SVX120KL TRIPPLITE | Alldatasheet

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 6

Technical content

Features

Tripp Lite's SVX120KL 120kVA / 120kW SmartOnline UPS offers network-grade power protection in a highly-configurable large-chassis modular, scalable form factor Supports 220/380, 230/400 or 240/415V AC, 3-Phase Wye 4-Wire plus Earth Hardwire input and output● Highlights 120kVA / 120kW modular, scalable, 3-phase, Large-Frame tower UPS Supports 3 phase 220/380, 230/400 or 240/415V AC, 50/60Hz, Wye; Scalable to 210kVA with N+1 redundancy High efficiency on-line UPS with DSP/IGBT technology and 1% output voltage regulation Pre-installed WEBCARDLX network interface; Economy mode option reduces operating and cooling costs Batteries not included, External battery cabinets sold separate; Tested to CE for worldwide

applications

SVX120KL UPS System● Instruction manual● Warranty information●

Tested to CE for worldwide applications● Open slots for up to 4 additional SVX30PM 30kW power modules enables scalable capacity configurations up to 210kW with enhanced N+1 reliability Pre-installed WEBCARDLX network interface● Serial port enables unattended shutdown and UPS monitoring ability● Modular configuration with hot-swappable power modules enables easy and fast maintenance with zero downtime Wide input voltage operating range enables full continuous online operation during brownouts as low as 120V (Ph-N) and overvoltages up to 276 (Ph-N) Narrow output voltage operating range regulates output voltage within 1% of the selected 220/230/240 nominal output voltage in online, double-conversion mode Over 95% efficient in online, double-conversion mode and over 99% efficient in optional economy-mode enables reduced operating and cooling costs Less than 3% input Total Harmonic Distortion (THDi) prevents the need to oversize generator systems relative to UPS capacity Dual hardwire input design enables operation from one or two input power sources● N+1 fault tolerance is supported anytime there is an “extra” SVX30PM 30kW power module installed beyond the minimum required quantity (For example, this UPS provides N+1 fault-tolerance when loaded to 90kVA or less; Loads of 90-120kVA are fully supported, but without N+1 fault tolerance) Front panel combination LCD/LED display offers full UPS condition and status reporting plus additional configuration options OVERVIEW UPC Code 037332194367 OUTPUT Output Volt Amp Capacity (VA) 120000 Output kVA Capacity (kVA) 120 Output Watt Capacity (Watts) 120000 Output kW Capacity (kW) 120 Output Capacity Details OVERLOAD CAPABILITY: Supports 105-110% load for 1 hour, 111-125% load for 10 minutes, 126-150% for 1 minute and Over 150% for 200ms before switching to Bypass; Online operation resumes when load is reduced to 100% or less Power Factor 1.0 Crest Factor 3:1

Nominal Output Voltage(s) Supported 220/380V 3-PH Wye; 230/400V 3-PH Wye; 240/415V 3-PH Wye Nominal Voltage Details Output THD full resistive load: <1.5%; Output THD non-linear load: <4%; Max DC offset: ±50mV; Max Phase angle deviation: 2°; Max Voltage unbalance deviation: 1%; Output short-circuit protection included Frequency Compatibility 50 / 60 Hz; Supports 50 to 60 Hz and 60 to 50 Hz conversion Frequency Compatibility Details Auto-selectable, user adjustable Output Receptacles Hardwire Output Circuit Breakers 400A 3 pole magnetic breaker Output AC Waveform (AC Mode) Pure Sine wave Output AC Waveform (Battery Mode) Pure Sine wave Output Voltage Regulation ONLINE, FREQUENCY CONVERSION, BATTERY MODE: 220/230/240V ±1% typical (balanced load); ±2% typical (unbalanced load); ECONOMY MODE: 220/230/240V ±15V; BYPASS MODE: +15% (default, adjustable to +10%, +15% or +20%), -20% (default, adjustable to -10%, -20%, -30%) Output Frequency Regulation ONLINE MODE: Output frequency is ±0.05Hz of input frequency when input is within ±4Hz* of the configured 50/60Hz output setting; Output frequency is ±0.05Hz the configured 50/60Hz output setting when input is outside ±4Hz* of the configured 50/60Hz output setting; BATTERY MODE: Output frequency is ±0.1Hz of the configured 50/60Hz output setting; FREQUENCY CONVERTER MODE: Output frequency is ±0.1Hz of the configured 50/60Hz output setting; ECONOMY MODE: Output frequency equals input frequency up to ±4Hz* of the configured 50/60Hz output setting (UPS switches to Online mode if frequency goes outside of this range); BYPASS MODE: Output frequency equals input frequency up to ±4Hz* of the configured 50/60Hz output setting (switches to STANDBY mode if frequency goes outside of this range). *The TRACKING RANGE is factory set to ±4Hz and is user adjustable to ±1Hz, ±2Hz or ±4Hz; The selected TRACKING RANGE setting controls frequency output tolerances as described above in Online, Economy and Bypass modes Output Amp Capacity Output Amp Capacity 182A (220/380V); 173A (230/400V); 167A (240/415V) Individually Controllable Load BanksNo Modular Upgrade Options Includes 4 SVX30PM 30kVA power modules. Up to 4 additional SVX30PM 30kVA power modules can be added for additional capacity or N+1 availability; Add 1 SVX30PM for 150kVA capacity (or 120kVA with N+1 redundancy); Add

2 SVX30PM for 180kVA capacity (or 150kVA with N+1 redundancy); Add 3 SVX30PM for 210kVA capacity (or

180kVA with N+1 redundancy); Add 4 SVX30PM for 210kVA total capacity with N+1 redundancy INPUT Rated input current (Maximum Load)SVX120KL 120kVA Configuration: 220A; Maximum 210kVA Large Chassis Configuration: 385A; 40A maximum inrush current Nominal Input Voltage(s) Supported220/380V 3-PH Wye; 230/400V 3-PH Wye; 240/415V 3-PH Wye Nominal Input Voltage DescriptionSet of two hardwire input connections enables 3-Phase Wye, 4 wire (3P, N, G) inputs from two separate power sources UPS Input Connection Type Hardwire Input Circuit Breakers MAIN and ALTERNATE AC inputs are each protected by 400A 3 pole magnetic breakers Input Phase 3-Phase Input Frequency 40 to 70Hz (online mode); 50/60Hz Auto-selectable Power Factor (Input) Greater than 0.99 (full load) THDi Less than 3% (full linear load) BATTERY Full Load Runtime (min.) Batteries sold separate; Runtime is dependent on battery pack quantity and load level

Expandable Battery Runtime Supports extended runtime with optional external battery packs; 100A 3 pole 250VDC breaker recommended for external battery Expandable Runtime Description External battery pack wiring is contractor supplied DC System Voltage (VDC) ±240VDC Battery Recharge Rate (Included Batteries) User selectable charging current of 1A to 8A (2A factory setting); Recharge rate is dependent on number of external battery packs connected and the selected charge current setting Battery Replacement Description Hot-swappable, replaceable batteries Expandable Runtime Yes VOLTAGE REGULATION Voltage Regulation Description Online, double-conversion power conditioning Overvoltage Correction Maintains continuous output in online mode, without using battery power, during overvoltages to 478V (Ph-Ph), reducing output to within 1% of selected 380/220V, 400/230V, 415/240V nominal output voltage Undervoltage Correction Maintains continuous output in online mode, without using battery power, during brownout/undervoltage conditions to 305V (Ph-Ph) at full load and to 208V (Ph-Ph) at 70% output load or less, increasing output to within 1% of selected 380/220V, 400/230V, 415/240V nominal output voltage USER INTERFACE, ALERTS & CONTROLS Front Panel LCD Display 145mm front panel LCD display with directional scroll and select buttons offers complete operating status display, plus setting and selection options for all UPS functions Switches Front panel buttons include ESC (menu escape), UP/LEFT (menu up / left), DOWN/RIGHT (menu down / right), ENTER (confirm selection), HOME (return to home screen) and POWER (on/off power control); Also includes Manual Bypass switch Alarm Cancel Operation Audible alarms can be muted using on-screen prompts Audible Alarm Unique audible alarms for POWER ON / POWER OFF (alarm sounds for 2 seconds), BATTERY MODE (alarm sounds every 2 seconds), LOW BATTERY (alarm sounds every 0.5 seconds), UPS ALARM (alarm sounds every 1 second), UPS FAULT (continuous alarm) LED Indicators Front panel LED indicators represent INPUT (green), BYPASS (amber), INVERTER (green), BATTERY (red) and ALARM (red) SURGE / NOISE SUPPRESSION EMI / RFI AC Noise Suppression Yes AC Suppression Joule Rating 2496 AC Suppression Joule Rating Details 2496 joules (Ph-E), 2496 joules (Ph-N), 1872 joules (N-E) AC Suppression Response Time Instantaneous PHYSICAL Installation Form Factors Supported with Included Accessories Tower Primary Form Factor Tower UPS Power Module Dimensions (hwd, in.) 79.13 x 23.62 x 43.3 UPS Power Module Dimensions (hwd, cm) 200.99 x 59.99 x 109.98

UPS Power Module Weight (lbs.) 906.1 UPS Power Module Weight (kg) 411.00 Shipping Dimensions (hwd / in.) 75.00 x 29.00 x 48.00 Shipping Dimensions (hwd / cm) 190.50 x 73.66 x 121.92 Shipping Weight (lbs.) 1055.00 Shipping Weight (kg) 478.54 Cooling Method Fans UPS Housing Material Steel Primary UPS Height (mm) 2,010 Primary UPS Width (mm) 600 Primary UPS Depth (mm) 1,100 ENVIRONMENTAL Operating Temperature Range 0° to +40°C (+32° to +104°F); De-rates to 90% capacity at 35°C / 95°F and 80% capacity at 40°C / 104°F Storage Temperature Range -15° to +60°C (+5° to +140°F) Relative Humidity 0 to 95%, non-condensing AC Mode BTU / Hr. (Full Load) 21701 AC Economy Mode BTU / Hr. (Full Load) 3302 AC Mode Efficiency Rating (100% Load) 95% AC Economy Mode Efficiency Rating (100% Load) 99% Audible Noise Less than 73 DBA front-side, 1m Operating Elevation (m) Up to 1000m (At elevations over 1000m, output de-rates by 1% per 100m) COMMUNICATIONS Communications Interface DB9 Serial; EPO (emergency power off); Pre-installed network card; Slot for SNMP/Web interface Network Management Cards &nbsp;<a class="productLink" href="//www.tripplite.com/Web-Management-Accessory- Card~WEBCARDLX">WEBCARDLX</a>&nbsp; Network Monitoring Port DescriptionIncludes pre-installed Tripp Lite WEBCARDLX network interface PowerAlert Software For local monitoring via the UPS’s built-in communication ports, download PowerAlert Local software at http://www.tripplite.com/poweralert Communications Cable DB9 cabling included SNMP Compatibility SNMP Compatibility Includes pre-installed&nbsp;<a class="productLink" href="//www.tripplite.com/Web- Management-Accessory-Card~WEBCARDLX">WEBCARDLX</a>&nbsp;network interface card LINE / BATTERY TRANSFER Transfer Time No transfer time (0 ms.) in online, double-conversion mode; Less than 20 ms. transfer time in economy mode

© 2019 Tripp Lite. All rights reserved. All product and company names are trademarks or registered trademarks of their respective holders. Use of them does not imply any affiliation with or endorsement by them. Tripp Lite has a policy of continuous improvement. Specifications are subject to change without notice. Tripp Lite uses primary and third-party agencies to test its products for compliance with standards. See a list of Tripp Lite's testing agencies: https://www.tripplite.com/products/product-certification-agencies Low Voltage Transfer to Battery Power (Setpoint) Maintains continuous operation without using battery power during brownout/undervoltage conditions to 305V (Ph- Ph) Full load or 208V (Ph-Ph) 70% load or less; Below the low transfer voltage point, output is maintained utilizing reserve battery power High Voltage Transfer to Battery Power (Setpoint) Maintains continuous operation without using battery power during overvoltages to 478V (Ph-Ph), reducing output within 1% of nominal; Above this point, output is maintained utilizing reserve battery power SPECIAL FEATURES Cold Start (Startup in Battery Mode During a Power Failure) Cold-start operation supported High Availability UPS Features Automatic inverter bypass; Hot swappable batteries Green Energy-Saving Features Greater than 95% efficiency - GREEN UPS; High efficiency economy mode operation; Schedulable daily hours of economy mode operation CERTIFICATIONS UPS Certifications CE; ROHS (Restriction of Hazardous Substances) UPS Certification Details Agency standards IEC 62040-1:2008+A1:2013; EMI Approvals EN62040-2, 2006 (Category C3); Vibration and Shock: SS-EN 60068-2-64 WARRANTY Product Warranty Period (International) 2-year limited warranty