www.e-t-a.de Power Distribution System SVS02 1646

Description

Ordering information

SVS02-08-... The E-T-A power distribution system SVS02 is designed to accommodate the electronic circuit breaker series ESS20-003 or electronic circuit protector ESX10. It distributes the current supplied by a switch mode power supply up to 40 A to 4, 8, 12 or 16 channels. Input connections are via screw terminals. The individual circuit breakers can be plugged in. Loads are connected via spring-loaded screwless terminals. The power distribution includes integral wiring of the signalisation of the individual channels which can be combined to a group signal. The SVS02 can be snapped onto a DIN symmetrical rail. Suitable for l ESS20-003 l ESX10-103 l 2210-S21 l Modular Power distribution system for short-circuit limited DC 24 V applications up to max. 40 A continuous load, max. voltage DC 32 V. l Three screw terminals (max. 10 mm2/AWG 8) for: - FE (functional earth) = X 21 FE for connecting the DC 24 V power supply max. 40 A l 5 load outputs per channel complete with Combicon screwless connectors, wiring 5 x max. 2.5 mm2 (AWG 14)/ without connector sleeve max. 8 A: - (L+S) group output (+), internally bridged across all channels - (L+L) load output (+), per channel - (-) DC 24 V (-) - (-) DC 24 V (-) - (FE) functional earth l Signal terminal (X31) for group signal complete with Combicon screwless connectors, wiring 5 x max. 2.5 mm2 (AWG 14)/ without connector sleeve, max. 0.5 A (signal contact ESS20): - (+) internal +DC 24 V supply for signalisation of terminal X 21 + via insulated jumper from (+) to (SC), protected by CB2 - (SC) external supply possible +DC 24 V for signalisation, protected by CB1 - (S0) signal output group signalisation - (-) additional output DC 24 V (-) - (FE) additional functional earth l Selective overcurrent protection CB1 and CB2 for group signalisation of the power distribution system, red LED blinks after CB1 has tripped (see schematic diagram). Reset of circuit breakers: momentarily press red actuator button l Protection class to: IP20 l Insulation co-ordination to IEC 60934: 0.5 kV / pollution degree 2 l Dielectric strength AC 500 V l Temperature range: 0...50 °C (without condensation) l for DIN symmetrical rail mounting EN 50022 - 35 x 7.5 l Dimensions: see dimensional drawing Type SVS02 Power distribution system for ESS20-003 l short circuit current limited DC 24 V applications l max. 40 A continuous load l two integral circuit breakers (CB1 and CB2): overcurrent protection of group signalisation of power distribution system, red LED glashes upon trip of CB1 l 2 insulated wire bridges Y 303 881 08 included l without jumpers SB-S11-P1-01-1-1A (for unused positions) Version, max. number of circuit breakers ESS20-003 on the power distribution system 04 4 channels (F1...F4) 08 8 channels (F1...F8) 12 12 channels (F1...F12) 16 16 channels (F1...F16) Screw terminals for power supply DC 24 V P310 3 loop-through terminals (X 21) max. 10 mm2 for DC 24 V (+) / DC 24 V (-) / FE functional earth Load outputs per channel (F1 .. Fn, n = 04, 08, 12, 16) L50 5 load outputs per channel, max. 8 A each l (L+S) group output (+) internally bridged over all channels l (L+L) protected load output (+), per channel l (-) DC 24 V (-) l (-) DC 24 V (-) l (FE) functional earth Signal outputs S15 1 signal terminal (X31) for group signal, 5-pole, complete with plug-in terminal, wiring 5 x max. 2.5 mm 2 / without connector sleeve, max. 0.5 A: l (+) internal +DC 24 V supply for signalisation via insulated wire bridge from (+) to (SC) l (SC) external supply possible +DC 24 V for signalisation l (S0) signal output group signalisation l (-) additional output DC 24 V (-) l (FE) additional functional earth Control input E00 without control input Fitting variants B10 complete with screwless spring-loaded terminals, (max. 2.5 mm 2, without connector sleeve) (standard) B20 complete with plug-in screw terminals (max. 2.5 mm2, without connector sleeve) SVS02 - 16-P310 - L50 - S15 - E00 - B10

Power Distribution System SVS02 www.e-t-a.de Power Distribution System SVS02 1646 Dimensions SVS02-16 Schematic diagram SVS02-(n) n = 04, 08, 12, 16 F1 F2 F3 F4 F5 F6 F7 F8 F9 F10F 11 F12 F13 F14F 15 F16 L+S L+L FE RESET NUR KURZ DRUECKEN ONLY PUSH BRIEFLY + - FE CB2 CB1DC 24V/40A SC FE Insulated wire bridge, not fitted (2 pcs enclosed) Rail EN 50022-35x7,5 (not supplied) 52.1 2.05 44.6 1.75 red LED blinks after CB1 has tripped 105.4 4.15 F4 = 109.5 F4 = 4.31 F8 = 171.5 F8 = 6.75 F12 = 233.5 F12 = 9.19 F16 = 295.5 F16 = 11.63 .610 15.5 screw terminals DC 24 V power supply load outputs screwless spring-loaded terminals www.e-t-a.de Typ: SVS02-16 B10 B20 X1 X2 X3 X4 X5 X6 X7 X8 X9 X10X 11 X12X 13 X14X 15 X16 X21+ X21- X21FE X31 SC SO FE X31 *) see application example for insulated wire bridge DC 24V/40A X21+ X21- X21FE FE LED V1 blinks after CB1 has tripped CB2: no visual indication CB2 CB1 3 1 3 1V2 Circuit breakers CB1 and CB2: shown in tripped condition Line (+) GND (-) SC SI LOAD (L+) ESS20-003 Line (+) GND (-) SC SI LOAD (L+) ESS20-003 Line (+) GND (-) SC SI LOAD (L+) ESS20-003 Line (+) GND (-) SC SI LOAD (L+) ESS20-003 L+S L+L FE L+S L+L FE L+S L+L FE L+S L+L FE XnX3X2X1 F1 F2 F3 Fn This is a metric design and millimeter dimensions take precedence ( mm ) inch

www.e-t-a.de Power Distribution System SVS02 1646 Power Distribution System SVS02 Dimensions SVS02-04, fitted with ESS20-003 105.4 52.1 102 (105) red LED blinks after CB1 has tripped 2.36 4.02 (4.13) Insulated wire bridge, not fitted (2 pcs enclosed) 4.15 Rail EN 50022-35x7,5 (not supplied) 2.05 SC FE CB2 CB1DC 24V/40A F1 F2 F3 F4 RESET NUR KURZ DRUECKEN ONLY PUSH BRIEFLY L+S L+L FE load outputs screwless spring-loaded terminals 109.5 screw terminals DC 24 V power supply OK OK OK OK www.e-t-a.de Typ: SVS02-04 B10 B20 X21+ X21- X21FE X31 4.31 Elektronischer Schutzschalter Electronic Supplementary Protector -003-DC24V-1A /2A X1 X2 X3 X4 d This is a metric design and millimeter dimensions take precedence ( mm ) inch

Power Distribution System SVS02 www.e-t-a.de Power Distribution System SVS02 1646 Dimensions SVS02-04, fitted with ESX10-103 Insulated wire bridge 105.4 109.5 15.5 105.4 L + S L + L FE F1 F2 F3 F4 SC SO FE DC 24V/40A X21 + X21 X21F E 2.76 4.15 4.31 .610 4.15 load outputs screwless spring-loaded terminals screw terminals power supply

www.e-t-a.de Power Distribution System SVS02 1646 Power Distribution System SVS02 blade terminals DIN 46244-A 6.3-0.8 7010.3 2.36 12.3 terminals 13+14 bridged Signalbrücke Signal loop Germanywww.e-t-a.de Signalbrücke Signal loop xxxx SB-S11-P1-01-1-1A Jumper SB-S11-P1-01-1-1A .484 .406 2.76 top view AC 240 V / DC 65 V, 1 A Application example for jumper to replace SC FE CB2 CB1DC 24V/40A X21+ F1 F2 F3 F4 RESET NUR KURZ DRUECKEN ONLY PUSH BRIEFLY L+S L+L FE OK OK OK www.e-t-a.de Typ: SVS02-04 B10B 20 X21- X21FE X31 X1 X2 X3 X4 Signalbrücke Signal loop Accessories Insulated wire bridge Y 303 881 08 Two insulated wire bridges are supplied with the power distribution system. They may be used for: - Channel X31: internal +DC 24 V supply for signalisation wire bridge from (+) to (SC) Signal circuit (+) to (SC) protected by CB2 Signal circuit (SC) to (SO) protected by CB1 - Channel X1: Protected load output (L+L) of CBE position F1 takes over protection of (L+S) terminals of all CBEs F2 up to Fn (n= 04, 08, 12, 16) Application example for insulated wire bridge Terminal X1 Protected load output (L+L) of CBE position F1 takes over protection of (L+S) terminals of all CBEs F2 up to Fn (n= 04, 08, 12, 16) Terminal X31 (group signalisation) wire bridge from (+) to (SC) internal +DC24V feed for signalisation Thus plus potential of terminal X21+ is connected to (SC) SC FE CB2 CB1DC 24V/40 F1 F2 F3 F4 RESET NUR KURZ DRUECKE Y PUSH BRIEFL L+S L+L FE OK OK OK X1 X2 X3 X4 www.e-t-a.de p: SVS02-04 X21+ X21- X21FE OK A N ONLY Ty B1 B2 X31 The signalling pathway of the group signalisation is as follows: - feed-in of +DC 24 V potential in (SC = terminal 31.2) - via in-built overcurrent protection CB1 - via all signal contacts of the fitted circuit breakers type ESS20-003 - back to signal output of group signalisation (S0 = terminal 31.3) In operating condition (i.e. all circuit breakers plugged in and functional) the signalling pathway (SC) to (S0) is closed. If the distribution rail is not completely fitted with ESS20-003, the open pathway (SC) to (S0) may be closed by means of a jumper type SB-S11-P1-01-1-1A All dimensions without tolerances are for reference only. In the interest of improved design, performance and cost effectiveness the right to make changes in these specifications without notice is reserved. Product markings may not be exactly as the ordering codes. Errors and omissions excepted. This is a metric design and millimeter dimensions take precedence ( mm ) inch

www.e-t-a.de 1646