DATASHEET SEARCH SITE | WWW.ALLDATASHEET.COM
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 4
Technical content
Features
- Accurate carbon dioxide transmitter for HVAC control applications
- Easy mount with 2 external tabs.
- Rated up to IP67 (build dependent)
- Available with potting
- Different calibrations available up to 20% CO concentration
- Analogue or digital output options
- Non-Dispersive Infra-Red measuring technology
- Sensors are shipped factory calibrated
- Accuracy for 10 year life
- Extended operating temperature range Amphenol Advanced Sensors
Non-Dispersive Infra-Red (NDIR), single or dual wavelength. Power Supply Requirements 15 – 15Vdc ±10% 24 - 18-30 VAC RMS, 50/60 Hz, or 18 to 42 VDC, polarity protected Power Consumption Typical 0.7 W at nominal voltage of 24V AC RMS Range See Ordering Information for calibrated ranges Resolution Minimum 10bit or analog equivalent Accuracy Single Wavelength (0~2,000 ppm as example)
- 400-1250 ppm ±30 ppm or 3% of reading, whichever is greater*,**
- 1250-2000 ppm ±5% of reading + 30ppm *, ** Dual Wavelength 0~2,000ppm range
- 75 ppm or 10% of reading (whichever is greater) 0~200,000 ±5% of reading or ±0,3 vol% CO 2 (whichever is larger) at 0 - 20 vol% CO2 and 0°C to +25°C, At 25°C to 50°C additional ±0,1% of reading or ±0,01 vol% CO 2 (whichever is larger) per degree C. *Tolerance based on span gas of ±2% ** ABC Logic not deactivated Temperature Dependence 0.2% FS / °C Response time, tau (63%) < 200 sec Aging (Dual Wavelength only) +/- 5% of reading annual drift. Less than +/- 25% of reading within product life time. Recommended Recalibration Interval Single Wavelength – no calibration required Dual Wavelength - 1 year Working Temperature 0° to +50°C (measures within tolerance) Operation Temperature (Sensor Is Powered) -30° to +50°C Storage Temperature -40° to +70°C Minimum Lifetime 10 years or 30000 operating hours Flammability Classification To UL94 5VA (dependent upon build) RH Range 0% to 99% RH (non-condensing) Atmospheric Conditions Sensors have been designed and tested to the following, however, not all models are as capable; please discuss your application with Telaire.
- Marine, salt mist and particles present
- 0 2 level 0-21 vol%
- 0 to 100% RH.
- Ammonium max 200mg/m3
- S02 max 0,5 vol%
- Ethylene max 500ppm vol
- Ozone IP Class Up to IP67, dust tight and immersion to 1m. Optional potting Discuss your requirement with Telaire. Output Configurations Digital
- Modbus over RS485
- UART Analogue*
- 0 to 5 V
- 0 to 10 V
- 4 to 20mA *Digital to Analogue Error ±1% T3000 Series Specifications
Carbon Dioxide ABC Logic™ Self Calibration The single wavelength sensors employ the patented ABC (Automatic Background Calibration) Logic self- calibration system. ABC Logic virtually eliminates the need for manual calibration in applications where the indoor CO2 level drops to outside levels during unoccupied periods (e.g. during evening hours). ABC Logic is a special software routine in the sensor that remembers the background readings for 14 consecutive evenings, calculates if there is a sensor drift, and then corrects for it. With ABC Logic enabled, the sensor will typically reach its operational accuracy after 25 hours of continuous operation at a condition that is exposed to ambient reference levels. Sensors will maintain accuracy specifications with ABC Logic enabled, given that it is at least three times in 14 days exposed to the reference value and this reference value is the lowest concentration to which the sensor is exposed. Note: Applies when used in typical indoor ambient air. Consult Telaire if other gases or corrosive agents are part of the application environment. CO2 Calibration Guarantee Telaire is serious about minimizing maintenance, so each single-wavelength sensor comes with a lifetime calibration guarantee. And each dual wavelength sensor has a two-year calibration guarantee.
Ordering Information
Please discuss your specific needs with the Telaire account management team, as many configurations are possible. Some combinations are already in production. Derivatives include lesser ingress protection, higher fire and smoke ratings, different outputs, and different calibration levels. Output Options: Digital Analogue Modbus 0-5V UART 0-10V 4-20mA Measuring Technology Options: Single Wavelength with ABT Logic for HVAC Applications Dual Wavelength for 24/7 Applications Materials: Materials to Railway Specifications, or room environment specification, with or without potting. Available Calibrations: 0-2K 0-5K 0-50K 0-200K 0-3K 0-10K 0-100K ppm by volume Power Supply Options:
15 Vdc supply
www.amphenol-sensors.com © 2014 Amphenol Corporation. All Rights Reserved. Specifications are subject to change without notice. Other company names and product names used in this document are the registered trademarks or trademarks of their respective owners. Amphenol Advanced Sensors www.telaire.com