MODEL: TR30 TR30 SPECIFICATIONS ES-8631 Rev.16 Page 1/8 http://www.m-system.co.jp/ Paperless Recorder TR30 Series PAPERLESS RECORDER Functions & Features

  • Records measurement data and running / stopping status of device in an SD card
  • Allows Web browsing of the recorded data
  • Flexibly combined with R30 series I/O modules depending on required signal type and the number of points 110 (4.33) (1 .97) (3.86) mm (inch) MODEL: TR30-G-R[1]

ORDERING INFORMATION

  • Code number: TR30-G-R[1] Specify a code from below for [1]. (e.g. TR30-G-R/Q)
  • Specify the specification for option code /Q (e.g. /C01) MODULE TYPE G: High functionality POWER INPUT DC power R: 24 V DC (Operational voltage range: ±10 %; ripple 10 %p-p max.) [1] OPTIONS blank: none /Q: With options (specify the specification) SPECIFICATIONS OF OPTION: Q COATING (For the detail, refer to M-System's web site.) /C01: Silicone coating /C02: Polyurethane coating /C03: Rubber coating FUNCTIONS & FEATURES TR30 is used in combination with base (model: R30BS) and I/O modules (Remote I/O R30 series). ■ TR30 Input data cllection and recording, and output data transmission: Collects data from I/O modules via internal bus and records the data in the internal memory, then in SD card; Connects with remote I/Os using Modbus/TCP via Ethernet, and collects and records input data of the remote I/Os; Connects with Mitsubishi programmable controller MELSEC using SLMP to collect and record data of the CPU of MELSEC; and Transmits alarm output to Output module in accordance with the preset alarm level.
  • Web server: Works as a web server and displays collected data on the browser of a tablet. Various settings and operations can be done from the tablet.
  • Internal power Internal power required for TR30 and I/O modules is generated from supplied power. ■ I/O Module Outputs data received through the internal bus as discrete outputs; and outputs discrete input data and A/D converted analog input values to the internal bus. (Refer to the specification of each R30 I/O module for details) ■ Installation base The base for installation of modules incorporates PWB for internal power and internal bus. (Refer to the specification of installation base (model: R30BS))

RELATED PRODUCTS

  • Remote I/O R30 series
  • PC Configurator cable USB 2.0 compatible cable (TR30 connector: mini-B type, 5.0m max.)
  • PC configurator software (model: TRGCFG)
  • PC configurator software (model: R30CFG)
  • Viewer software (model: TRViewer) Software downloadable at M-System’s web site.
  • SD card An SD card is required to store data in the unit. Use a memory card of the specified model number. Consult M-System for purchase. - Hagiwara Solutions NSD6-004GH(B21SEI, NSD6-016GH(B20SEI (NSD6-004GH(A00SDI ... discontinued)

MODEL: TR30 TR30 SPECIFICATIONS ES-8631 Rev.16 Page 2/8 http://www.m-system.co.jp/ GENERAL SPECIFICATIONS Connection RUN contact output, power supply: M3 separable screw terminal (torque 0.5 N·m) Ethernet: RJ-45 modular jack Internal bus: Via the Installation Base (model: R30BS) Internal power: Via the Installation Base (model: R30BS) Solderless terminal: Refer to the drawing at the end of the section. Recommended manufacturer: Japan Solderless Terminal (Solderless terminals with insulation sleeve do not fit.) Applicable wire size: 0.25 to 0.75 mm2 Screw terminal: Nickel-plated steel Housing material: Flame-resistant resin (gray) Max. number of R30 I/O modules: 16 (Max. consumption current of I/O modules: 500 mA) Isolation: Ethernet to internal bus or internal power to RUN contact output to power supply to FE Calendar clock: Year (4 digits), month, date, day, hour, minute, second Read rate: Approx. ≤ 1 msec. (Connected max. modules) Indicator LEDs: PWR, TR30 RUN, RECORD, SD CARD, ERROR (Refer to the insruction manual) ■ RUN CONTACT OUTPUT RUN contact output: Turns on (closed) at normal operation Rated load: 250 V AC @ 0.5 A (cos ø = 1) 30 V DC @ 0.5 A (resistive load) (Less than 50 V AC to conform with EU Directive) Maximum switching voltage: 250 V AC or 30 V DC Maximum switching power: 250 VA (AC) or 30 W (DC) Minimum load: 5 V DC @ 10 mA Mechanical life: 2 × 107 cycles (rate 300 cycles/min.) When driving an inductive load, external contact protection and noise quenching recommended. ■Recommended solderless terminal size - M3 (unit: mm) 12 max. 6 max. 3 max. 3.2 dia. R30 CONNECTION ■ TR30 INSTALL POSITION Install to PWR slot (most left slot) and COM slot (right next to PWR slot). ■ COMPATIBLE R30 SERIES MODULES TYPE MODEL Base R30BS Discrete input R30XN16A Discrete output R30YN16A, R30YN16C DC voltage/current input R30SV2, R30SV4 DC voltage/current input, high speed R30SVF4 Thermocouple input R30TS4 RTD input R30RS4 Potentiometer input R30MS4 AC current input R30CT4E Universal input R30US2, R30US4 Totalized pulse input R30PA2 Blank filler R30DM ETHERNET COMMUNICATION Communication Standard: IEEE 802.3u Transmission: 10BASE-T, 100BASE-TX Baud rate: 10/100 Mbps (Auto Negotiation function) Protocol: TCP/IP, Modbus/TCP, HTTP, SLMP, FTP, SMTP, SNTP Transmission media: 10BASE-T (STP, Category 5) 100BASE- TX (STP, Category 5e) Max. length of fieldbus segment: 100 meters Ethernet indicator LED: DPX, LNK IP address: 192.168.0.1 (factory setting) INSTALLATION Power consumption

  • DC: Approx. 18 W 24 V DC (@ output current max. 500 mA) Internal power
  • Max. rated output voltage / current: 21 V DC / 500 mA Total current consumed at the R30 I/O modules used combination with TR30 must be within above current. Operating temperature: 0 to 50°C (32 to 122°F) Storage temperature: -10 to +60°C (14 to 140°F) Operating humidity: 10 to 90 %RH (non-condensing) Atmosphere: No corrosive gas or heavy dust Mounting: Installation Base (model: R30BS) Weight: 300 g (0.66 lb)

MODEL: TR30 TR30 SPECIFICATIONS ES-8631 Rev.16 Page 3/8 http://www.m-system.co.jp/ PERFORMANCE Calendar clock: (with battery backup) Accuracy: Monthly deviation 2 minutes at 25°C Back up period: Approx. 2 years at 25°C Battery: Primary lithium battery (non-removable) (In order to prevent battery drain, battery back up is OFF at factory default. Turn it ON prior to start using.) Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 1500 V AC @ 1 minute (Ethernet to internal bus or internal power to RUN contact output to power supply to FE) STANDARDS & APPROVALS EU conformity: EMC Directive EMI EN 61000-6-4 EMS EN 61000-6-2 RoHS Directive EN 50581 EXTERNAL VIEW Status Indicator LEDs RJ-45 Connector for Ethernet Lock Tab Specifications Ethernet Indicator LEDs SD Card Slot ■ FRONT VIEW ■ BOTTOM VIEW ■ SIDE VIEW Configuration Select SW Logging Button SD Button Function Setting DIP SW Terminal Block for RUN Contact Output, Power Supply Terminal Fixing Screw Base Fixing Screw ON TR30 RUN RECORD SD CARD PWR RUN ERROR CFG DPX LNK RECORD SD CARD TR30 I/O On Configuration Connector U(+) NC V(-) FE Positioning Guide Terminal Cover

MODEL: TR30 TR30 SPECIFICATIONS ES-8631 Rev.16 Page 4/8 http://www.m-system.co.jp/ TERMINAL ASSIGNMENTS NC FE U(+) V(-) NO. ID FUNCTON

1 RUN contact output RUN contact output

2 U (+) Power supply (24 V DC)

3 V (

-) Power supply (0 V DC)

4 RUN contact output RUN contact output

5 NC Not used

6 FE Functional earth

EXTERNAL DIMENSIONS unit: mm (inch) 50 (1 .97) 110 (4.33) 6–M3 SCREW (.24) DIN RAIL 35mm wide [5 (.20)] 110 (4.33) 98 (3.86)

MODEL: TR30 TR30 SPECIFICATIONS ES-8631 Rev.16 Page 5/8 http://www.m-system.co.jp/ SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM Note: In order to improve EMC performance, bond the FE terminal to ground. Caution: FE terminal is NOT a protective conductor terminal. INTERNAL POWER INTERNAL BUS Comm. Circuit Control Circuit Power Circuit INTERNAL POWER Ethernet Configuration STATUS INDICATOR LEDs DIP SW CONFIGURATION SELECT SW SD Botton Logging Botton SD CARD SLOT CONNECTOR RJ-45 CONNECTOR U (+) V (–) FE POWER SUPPLY RUN CONTACT OUTPUT Isolation CONNECTOR CONNECTOR DATA STORING The trend data, event data and comment data are stored into the memory blocks with specified storing rate. These data can be transferred into the SD card with the timing according to the storing rate. ■ No. of memory blocks

  • 50 memory blocks ■ Event data
  • Event: Transition of analog input zone, transition of pulse input zone, status change of discrete input
  • Event detection interval: Same as trend data sampling cycle
  • Stored contents: Date/time, event
  • Number of event: 3000 (per one memory block) ■ Comment data
  • Number of characters for comment: 32
  • Stored contents: Date/time, comment.
  • Number of comment: 1000 (per one memory block) ■ Trend data
  • Channel: Max. 120 points (Choose among followings: analog input (AI), discrete input (DI), pulse input (PI), function input (OI), discrete output (DO)
  • Number of records: Save maximum 50000 samples per one block STORING RATE SAMPLING CYCLE PEN AI DI PI OI DO 5 ms 5 ms 16 16 32 16 16 32 10 ms 5 ms 16 16 32 16 16 32 50 ms 5 ms 16 16 32 16 16 32 100 ms 100 ms 32 32 64 32 32 64 500 ms 100 ms 32 32 64 32 32 64 1 sec. 100 ms 32 32 64 32 32 64 2 sec. 1 sec. 32 32 64 32 32 64 5 sec. 1 sec. 32 32 64 32 32 64 10 sec. 1 sec. 32 32 64 32 32 64 1 min. 1 sec. 120 64 64 32 32 64 2 min. 1 sec. 120 64 64 32 32 64 5 min. 1 sec. 120 64 64 32 32 64 10 min. 1 sec. 120 64 64 32 32 64 15 min. 1 sec. 120 64 64 32 32 64 30 min. 1 sec. 120 64 64 32 32 64 1 hour 1 sec. 120 64 64 32 32 64

MODEL: TR30 TR30 SPECIFICATIONS ES-8631 Rev.16 Page 6/8 http://www.m-system.co.jp/ ■ SD card

  • Recording contents: Trend data, event data, comment data, settings information STORING RATE TRANSFER INTERVAL 5 ms 3 min. 10 ms 5 min. 50 ms 10 min., 30 min. 100 ms 10 min., 30 min., 1 hour 500 ms 30 min., 1 hour, 6 hours 1 sec. 1 hour, 6 hours, 12 hours 2 sec. 1 hour, 6 hours, 1 day 5 sec. 6 hours, 12 hours, 1 day 10 sec. 6 hours, 12 hours, 1 day 1 min. 1 day, 1 week 2 min. 1 day, 1 week 5 min. 1 day, 1 week, 1 month 10 min. 1 day, 1 week, 1 month 15 min. 1 day, 1 week, 1 month 30 min. 1 day, 1 week, 1 month 1 hour 1 week, 1 month Note: De/f_i ning no speci/f_i cation of interval (50000 points) is available for all storing rate.
  • Data format Trend data, event data and comment data are saved with dedicated format (binary, extension “TRD”) or CSV format. Setting information is saved into text format (xml format, extension “xml”).
  • Data file name File name is created with YYYYMMDDHHMMSS and daylight saving time (S or D) in the beginning of sample. (e.g. 20140212100000S.TRD)
  • Viewer Software The data transferred to SD card can be displayed with using dedicated Viewer Software (model: TRViewer). Also, data can be converted to CSV format file.
  • Auto file delete When auto file delete is disabled, data are recorded until there is no remaining space in the SD card. When auto file delete is enabled and the remaining space in the SD card reaches 100MB or less, the data is deleted from the oldest.
  • Storable time duration (rough guide for 4GB SD card “TRD”) STORING RATE 16 pens 32 pens 64 pens 120 pens 5 ms 3 days 10 ms 6 days 50 ms 25 days 100 ms 50 days 30 days 500 ms 8 months 4 months 1 sec. 1 year 9 months 2 sec. 2 years 1 year 5 sec. 7 years 4 years 10 sec. 10 years 7 .5 years 1 min. – 1 hour 10 years (max. 10 years) Note: When only trend logging is enabled.
  • Storable time duration (rough guide for 4GB SD card “CSV”) STORING RATE 16 pens 32 pens 64 pens 120 pens 5 ms 34 hours 10 ms 69 hours 50 ms 14 days 100 ms 28 days 15 days 500 ms 4 months 78 days 1 sec. 9 months 5 months 2 sec. 1 .5 years 10 months 5 sec. 3.5 years 2 years 10 sec. 7 years 4 years 1 min. – 1 hour 10 years (max. 10 years) Note: When only trend logging is enabled. COMMUNICATION ■ IP Supports DHCP client. Allows manual setting of IP address, subnet mask, default gateway and DNS server. ■ Web server function This unit works as a Web server, and allows 'Data,' 'Trend' and 'Event Log' to be viewed from a remote location. Compatible terminals, browser
  • iPad (iPadOS 13.7): Safari
  • Android tablet (Android 9): Chrome 85.0.4183.101
  • Windows PC (Windows 7, 8.1, 10), Edge 85.0.565.44, Internet Explorer 11, Firefox 75.0, Chrome 85.0.4183.102 ■ Modbus/TCP master Allows I/O expansion with remote I/Os such as R3 or R7 series. Collectively handles data from measuring points in multiple locations. ■ Connectable devices
  • R3-NE1
  • R5-NE1
  • R6-NE1, R6-NE2
  • R7E series
  • R9EWTU
  • 72EM2-M4
  • GR8-EM
  • DL8 series
  • TR3EX
  • IT series
  • 73VR series ■ SLMP Client Allows I/O expansion by connecting with the SLMP- compatible CPU unit of Mitsubishi programmable controller MELSEC. Collectively handles data from measuring points in multiple locations ■ Connectable MELSEC model

MODEL: TR30 TR30 SPECIFICATIONS ES-8631 Rev.16 Page 7/8 http://www.m-system.co.jp/

  • MELSEC iQ-R series
  • MELSEC iQ-F series
  • MELSEC Q series ■ Max. number of connectable devices (Number of slaves)
  • 12 nodes (selectable from among Modbus/TCP and SLMP devices) Establishes connection for the number of slaves connected. Note) The number of connectable devices may differ depending on the specifications of each device. Specically, the number of slaves to be connected under 72EM2, GR8, or, WL40EW2 is limited to 8 as the max. number of connections of the device is 8. Note that a communication error can occur when two or more slaves are connected under WL40EW2 as it does not have the Cache function. Avoid such an error by setting the Pause period (interval between communications) longer, for example, so that communication with one slave does not coincide with communication with another slave. ■ Max. I/O points
  • Analog input: 64 points
  • Discrete input: 64 points
  • Pulse input: 32 points
  • Discrete output: 64 points ■ Modbus/TCP slave Remotely monitored with SCADA. Operations such as recording start/stop, entering comment, specifying folder/file name for SD card transfer destination and setting folder name for ftp transfer destination are possible from PLC. ALARM OUTPUT DO designated as alarm contact output can be turned ON at event occurrence. EVENT REPORTING E-MAIL Reporting e-mail function available at event or designated time. Encrypted communication is supported. (SMTP over SSL). The TR30 turns a designated Do ON after transmitting the report.
  • Number of e-mail attention: 32
  • Number of event report text: 32
  • Number of regular report text: 1
  • Channel status: AI, DI, PI, OI, DO status attachable to e- mail
  • Output at transmitting failure: 1 point FTP CLIENT It is available to upload the /f_i le saved in the SD card to FTP server. STORING RATE TRANSFER INTERVAL 5 ms 3 min. 10 ms 5 min. 50 ms 10 min., 30 min. 100 ms 10 min., 30 min., 1 hour 500 ms 30 min., 1 hour, 6 hours 1 sec. 1 hour, 6 hours, 12 hours 2 sec. 1 hour, 6 hours, 1 day 5 sec. 6 hours, 12 hours, 1 day 10 sec. 6 hours, 12 hours, 1 day 1 min. 1 day, 1 week 2 min. 1 day, 1 week 5 min. 1 day, 1 week, 1 month 10 min. 1 day, 1 week, 1 month 15 min. 1 day, 1 week, 1 month 30 min. 1 day, 1 week, 1 month 1 hour 1 week, 1 month Note: If interval is maximum, the data is transferred at the time when 50000 points is stored. FTP SERVER Reading and deleting files in the SD card by an FTP client is available. Operation verified FTP client
  • Explorer
  • Web browser Internet Explorer version 11 Chrome 57.0.2987.98
  • FFFTP 1.98g ARITHMETIC FUNCTION Addition and subtraction, multiplication, division, square root, moving average, delay buffer, exp, common logarithm, natural logarithm, peak hold(max/min), analog accumulation, power, F value calculation, inverse logarighm and scaling are available with function input (OI). OTHER FUNCTIONS Configuration: Configurable with the dedicated software model: TRGCFG

MODEL: TR30 TR30 SPECIFICATIONS ES-8631 Rev.16 Page 8/8 http://www.m-system.co.jp/ SYSTEM CONFIGURATION EXAMPLES Devices other than the TR30 in below provided by the user. TR30 PC SD CARD Viewer software (model: TRViewer) ■ STAND-ALONE Router Ethernet LAN PC TR30 Tablet Router *1 Internet (WAN) ■ VIA INTERNET (WAN) ISP ISP Mobile Line *1. D.DNS service or static IP address is reguired. Note: Data storing to SD card is performed at every transfer interval. Wi-Fi Router Tablet ■ VIA LOCAL NETWORK (LAN) Ethernet PC TR30 Hub Specifications are subject to change without notice.