TC100PI MORNSUN | Alldatasheet

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 4

Technical content

The copyright and authority for the interpretation of the products are reserved by MORNSUN TCx00PI 2013.07.01-A/2 Page 1 of 4 Thermocouples Isolation Safety Barrier TC100PI (1 input & 1 output) TC100PI-SP (1 input & 1 output) TC600P (1 input & 2 output) TC600PI-SP (1 input & 2 output) —— TCx00PI Series PART NUMBER SYSTEM TCxxxPI-SP Programmable Symbol Serial Number Channel Type Transducer Type Surge protection symbol RS485

FEATURES

  • 3-port isolation (input, output and power supply)
  • High accuracy (0.1% F.S.) (Accuracy decreases with the smaller range)
  • High linearity (0.1% F.S.)
  • Isolation voltage (Between Hazardous area and safe area: 2500VAC)
  • Low temperature drift (35PPM/°C)
  • Digital bus (RS485)
  • Programmable input/ output
  • Alarm indications
  • High reliability(MTBF>1,000,000 hours)
  • Surge protection GENERAL DESCRIPTION The thermocouples or mV-level signal from the hazardous field is picked up by this product, converted to the standard current or voltage signal which is isolated with the hazardous area and transmitted to the control cabinet, PLC, DCS, display meter etc.. The product is equipped with cold junction compensation. Furthermore, it is armed with RS485 digital bus interface, which makes network configuration and the input or output configuration possible in many application fields. It is an intelligent safety barrier, and the type or range of the thermocouples can be set through the host computer, moreover, cold junction compensation can work automatically. One independent power supply is required. Moreover, within the product power supply, input and output are mutually isolated. Field devices connected and regions: J, K, T, E, S, B thermocouple, millivolt signal sensor; Zone 0, Zone 1, Zone 2, IIA, IIB, IIC, and hazardous area of T4~T6. SELECTION GUIDE Description TCx00PI-/ TCx00PI-SP- Signal Type Range Minimum range R -40~+1700℃ 600℃ S -40~+1700℃ 600℃ K -150~+1370℃ 120℃ J -80~+900℃ 100℃ T -160~+390℃ 100℃ B 320~+1820℃ 780℃ E -80~+700℃ 500℃ Input Signal mV -60~+60mV 10mV Current 4~20mA Output Signal Current 0~20mA Note: 1. The initial setting of the product is signal type: mV, measurement range: -60~+60mV, minimum range: 10mV, current output: 4~20mA. Customers can choose signal type 2. If you need, you can get the isolator's USB adapter which P/N is T-02 free of charge.

The copyright and authority for the interpretation of the products are reserved by MORNSUN TCx00PI 2013.07.01-A/2 Page 2 of 4 ELECTRICAL SPECIFICATIONS Power Supply 18~36VDC (Typ. : 24VDC) Input Power About 2.0W Power Supply Power Protection Reverse protection Input Signal Refer to product overview Compensation range: -25 ~ +75 °C (Every 20°C error of 1°C) Hazardous Area Cold junction compensation Compensation mode: Internal compensation Output Signal Refer to product program ≤ 500Ω (@maximum output current) Load ≥ 10KΩ (@maximum output voltage) Communication Interface RS485 Physical Bus Interface Safe Area Communication protocol Refer to ”MORNSUN Science and Technology Modbus Protocol Rule” TRANSMISSION SPECIFICATIONS Offset 0.1%F.S. Gain Error 0.1%F.S. Plus Error 0.1%F.S. Temperature Drift 0.0035%F.S./°C (-25 ~ +71°C) ISOLATION SPECIFICATIONS 2.5kVAC between control cabinet and application field (Tested for 1 minute and leakage current ≤1mA ) Galvanic isolation 1.5kVDC between power supply and output (Tested for 1 minute) EMC EN 61326 SURGE PROTECTION SPECIFICATIONS (–SP SERIALS) Maximum continuous operation voltage 30VDC Rated discharge current 5KA (Line-to-ground, line-to-line) Maximum discharge current 10KA (Line-to-ground) Standard GB18802. 21-2004 OTHER SPECIFICATIONS Lower limit alarm Below its lower limit of -5 °C (temperature signal) or -2mV (mV signal), output current about 3mA (4~20mA) or 21mA (4~20mA), light “ L” on Upper limit alarm Exceeding its upper limit of +5°C (temperature signal) or +2mV (mV signal), output current about 22mA, light “ H” on Break coupling alarm Break coupling or input signal ≥ 70mV, output current about 23mA, light “O” on Operation temperature: -25 ~ +60°C Ambient temperature Transport and Storage temperature: -50 ~ +105°C Safety Class IP20(IEC60529 / EN60529) Weight About 123g Note: 1. All specifications measured at TA=25 °C, humidity<75%, nominal input voltage and rated output load unless otherwise specified. 2. Only typical models listed, specifications of custom product may be different. Please contact our service people directly for certain conditions. 3. Communication protocol details refer to ”MORNSUN Science and Technology Modbus Protocol Rule ”. 4. The MORNSUN Safety Barrier Configuration software can be downloaded free from the MORNSUN homepage www.mornsun.cn or you can contact us to get it. CONNECTION 1. Removable terminal; 2. Cross section area of wiring: 0.5mm ~2.5 mm 3. The length of bare wire is about 8mm, locked up by the M3 bolt. Application about Surge Protector Connect the ground of protected equipment or case, and ground of surge protectors directly, and connecting wire is as short as possible. Single point grounding can make surge protectors avoid high-voltage between surge protectors and the ground, which makes protection more effectively. Operation notes 1. Please read the user manual carefully before using. If any questions please contact our technical support department. 2. Please do not use this product in hazardous area. 3. Power supply of this product should be 24VDC. 220VAC is prohibited. 4. To avoid explosion protection function invalid or any failure, disassembling the product is forbidden.

The copyright and authority for the interpretation of the products are reserved by MORNSUN TCx00PI 2013.07.01-A/2 Page 3 of 4 APPLICATION CIRCUIT DIAGRAM & PIN DESCRIPTION Hazardous-area Safe-area 485B 485A 5 6 485B 485A 5 6 TC600PI-SPTC100PI-SP RL RL RL 18~36VDC 18~36VDC 4/0~20mA 4/0~20mA 4/0~20mA Hazardous-area Safe-area mV mV + - + - Note: No surge protection products (without the suffix-SP), no pin 13,14,15,16. INSTALLATION & DISASSEMBLY Installation DIN35mm standard rail installation: 1.Insert the top of the instrument card in the rail; 2.Push the bottom of the instrument into the rail. Disassembly 1. Use a screwdriver (Width of edge ≤ 6mm), cut in the metal card lock from the underside; 2. Boost up the screwdriver and pry the metal card lock downwards; 3. Pull the instrument out of the rail. PACKAGING DIMENSION & PACKAGING DIAGRAM

The copyright and authority for the interpretation of the products are reserved by MORNSUN TCx00PI 2013.07.01-A/2 Page 4 of 4 Note: 1. All specifications are measured at Ta=25°C, humidity<75%, nominal input voltage and rated output load unless otherwise specified. 2. In this datasheet, all the test setup and methods are based on our corporate standards. 3. All characteristics are for listed models, and non-standard models may perform differently. Please contact our technical support for more details. 4. Please contact our technical support for any specific requirement. 5. Specifications of this product are subject to changes without prior notice. MORNSUN Science & Technology Co.,Ltd. Tel: 86-20-38601850 Fax:86-20-38601272 E-mail: info@mornsun.cn Http://www.mornsun-power.com