60sec., it will return to RUN mode automatically. ※1: It may not be displayed by input type switch. ※2: This is displayed only for model with High/Low-limit of transmission output. Factory defaults(Parameter 2 group) IN-T Input type: Select from 19 type L-SC Set scaling low limit (include analog output) EU-1 Event 1: Select from 9 type DOT Select decimal point position for Analog input EU-2 Event 2: Select from 9 type FS-H Set the high-limit when retransmission output is applied. (20mA) AL-T Alarm type: Select from 4 type FS-L Set the low-limit when retransmission output is applied. (4mA) AtT Auto-tuning: Selectable TUN1 or TUN2. RAMP Able to set ON and OFF of Ramp function. PIDT PID: Selectable PIDF or PIDS. BPS Set communication speed O-FT Selectable heat-function or cool-function ADRS Set communication address(01 to 99) UNIT Temperature unit: ℃ or ℉ LOC The data cannot be changed when the lock key is ON H-SC Set scaling high limit (include analog output) If pressing MD + key for 3sec. at once in RUN state, it will go to parameter 2 group. Input type Event 1 mode Alarm type PID type Control operating type Temperature unit Input type Lock Event 2 mode Auto-tuning type Scaling high limit Transmission output low limit Communication address Communication speed Ramp function Transmission output high limit Scaling low limit Decimal point IN-T KCaH JIcH JIcL R PR ECrL ECrH TCcH TCcL S PR NN U TT JPtH KCaL JPtL DPtH DPtL A--1 A--2 A--3 EU-1 LBA SBA AL-0 AL-1 AL-2 AL-4 AL-3 AL-5 AL-6 EU-2 LBA SBA AL-0 AL-1 AL-2 AL-4 AL-3 AL-5 AL-6 AL-T AL-A AL-B AL-C AL-D IN-T AtT TVN1 TVN2 LOC OFF ON PIDT PIdS PIdF ADRS O-FT HEAT COOL BPS 2400 4800 9600 UNIT H-SC 1300 RAMP OFF ON L-SC -100 FS-L -100 FS-H 1300 DOT )00 )000 MD MD MD MD MD MD MD MD MD MD MD MD MD MD MD MD MD Run mode MD + 3sec.
A) In case of sensor input : K(CA), J(IC), R(PR), E(CR), T(CC), S(PR), N(NN), W(TT), DPt 100Ω, JPt 100Ω B) In case of voltage input : 1-5VDC, 0-10VDC C) In case of current input : DC4-20mA SW1 SW1 SW1 SW2 SW2 SW2 SW1:1 SW1:2 SW1:2 SW2: V SW2: V SW2: mA 1 1 2 2 2 2 V V V mA mA mA Input type and range Input type switch ※Factory default of input type switch: Temperature sensor input. ※Please select B) or C) according to input specification when it is voltage or current. Input type Display Input range(℃) Input range(℉) Thermocouple K(CA) H KCaH -100 to 1300℃ -148 to 2372℉ K(CA) L KCaL -100.0 to 999.9℃ This mode cannot be used as ℉ J(IC) H JIcH 0 to 800℃ 32 to 1472℉ J(IC) L JIcL 0.0 to 800.0℃ This mode cannot be used as ℉ R(PR) R PR 0 to 1700℃ 32 to 3092℉ E(CR) H ECrH 0 to 800℃ 32 to 1472℉ E(CR) L ECrL 0 .0~800.0℃ This mode cannot be used as ℉ T(CC) H TCcH -200 to 400℃ -328 to 752℉ T(CC) L TCcL -199.9 to 400.0℃ This mode cannot be used as ℉ S(PR) S PR 0 to 1700℃ 32 to 3092℉ N(NN) NN 0 to 1300℃ 32 to 2372℉ W(TT) U TT 0 to 2300℃ 32 to 4172℉ RTD JPt100Ω H JPtH 0 to 500℃ 32 to 932℉ JPt100Ω L JPtL -199.9 to 199.9℃ -199.9 to 391.8℉ DPt100Ω H DPtH 0 to 500℃ 32 to 932℉ DPt100Ω L DPtL -199.9 to 199.9℃ -199.9 to 391.8℉ Analog input 0-10VDC A--1 -1999 to 9999℃ -1999 to 9999℉ 1-5VDC A--2 -1999 to 9999℃ -1999 to 9999℉ DC4-20mmA A--3 -1999 to 9999℃ -1999 to 9999℉
(A) Photo electric sensor (B) Fiber optic sensor (C) Door/Area sensor (D) Proximity sensor (E) Pressure sensor (F) Rotary encoder (G) Connector/ Socket (H) Temp. controller (I) SSR/ Power controller (J) Counter (K) Timer (L) Panel meter (M) Tacho/ Speed/ Pulse meter (N) Display unit (O) Sensor controller (P) Switching mode power supply (Q) Stepper motor& Driver&Controller (R) Graphic/ Logic panel (S) Field network device (T) Software (U) Other Dual PID Auto Tuning Control This unit has output for control and sub(alarm) output. Sub output is optional. (This alarm output is relay contact(1a) and operates regardless of output for control.) Alarm output operates when the temperature of target is getting higher or lower than setting value. Select one among 6 alarm operations [ AL-1/2/3/4/5/6] of event 1, 2[ EU-1, EU-2] at parameter 2 group and set alarm temperature (deviation or absolute temperature) in AL1, AL2 alarm temperature[AL1, AL2] at parameter 1 group.
- Since EU-1 and EU-2 operate separately, both EU-1 and EU-2 can be used as a high or low 2nd alarm operation.
- When selecting LBA or SBA function in EU-1, EU-2 of parameter 2 group, alarm cannot be operated. Alarm Alarm operation Alarm option Mode Name Description AL-A Standard alarm If it is an alarm condition, alarm output is ON. If it is a clear alarm condition, alarm output is OFF. AL-B Alarm latch If it is an alarm condition, alarm output is ON and maintains ON status. AL-C Standby sequence First alarm condition is ignored and from second alarm condition, standard alarm operates. When power is supplied and it is an alarm condition, this first alarm condition is ignored and from the second alarm condition, standard alarm operates. AL-D Alarm latch and standby sequence If it is an alarm condition, it operates both alarm latch and standby sequence. When power is supplied and it is an alarm condition, this first alarm condition is ignored and from the second alarm condition, alarm latch operates. Mode Name Alarm operation Description AL-0 - - No alarm output AL-1 Deviation high-limit alarm SV 100℃ PV 110℃ OFF ONH PV 90℃ SV 100℃ OFF ONH If deviation between PV and SV as high- limit is higher than set value of deviation temperature, the alarm output will be ON. High deviation: Set as 10℃ High deviation: Set as -10℃ AL-2 Deviation low-limit alarm PV 90℃ SV 100℃ OFFON H SV 100℃ PV 110℃ OFFON H If deviation between PV and SV as low- limit is higher than set value of deviation temperature, the alarm output will be ON. Lower deviation: Set as 10℃ Lower deviation: Set as -10℃ AL-3 Deviation high/low-limit alarm PV 90℃ PV 120℃ SV 100℃ OFFON ONH H If deviation between PV and SV as high/low-limit is higher than set value of deviation temperature, the alarm output will be ON.Lower deviation: Set as 10℃, High deviation: Set as 20℃ AL-4 Deviation high/low-limit reserve alarm PV 90℃ PV 120℃ SV 100℃ OFF OFFONH H If deviation between PV and SV as high/low-limit is higher than set value of deviation temperature, the alarm output will be OFF. Lower deviation: Set as 10℃, High deviation: Set as 20℃ AL-5 Absolute value high limit alarm PV 90℃ SV 100℃ OFF ONH SV 100℃ PV 110℃ OFF ONH If PV is higher than the absolute value, the output will be ON. Absolute-value Alarm: Set as 90℃ Absolute-value Alarm: Set as 110℃ AL-6 Absolute value low limit alarm PV 90℃ SV 100℃ OFFON H SV 100℃ PV 110℃ OFFON H If PV is lower than the absolute value, the output will be ON. Absolute-value Alarm: Set as 90℃ Absolute-value Alarm: Set as 110℃ SBa Sensor break Alarm - It will be ON when it detects sensor disconnection. LBa Loop break Alarm - It will be ON when it detects loop break. ※ H: Alarm output hysteresis [ AHYS]
(tun 1 mode) Auto tuning time Time(t) SV (tun 2 mode) Auto tuning time 70% of SV Time(t) SV Functions Auto tuning [ AtT] Sensor Break Alarm [ SBA] Sub output [ EU-1, EU-2] Error Loop Break Alarm [ LBA] PID auto tuning function automatically measures the thermal characteristics and response of the control system and then executes its value under high response & stability after calculating the time constant of PID required to control optimum temperature.
- Execute the auto tuning function at initial time after connecting the controller & the sensor.
- Execution of auto tuning is started when pressing AT key for 3 sec. or more.
- When the auto tuning is started, AT lamp will flash, and when the lamp is OFF, this operation will stop.
- While the auto tuning function is executing, it is stopped by pressing AT key for 5sec. or more.
- When the power turns off or the stop signal is applied while auto tuning function is executing, time constant of PID is not changed and it remembers the value before power turns off.
- Time constant of PID selected by auto tuning function can be changed in parameter 1 group.
- It has two kinds of auto tuning mode auto tuning operation is executed at setting value(SV) in TUN1 mode which is factory default. Auto tuning operation in TUN2 mode is executed in 70% of setting value(SV). Mode change is available in AtT of the parameter 2 group.
- Execute the auto tuning function again periodically, because the thermal characteristics for the control object can be changed when the controller is used continuously for a long time. Sub output can execute as main control output and sub function as well. There is one sub output in this unit.
- This sub output is relay "1a" contact output.
- 1 mode can be selected among 7 kinds of alarm mode or LBA operated when the heater line is cut, SBA operated when the sensor line is cut.
- The Sub output can be latched ON or automatically reset depending on the alarm option mode selected.
- When the sensor line or the heater line is cut, SBA or LBA output turns on. This "Output on" status must be reset by turning the power off. This function causes the sub output to turn on when the sensor line is cut or open. It is easier to check that whether the sensor line is cut or not through buzzer or etc by exterior sub output (relay contact).
- For using SBA function, set SBA at EU-1 or EU-2 in parameter 2 group and SBA output operates as EV1 OUT or EV2 OUT contact. LBA function is to diagnose an abnormal temperature of the control system. If the temperature of the control system is not changed within ±2℃ during setting time of LBA, the LBA output will be ON. Ex) When setting value(SV) is 300℃, process value(PV) is 50℃, this unit controls 100%. In this time if there is no change of system temperature, it recognizes Heater is cut off then LBA output will be ON.
- LBA output can be selected at EV1 of the parameter 2 group.
- If LBA output is not selected at event output, it will not be displayed in parameter 1 group.
- Set range of LBA: 1 to 999 sec.
- If thermal response of the control system is slow, LBA value should be set to a high value.
- LBA output operates when the manipulated value of the controller is 0% and 100%.In case the LBA output is ON, please check the following; ① Short-circuit or cutting of the temp. sensor. ② Abnormal condition of the equipment (magnet, sub-relay, etc.) ③ Abnormal condition of the load(heater, cooler) ④ Wrong-wiring or cutting of the other cables.
- Once SBA is ON due to broken sensor, it will not reset, although sensor is connected. In this case, turn off the power then turn on again. If error is occurred while the controller is operating,it will be displayed as follow.
- LLLL is flashing when measured input temperature is lower than input range of the sensor.
- HHHH is flashing when measured input temperature is higher than input range of the sensor.
- OPEN is flashing when the input sensor is not connected or its wire is cut.
(A) Photo electric sensor (B) Fiber optic sensor (C) Door/Area sensor (D) Proximity sensor (E) Pressure sensor (F) Rotary encoder (G) Connector/ Socket (H) Temp. controller (I) SSR/ Power controller (J) Counter (K) Timer (L) Panel meter (M) Tacho/ Speed/ Pulse meter (N) Display unit (O) Sensor controller (P) Switching mode power supply (Q) Stepper motor& Driver&Controller (R) Graphic/ Logic panel (S) Field network device (T) Software (U) Other Dual PID Auto Tuning Control Setting value (SV) Decrease reset Increase reset Normal deviation Normal deviation Process value(PV) (Fig. 1) SV S PV t PIdF ※ t : Reaching time S : Overshoot SV: Setting value PV: Process value (Fig. 2) SV PV t PIdS ※ t : Reaching time SV: Setting value PV: Process value ON/OFF control Manual reset [ REST] Dual PID control RS485 communication Decimal point setting [ DOT] ON/OFF control is called two position control because the output turns on when PV falls lower than SV and the output turns off when PV is higher than SV. This control method is not only for controlling temperature, but also it is basic control method for sequence control.
- If you set value P as )0 in parameter 1 group, ON/OFF control will operate.
- There is a programmable temperature difference between ON and OFF in ON/OFF control, if difference is too small, then hunting(chattering) can occur.
- Temperature difference can be set in HYS mode of parameter 1 group. Setting range is 1 to 100(or 0.1 to 100.0).
- HYS mode is displayed when P value is )0, but HYS will not be displayed, and then jump if P value is not )0.
- This ON/OFF control should not be applied when equipment(cooling compressor) to be controlled can be damaged by frequent ON and OFF.
- Even if ON/OFF control is stable status, the hunting can be occurred by setting value in HYS or capacity of the heater or response characteristic of the equipment to be controlled or installing position of the sensor. Please consider above points to minimize the hunting when designing the system. Proportional control has deviation because rising time is not same as falling time, even if the unit operates normally. Manual reset function is used at proportional control mode only.
- If set RESTfunction in parameter 1 group, the manual reset will run.
- When PV and SV is equal, REST value is 50.0% and when control is stable, if the temperature is lower than SV, RESTvalue should be higher and on the other hand, REST value should be smaller.
- REST setting method according to result of control. When controlling temperature, two types of control characteristic are available as below. One is when you need to minimize the time which PV reaches to SV as like(Fig. 1). The other is when you need to minimize overshoot even though the reaching time(PV to SV) is slow(Fig. 2).
- There are high-speed response type and low-speed response type built in this unit. Therefore user can select each function according to their application.
- You can select dual PID control function in parameter 2 group. It is selectable PIdFor PIdS in PIDT mode. PIdF(high-speed response type) This mode is applied to machines or systems which require high-speed response. PIdS (low-speed response type) It is PID Slow, used to minimize overshoot even though the response is slow. For control temperature of oil, plating machine have a possibility of fire with overshoot, PIdS (limit over) should be used. ※ Factory default setting is PIdS. Please select mode according to control system. It is used on the purpose that transmitting PV to an external equipment, setting SV at the external equipment.
- It can be set at BPS, ADRS in second parameter 2 group.
- Communication speed[ BPS] set range: 2400, 4800, 9600bps
- Start bit(1bit, fixed), Stop bit(1bit, fixed), Parity bit(none)
- Communication address[ ADRS] set range: 1 to 99 Communication converters (sold separately) SCM-38I(RS-232C to RS485 converter) SCM-US48I(USB to RS485 converter) SCM-WF48(Wi-Fi to RS485/USB communication converter(available soon) Decimal point is displayed as DOT in parameter 2 group when the input is analog only.(0-10VDC, 1-5VDC, DC4-20mA)
when ramp function is used RAPU setting time RAPU setting time tutu Initial SV Changing SV Cool / Heat function [ O-FT] SV2 function [ SU-2] If using SV2 function, it changes the temperature of control system to the second setting value by external relay contact signal. It can change the setting value as sequentially by relay contact without key operation.
- It can set SV2 at required time and particular area as like the above chart.
- SV2 is in parameter 1 group.
- Application : The control system, which has to maintain constant temperature such as oven. If you open the door, temperature will go down. In this case, if you set the second setting value higher than setting value, temperature will rise fast. Therefore, after installing a micro-switch in order to detect the door Open/Close and connect it to SV2 (the second setting value should be higher than SV) then it controls temperature of oven efficiently. Ramp function [ RAMP] Ramp function is to delay the rising time or falling time of temperature. If you change setting value at stable state of control, it forces to rise or fall the temperature of control system during setting time at RAMP, RAPD in parameter 1 group. If RAMP is not ON in parameter 2 group, RAPU, RAPD will not be displayed in parameter 1 group.
- Set RAMP is ON in parameter 2 group for using ramp function.
- Set the rising time and falling time at RAPU mode and RAPD mode of parameter 1 group.
- Ramp function will be operating when changing the set value at stable control status or supply the power again after the power was removed.
- The setting range of rising and falling time is 1 to 99 minute. Ramp rising[ RAPU] (delay of rising time) It makes delay rising temperature when change the set value at stable control status or delay the initial rising temperature as like above picture. ※ RAPU time cannot be shorter than rising time(tu) of temperature when Ramp function is not used. Ramp falling[ RAPD] (delay of falling time) It controls falling temperature as like above. ※ RAPD time cannot be shorter than falling time(td) of temperature when Ramp function is not used. Generally there are two ways to control temperature, one (heat-function) is to heat when PV is getting down(heater). The other(cool-function) is to cool when PV is getting higher (freezer). These functions are operating oppositely when it is ON/ OFF control or proportional control. But in this case PID time constant will be different due to PID time constant will be decided according to control system when it is PID control.
- Cool-function and heat-function can be set at Parameter 2 group.
- Cool-function [ COOL] and heat-function [ HEAT] must be set correctly according to the application, if set as opposite function, it may cause a fire. (If set cool-function [ COOL] at heater, it will be maintained ON and it may cause a fire.)
- Avoid changing heat-function to cool-function or cool- function to heat-function when the unit is operating.
- It is impossible to operate both function at once in this unit. Therefore, only one function should be selected only.
- Factory default setting is heat-function [ HEAT]. Control temperature when ramp function is not used Control temperature when ramp function is used td Initial SV Changing SV RAPD setting time
(A) Photo electric sensor (B) Fiber optic sensor (C) Door/Area sensor (D) Proximity sensor (E) Pressure sensor (F) Rotary encoder (G) Connector/ Socket (H) Temp. controller (I) SSR/ Power controller (J) Counter (K) Timer (L) Panel meter (M) Tacho/ Speed/ Pulse meter (N) Display unit (O) Sensor controller (P) Switching mode power supply (Q) Stepper motor& Driver&Controller (R) Graphic/ Logic panel (S) Field network device (T) Software (U) Other Dual PID Auto Tuning Control Equipment to be controlled Converter Analog output 1-5VDC 0-10VDC DC4-20mA TZ Series SSR Load power PowerVoltage output terminal I N P U T L O A D T TZ Series DC4-20mA LOAD 600Ω Max. Power controller Load power Load Current output terminal U W R TZ Series Recording instrument /Panel meter DC4-20mA IN Tranmission output terminal + + - - RS485 PC RxD RxD TxD TxD Gnd Gnd IN TZ/TZN Series Converter Communi cation output terminal TZ Series Relay contact terminal Heater Power L C H Magnet or Relay contact Condenser 0.1㎌ 630V A Input correction [ IN-B] Input correction is to correct deviation occurred from temperature sensor such as thermocouples, RTD, Analog sensor etc. If you check the deviation of every temperature sensor precisely, it can measure temperature accurately.
- Input revise can be set at IN-B mode in parameter 1 group.
- Use this mode after measuring deviation occurred from temperature sensor exactly. Because if measured deviation value is not corrected, dis-played temperature may be too high or too low.
- Set range: -49 to 50℃(-50.0 to 50.0℃)
- When you set the Input revise value, you may need to record it, because it will be useful when performing maintenance. Analog input [ A--1, A--2, A--3]
- In case of measuring or controlling humidity & pressure, flux, etc, it uses the proper converter which is converting the measuring value to DC4-20mA or 1-5VDC or 0-10VDC.
- To use analog output of converter as controller input, select the input type as same as analog output conditions. (This should be operated in power-off status.)
- This unit has the mode for the converter built-in.
- Please select A--1(0-10VDC) or A--2(1-5VDC) or A--3 (DC4-20mA) in selection mode of input in parameter 2 group.
- Set the input value by High scale[ H-SC] and Low scale [ L-SC] mode.
- Please connect the analog output of the converte to the temperature sensor terminal of the controller. Please be cautious of the polarity.
- After the procedure, it is controlled same with temperature control.
- Example of usage Output connections
- Application of relay output type Keep power relay as far away as possible from TZ/TZN Series. If wires length of A is short, electromotive force occurred from a coil of magnet switch & power relay may flow in power line of the unit, it may cause malfunction. If wires length of A is short, please connect a mylar condenser 104(630V) across coil of the power relay " " to protect electromotive force.
- Application of SSR output type ※ SSR should be selected by the capacity of load, otherwise, it may short-circuit and result in a fire. Indirect heated should be used with SSR for efficient working. ※ Please use a cooling plate or it may cause the capability deterioration, breakdown of SSR for a long usage.
- Application of current output(DC4-20mA) ※ It is important to select SCR unit after checking the capacity of the load. ※If the capacity is exceeded, it may cause a fire.
- Application of communication output(RS485)
- Application of transmission output(DC4-20mA) For more information about output, refer to the H-139 page. Pressure sensor Pressure Temperature controller Feedback IN-Tsetting : A--3 H-SCsetting : 100 L-SCsetting : 0 DC4-20mA Converter Control system (0 to 100kg)
Calculation range of Block Check Character Start Code Header Code END Code BCC Code Address Code Text STX 10 R/W X/D ETX FSC Supply system power ※A → Over min. 4sec, B → Within max. 300ms, C → Over min. 20ms A B CTZ/TZN S T X A D R C M D T X T E T X B C C S T X A D R C M D T X T E T X B C C A C K S T X A D R C M D T X T E T X B C C Master Interface Standard EIA RS485 Number of connections Max. 31units. It is available to set address 01 to 99. Communication method 2 wire half duplex Synchronous method Asynchronous type Communication distance Within 1.2km Communication speed 2400, 4800, 9600(available to set) Start bit 1bit(Fixed) Stop bit 1bit(Fixed) Parity bit None Data bit 8bit(Fixed) Protocol BCC Upper Terminating resistance N 1 (N-1) TZ/TZN TZ/TZN TZ/TZN (A+) (A+) (A+) (B-) (B-) (B-)RX(-) TX(+) System ordering ※Use a proper twist pair for communication. Communication control ordering 1. The communication control ordering of TZ/TZN Series is exclusive protocol. 2. After 4sec. being supplied the power into master system, then able to start communicating. 3. Initial communication will be started by master system. When Command signal comes out from master system then TZ/TZN Series will respond. Communication Command and Block Format of Command and Response ① Start code It indicates the first of Block STX → [02H], in case of response, ACK will be added. ② Address code This code is master system can discern TZ/TZN Series and able to set within range of 01 to 99.(BCD ASCII) ③ Header code: It indicates command as 2 alphabets as below. RX(Read request) → R[52H], X[58H] RD(Read response) → R[52H], D[44H] WX(Write request) → W[57H], R[58H] WD(Write response) → W[57H], D[44H] ④ Text: It indicates the detail contents of Command/ Response. (see command) ⑤ END code: It indicates the end of Block. ETX → [03H] ⑥ BCC: It indicates XOR operating value from the first to ETX of the protocol as abbreviation of TZ/TZN. Communication Command
- Read [RX] of measurement/setting value : Address 01, Command RX 1.Command (Master) ① Command STX 0 1 R X P 0 ETX FSC Start Address Command head P:Process value S:Setting value End BCC ② Application: Address(01), Header code(RX), Process value(P) STX 0 1 R X P 0 ETX FSC 02 30 31 52 58 50 30 03 BCC
- Write [WX] of setting value: Address 01, Command WX 1.Command(Master) ① Command STX 0 1 W X S 0 Symbol 10 ETX FSC Start Address Command head S:Setting value Space/- 10 End BCC ② Application: In case of writing Address(01), Heading Coad(WX), Setting value(S) +123. STX 0 1 W X S 0 Symbol 10 ETX FSC 02 30 31 57 58 53 30 20 30 31 32 33 03 BCC Response
- Read of process/Setting value 1. In case of receiving normal process value : The data is transmitted adding ACK[60H]. (In case process value is +123.4) A C K S T X 0 1 R D P 0 Symbol 10
0 Decimal
E T X F S C N U L L A C K S T X 0 1 R D P 0 Space 1 2 3 4 1 E T X B C C N U L L 06 02 30 31 52 44 50 30 20 31 32 33 34 31 03 B C C 2. In case process value is -100 A C K S T X 0 1 R D P 0 - 0 1 0 0 0 E T X B C C N U L L 06 02 30 31 52 44 50 30 2D 30 31 30 30 30 03 B C C ※It is responded with 1 byte sized NULL(00H) at the end of response frame (next BCC 16).
(A) Photo electric sensor (B) Fiber optic sensor (C) Door/Area sensor (D) Proximity sensor (E) Pressure sensor (F) Rotary encoder (G) Connector/ Socket (H) Temp. controller (I) SSR/ Power controller (J) Counter (K) Timer (L) Panel meter (M) Tacho/ Speed/ Pulse meter (N) Display unit (O) Sensor controller (P) Switching mode power supply (Q) Stepper motor& Driver&Controller (R) Graphic/ Logic panel (S) Field network device (T) Software (U) Other Dual PID Auto Tuning Control
- Write of setting value In case setting value is -100 A C K S T X 0 1 W D S 0 Symbol 10 E T X F S C A C K S T X 0 1 W D S 0 - 0 1 0 0 E T X B C C 06 02 30 31 57 44 53 30 2D 30 31 30 30 03 B C C
- Others: In case of no response of ACK ① When the address is not the same after receiving STX. ② When receiving buffer overflow is occurred. ③ When the baud rate or others communication setting value are not the same.
- When there are no ACK response ① Check the status of lines ② Check the communication condition(Setting value) ③ When assuming the problem is due to noise, try to operate communication 3 times more until recovery. ④ When occurred communication failure frequently, please adjust the communicating speed. Proper usage Simple "error" diagnosis Caution for using
- When the load (Heater etc) is not operated Please check operation of the OUT lamp located in front panel of the unit. If the OUT lamp does not operate, please check the parameter of all programmed mode. If lamp is operating, please check the output(Relay, SSR drive voltage) after separating output line from the unit. But, the out lamp is not operated for DC4-20mA
- When it displays OPEN during operation This is a warning that external sensor is open. Please turn off the power and check the wire state of the sensor. If sensor is not open disconnect sensor line from the unit and short the input +, - terminal. Turn on the power of the unit and check the controller displays room temperature. If this unit cannot display room temperature, this unit is broken. Please remove this unit and contact our service center. (When the input mode is thermocouple, it is available to display room temperature.)
- In case of indicating ERR0 in display This Error message is indicated in case of damaging inner chip program data by outer strong noise. In this case, please send the unit to our after service center after removing the unit from system. Noise protection is designed in this unit, but it does not stand up strong noise continuously. If bigger noise than specified(Max. 2kV) flows in the unit, it can be damaged.
- Please use the terminal(M3.5, Max. 7.2mm) when connecting the AC power source.
- Please use separated line from high voltage line or power line in order to avoid inductive noise.
- Please install power switch or circuit-breaker in order to cut power supply off.
- The switch or circuit-breaker should be installed near by users.
- This unit is designed for temperature controlling only. Do not apply this unit as a voltage meter or a current meter.
- Be sure to use compensating wire when extending wire from controller to thermocouple, otherwise a temperature deviation will occur at the point where wires are connected to each other.
- In case of using RTD sensor, 3-wire type must be used. If you need to extend the line, 3-wires must be used with the same thickness as the line. It might cause temperature difference if the resistance of line is different.
- In case of making power line and input signal line close, line filter for noise protection should be installed at power line and input signal line should be shielded.
- Keep away from the high frequency instruments.(High frequency welding machine & sewing machine, big capacitive SCR controller)
- If you want to change the input sensor, reset switches (SW1, SW2) according to each input specification after power off. Turn on power and then set sensor mode by front keys at second flow chart.
- This SSR and current of this controller are insulate from internal power.
- Do not connect power line to sensor connecting part. The inner circuit may be damaged.
- Installation environment It shall be used indoor. Altitude Max. 2000m. Pollution Degree 2 Installation Category Ⅱ.