www.e-t-a.de Power Distribution System SVS15 1646
Description
Technical data (Tamb = 25 C, UB = DC 24 V)
Ordering information
SVS15-08-... The power distribution system SVS15 for rail-mounting distributes the voltage potentials U1 and U2, which are supplied by a DC 24 V power supply, to 8 ways ( 4 x U1, 4 x U2) and protects the connected loads selectively by means of plugged-in circuit breakers. With a maximum load current of 8 A per way and a maximum total current of 40 A the SVS 15 provides ease of power distribution in short circuit limited DC 24 V applications. Five protected »L+« load outputs per way and 30 minus- terminals significantly reduce wiring time. Suitable for the following devices: electronic circuit breaker ESS20-003.. electronic circuit protector ESX10-103.. thermal-magnetic circuit breaker 2210-S21 Type SVS15 power distribution system for ESS20-003, ESX10-103 and 2210-S21 l for short circuit limited DC 24 V-applications l max. 40 A continuous load l one integral circuit breaker (CB1): overcurrent protection for group and sum signalling, red LED flashes upon trip of CB1 l incl. 1 insulated wire bridge Y 303 881 08 l accessories: jumper SB-S11-P1-01-1-1A (for free ways), to be ordered separately Version, max. number of circuit breakers on the power distribution system 08 8 circuit breakers (F1...F8) Fitting version B10 standard: completely fitted with plug-in type screwless terminals (max. 2.5 mm2, without wire end ferrule) Minus terminals K01 30 minus terminals Special marking SB01 with marked terminals line entry U1/U1/U2/U2/0V/0V remaining terminals 1/2/3/4/5 SVS15 - 08 - B10 - K01- SB01 Accessories: jumper and wire bridge see page “Accessories” Application modular power distribution system for short circuit limited DC 24 V applications Line entry rated voltage: DC 24 V (18...32 V) total current: max. 40 A DC 24 V (+) = X21 U1 / U1 DC 24 V (+) = X21 U2 / U2 DC 24 V (-) = X21 0V / 0V terminals 3 x 2 screwless terminals max. 10 mm for supplies U1 and U2 integral loop-through for sub-distribution and additional connection of an external buffer module max. cable cross section with/without wire end ferrule 0.25 – 10 mm2 stripped length 12 mm F positions 8 positions for circuit breakers, suitable for ESS20-003, ESX10-103, 2210-S21 Plug jumper SB-11-P1-01-1-1A into free ways (order separately, see accessories) Load outputs per way rated voltage: DC 24 V (18…32 V) current: max. 8 A per terminal block/position 1) terminals: 5 x L+ protected per position F1...F8 carried out to terminals X1...X8 plug-in type screwless terminals max. 2.5 mm 2 Minus terminals rated voltage: DC 24 V (18…32 V) current: max. 8 A per terminal block terminals: 5-pole terminals X22 … X27 (30 minus terminals in total) plug-in type screwless terminals max. 2.5 mm max. cable cross section without wire end ferrule 0.2 – 2.5 mm2 stripped length 10 mm l systematic integration of protection and distribution functions l power distribution and selective protection of DC 24 V load circuits in one product l clear distribution concept for two voltage potentials U1 and U2 l cost-effective through reduction of wiring, design and installation time l ease of maintenance, diagnosis and expansion l compact power distribution for compact control cabinets l additional integral minus terminals 1) When connected in series and mounted side-by-side, circuit breakers type ESS20, ESX10, 2210, 3600 and 3900 rated 10 A can only carry 80 % rated load.
www.e-t-a.de Power Distribution System SVS15 1646 Technical data (Tamb = 25 C, UB = DC 24 V) Signalling rated voltage: DC 24 V (18...30 V) total current: max. 0.5 A signalling terminal X31 for sum or group signal X31.1 [OUT-S/GR1] signal output: output sum signal S or output group signal GR1 X31.2 [+DC24V] external supply + DC 24 V for signal circuit (max. 0.5 A) X31.3 [IN-GR] supply group signal via bridge between X31.4 and X31.3 X31.4 [PROT24) signal circuit, protected by integral circuit breaker CB1 X31.5 [IN-S/OUT-GR2] supply sum signal via bridge between X31.4 and X31.5 or output group signal GR2 (at bridge between X31.4 and X31.3) terminals: 5-pole terminals plug-in type screwless terminals max. 2.5 mm2 max. cable cross section without wire end ferrule 0.2 – 2.5 mm2 stripped length 10 mm Selective overcurrent protection CB1 for supply of sum or group signal. Red LED flashes after trip. Reset CB1: briefly push red actuator Termination for signalling, load outputs and minus-terminals B10: plug-in type screwless terminals max. 2.5 mm with integral test socket (standard) General data l Mounting: top hat rail to EN 50022 - 35 x 7.5 l temperature range: 0...50 °C (without condensation) l storage temperature: -20...+70 ° l housing material: plastics l protection class: terminals IP20 DIN 40050 pcb IP00 DIN 40050 (double coating) l insulation voltage: DC 250 V (pcb) l dimensions: see drawings (tolerances to DIN ISO 286 part 1 IT 13) l Mass: SVS15-08-B10: approx. 560 g Reference notes l The max. total current of 40 A must not be exceeded. l In each load circuit the cable cross sections and the current rating of the protective device must be selected according to the rating of the connected load. l The technical data of the circuit breaker used must be observed. l According to “Machinery Directive 98/37/EG and EN 60204-1, Machine Safety“ special precautions have to be taken in machinery (e. g. use of a safety PLC) to prevent inadvertent start-up of machinery parts. In the event of a failure (short circuit / overload) the load circuit will be disconnected by the circuit breaker. l The power distribution system must be installed by qualified personnel only. l The assembly is only suitable for use at safety extra-low voltage (DC 24 V) l Only after expert installation may the assembly be connected to a power supply. l After tripping of the circuit breaker and before reset the cause of tripping (short circuit or overload) must be remedied. l The international standards (e. g. DIN VDE 0100 for Germany) must be observed with respect to installation and selection of cables. l Connection to higher or not reliably disconnected voltages may be hazardous or cause damages.
www.e-t-a.de Power Distribution System SVS15 1646 Power Distribution System SVS15 Wiring example: SVS15-08... with ESX10-103 and group signalling Wiring example: SVS15-08... with ESX10-103 and sum signalling Signal path of the sum signalling from F1 to F8 X31.1 [OUT-S] signal output sum signal X31.2 [+DC24V] supply + DC 24 V for signal circuit X31.3 - free - X31.4 [PROT24] signal circuit, protected by CB1 X31.5 [IN-S] line entry sum signalling with insulated wire bridge SC/SO auxiliary make contact (ESX10-103) X31 SC OUT-S +DC24V SO -F1 SC SO -F2 SC SO -F3 SC SO -F4 SC SO -F5 SC SO -F6 SC SO -F7 SC SO -F8 CB1 The signal path of the group signalling is as follows: from F1 to F4 = group 1, from F5 to F8 = group 2 X31.1 [OUT-GR1] signal output group 1 X31.2 [+DC24V] supply + DC 24 V for signal circuit X31.3 [IN-GR] supply group signal with insulated wire bridge X31.4 [PROT24] signal circuit, protected by CB1 X31.5 [OUT-GR2] signal output group 2 SC/SO auxiliary make contact (ESX10-103) X31 SC SO -F1 SC SO -F2 SC SO -F3 SC SO -F4 SC SO -F5 SC SO -F6 SC SO -F7 SC SO -F8 OUT-GR1 OUT-GR2 CB1
www.e-t-a.de Power Distribution System SVS15 1646 Dimensions SVS15-08... K01 (with 30 minus terminals) Mounting position X21 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 U1 U1 U2 U2 0V 0V U1 U1 U1 U1 U2 U2 U2 U2 X2 X3 X4 X5 X6 X7 X8 X22 X23 X24 X25 X26 X27 F1 F2 F3 F4 F5 F6 F7 F8 B10 B20 C10 Typ: SVS15-08- xxx-K01 RESET NUR KURZ DRÜCKENDC24V/40A 52.2 2.06 4.15 105.4 top hat railEN 50022-35x7.5 (not supplied with product) 15.5 .610 spacing depending on fitting version marked (X) red LED flashes upon trip of CB1 terminals power suppply screwless terminals 45 ° 10 mm2 load outputs, 5-pole 2.5 mm2 depending on fitting version plug-in type screwless terminals B10 plug-in type screw terminals B20 pcb screwless terminals C10 211.5 8.33 X31 bridge, fully insulated, 2-pole
www.e-t-a.de Power Distribution System SVS15 1646 Power Distribution System SVS15 Schematic diagram SVS15-08-B10 K01, fitted with ESS20-003 and ESX10-103 154 (157) ESS20... 6.06 (6.18) 122 ESX10... 4.80 52 SVS... 2.05 105.4 4.15 211.5 8.33 top hat rail EN 50022-35x7.5 (not supplied with product) Germany SVS15-08- xxx-K01 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 U1 U1 U2 U2 0V 0V DC 24 V/40 A B10 F1 U1 F2 U1 F3 U1 F4 U1 F5 U2 F6 U2 F7 U2 F8 U2 X22 X23 X24 X25 X26 X27 X21 RESET NUR KURZ DRÜCKEN B20 C10 CB1 SB01 Please order plug-in modules (circuit breakers/jumpers) separately
www.e-t-a.de Power Distribution System SVS15 1646 Schematic diagram SVS15-08... K01 (fitted with ESX10-103) DC 24 V / max. 40 A X31 X21 CB1 1 1 Circuit breakers CB1: shown in tripped condition LED V1 flashes upon trip of CB1 DC 24 V / 8 A DC 24 V / 8 A DC 24 V / 8 A U1F1 SC GND (-) Line (+) SI LOAD (L+) U1F2 SC GND (-) Line (+) SI LOAD (L+) U2F5 SC GND (-) Line (+) SI LOAD (L+) U2F6 SC GND (-) Line (+) SI LOAD (L+) U2F7 SC GND (-) Line (+) SI LOAD (L+) U2F8 SC GND (-) Line (+) SI LOAD (L+) U1F3 SC GND (-) Line (+) SI LOAD (L+) U1F4 SC GND (-) Line (+) SI LOAD (L+) 1 - X22 X23 X24 X27 X26 X25 DC 24 V / 8 A DC 24 V / 8 A DC 24 V / 8 A DC 24 V / 8 A DC 24 V / 8 A
www.e-t-a.de Power Distribution System SVS15 1646 Power Distribution System SVS15 X21 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 U1 U1 U2 U2 0V 0V U1 U1 U1 U1 U2 U2 U2 U2 X2 X3 X4 X5 X6 X7 X8 X22 X23 X24 X25 X26 X27 F1 F2 F3 F4 F5 F6 F7 F8 B10 B20 C10 Typ: SVS15-08- xxx-K01 RESET NUR KURZ DRÜCKENDC24V/40A Signalbrücke Signal loop OK OK OK OK OK OKOK If the distribution rail is not completely fitted with ESS20-003, the open way may be closed by means of a jumper type SB-S11-P1-01-1-1A. The signal path of the sum signalling - to X31.4 via integral overcurrent protection CB1 upon feeding the +DC24V potential into X31.2 - from X31.4 via the plugged-in wire bridge to X31.5 - via all auxiliary make contacts SC/S0 of the plugged-in circuit breakers ESS20-003 - back to the signal output of the sum signal X31.1 (“OUT-S“) Under normal operating conditions (i.e. all circuit breakers fitted and working) the signal path (SC) to (SO) is closed. X31 Application example with insulated wire bridge X21 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 U1 U1 U2 U2 0V 0V U1 U1 U1 U1 U2 U2 U2 U2 X2 X3 X4 X5 X6 X7 X8 X22 X23 X24 X25 X26 X27 F1 F2 F3 F4 F5 F6 F7 F8 B10 B20 C10 Typ: SVS15-08- xxx-K01 RESET NUR KURZ DRÜCKENDC24V/40A OK OK OK OK OK OK OKOK Terminal X31 e.g. for group signalling plug in insulated wire bridge between X31.4 and X31.5 feed-in of + DC 24 V in X31.2 signal output of the group signal of all circuit breakers is X31.1 X31
www.e-t-a.de Power Distribution System SVS15 1646 Insulated wire bridge Y 303 881 08 1 insulated wire bridge is supplied with the power distribution system. blade terminals DIN 46244-A 6.3-0.8 7010.3 2.36 12.3 terminals 13+14 bridged Signalbrücke Signal loop Germany www.e-t-a.de Signalbrücke Signal loop xxxx SB-S11-P1-01-1-1A Jumper SB-S11-P1-01-1-1A .484 .406 2.76 top view AC 240 V / DC 65 V, 1 A Accessories All dimensions without tolerances are for reference only. In the interest of improved design, performance and cost effectiveness the right to make changes in these specifications wit- hout notice is reserved.Product markings may not be exactly as the ordering codes. Errors and omissions excepted. This is a metric design and millimeter dimensions take precedence ( mm ) inch