TM3TI4 SCHNEIDER | Alldatasheet

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 7

Technical content

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein. This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof. Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein. Aug 11, 2019 Product data sheet Characteristics TM3TI4 module TM3 - 4 inputs temperature Product availability: Stock - Normally stocked in distribution facility Main Range of product Modicon TM3 Product or component type Analog input module Range compatibility Modicon M221 Modicon M251 Modicon M241 Analogue input number 4 Analogue input type Current, analogue input range: 4...20 mA Current, analogue input range: 0...20 mA Voltage, analogue input range: 0...10 V Voltage, analogue input range: - 10...10 V Thermocouple, analogue input range: - 200...1000 °C with thermocouple J Thermocouple, analogue input range: - 200...1300 °C with thermocouple K Thermocouple, analogue input range: 0...1760 °C with thermocouple R Thermocouple, analogue input range: 0...1760 °C with thermocouple S Thermocouple, analogue input range: 0...1820 °C with thermocouple B Thermocouple, analogue input range: - 200...400 °C with thermocouple T Thermocouple, analogue input range: - 200...1300 °C with thermocouple N Thermocouple, analogue input range: - 200...800 °C with thermocouple E Thermocouple, analogue input range: 0...2315 °C with thermocouple C Ni 100/Ni 1000 temperature probe, analogue input range: - 60...180 °C Pt 100 temperature probe, analogue input range: - 200...850 °C Pt 1000 temperature probe, analogue input range: - 200...600 °C Complementary Analogue input resolution 15 bits + sign 16 bits Permissible continuous overload 13 V voltage 40 mA current Input impedance <= 50 Ohm current >= 1 MOhm temperature probe >= 1 MOhm thermocouple >= 1 MOhm voltage LSB value 2.44 mV, analogue input: 0...10 V voltage 4.88 mV, analogue input: - 10...10 V voltage 4.88 µA, analogue input: 0...20 mA current 3.91 µA, analogue input: 4...20 mA current 0.1 °C temperature probe 0.1 °C thermocouple Conversion time 100 ms + 100 ms per channel + 1 controller cycle time for analogue input thermo- couple 100 ms + 100 ms per channel + 1 controller cycle time for analogue input temper- ature probe 10 ms + 10 ms per channel + 1 controller cycle time for analogue input volt- age/current Sampling duration 10 ms for analogue input voltage/current 100 ms for analogue input voltage/current 100 ms for analogue input thermocouple 100 ms for analogue input temperature probe

Absolute accuracy error +/- 0.2 % of full scale at 77 °F (25 °C) for analogue input voltage/current +/- 0.2 % of full scale at 25 °C for Pt 100/Pt 1000, Ni 100/ Ni 1000 temperature probe +/- 0.2 % of full scale at 25 °C for thermocouple C 0...2315 °C +/- 6 °C at 25 °C for thermocouple R, S 0...200 °C +/- 0.2 % of full scale at 25 °C for thermocouple R, S 200...1760 °C +/- 0.2 % of full scale at 25 °C for thermocouple B 300...1820 °C +/- 0.4 % of full scale at 25 °C for thermocouple K - 200...0 °C +/- 0.2 % of full scale at 25 °C for thermocouple K 0...1300 °C +/- 0.4 % of full scale at 25 °C for thermocouple J - 200...0 °C +/- 0.2 % of full scale at 25 °C for thermocouple J 0...1000 °C +/- 0.4 % of full scale at 25 °C for thermocouple E - 200...0 °C +/- 0.2 % of full scale at 25 °C for thermocouple E 0...800 °C +/- 0.4 % of full scale at 25 °C for thermocouple T - 200...0 °C +/- 0.2 % of full scale at 25 °C for thermocouple T 0...400 °C +/- 0.4 % of full scale at 25 °C for thermocouple N - 200...0 °C +/- 0.2 % of full scale at 25 °C for thermocouple N 0...1300 °C Temperature drift +/- 0.01 %FS/°C Repeat accuracy +/-0.5 %FS Non-linearity +/- 0.2 %FS Cross talk <= 1 LSB [Us] rated supply voltage 24 V DC Type of cable Twisted shielded pairs cable 30 m for input circuit Current consumption 45 mA at 5 V DC via bus connector 50 mA at 5 V DC via bus connector 35 mA at 24 V DC via external supply 40 mA at 24 V DC via external supply Local signalling 1 LED green PWR Electrical connection 10 x 1.5 mm² removable screw terminal block with pitch 3.81 mm adjustment for inputs and supply 10 x 1.5 mm² removable screw terminal block with pitch 3.81 mm adjustment for inputs Insulation 500 V AC between input and internal logic

1500 V AC between input and supply

Surge withstand 1 kV for power supply with common mode protection conforming to EN/IEC 61000-4-5 0.5 kV for power supply with differential mode protection conforming to EN/IEC 61000-4-5 1 kV for input with common mode protection conforming to EN/IEC 61000-4-5 Mounting support Top hat type TH35-15 rail conforming to IEC 60715 Top hat type TH35-7.5 rail conforming to IEC 60715 Plate or panel with fixing kit Height 3.54 in (90 mm) Depth 2.76 in (70 mm) Width 0.93 in (23.6 mm) Product weight 0.24 lb(US) (0.11 kg) Environment Standards EN/IEC 61010-2-201 EN/IEC 61131-2 Resistance to electrostatic discharge 4 kV on contact conforming to EN/IEC 61000-4-2 8 kV in air conforming to EN/IEC 61000-4-2 Resistance to electromagnetic fields 9.14 V/yd (10 V/m) at 80 MHz...1 GHz conforming to EN/IEC 61000-4-3 0.91 V/yd (1 V/m) at 2 GHz...3 GHz conforming to EN/IEC 61000-4-3 Resistance to magnetic fields 30 A/m conforming to EN/IEC 61000-4-8 Resistance to fast transients 1 kV I/O conforming to EN/IEC 61000-4-4 Resistance to conducted disturbances 10 V at 0.15...80 MHz conforming to EN/IEC 61000-4-6 to Marine specification (LR, ABS, DNV, GL) Electromagnetic emission Radiated emissions, test level: 40 dBμV/m QP class A (10 m at 30...230 MHz) conforming to EN/IEC 55011 Radiated emissions, test level: 47 dBμV/m QP class A (10 m at 230...1000 MHz) conforming to EN/IEC 55011 Immunity to microbreaks 10 ms

-10...35 °C (vertical installation) Relative humidity 10...95 % without condensation in operation 10...95 % without condensation in storage IP degree of protection IP20 Pollution degree 2 3 gn at 8.4...150 Hz with DIN rail mounting support Shock resistance 15 gn during 11 ms Ordering and shipping details Category 22533 - M2XX PLC & ACCESSORIES Discount Schedule MSX GTIN 00785901981732 Nbr. of units in pkg. 1 Package weight(Lbs) 0.47000000000000003 Returnability Y Country of origin JP Offer Sustainability Sustainable offer status Green Premium product RoHS (date code: YYWW) Compliant - since 1415 - Schneider Electric declaration of conformity Schnei- der Electric declaration of conformity REACh Reference not containing SVHC above the threshold Product environmental profile Available Product end of life instructions Available California proposition 65 WARNING: This product can expose you to chemicals including: - - - - - - - Substance 1 Lead and lead compounds, which is known to the State of California to cause can- cer and birth defects or other reproductive harm. - - - - - - - More information For more information go to www.p65warnings.ca.gov

(*) 8.5 mm/0.33 in when the clamp is pulled out.

Mounting on a Panel Surface (1) Install a mounting strip Mounting Hole Layout

Wiring Diagram (Current/Voltage type) (*) Type T fuse (1) Current/Voltage analog output device Wiring Diagram (Thermocouple input type) (*) Type T fuse (2) Thermocouple

Wiring Diagram (Temperature probe input type) (*) Type T fuse