SPP40SP1120SN EATON | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 4
Technical content
SurgePOD™ PRO UL Listed Type 1 surge protective devices Catalog symbols:
- SPP40SP_ Description: Bussmann™ series SurgePOD™ PRO Type 1 surge protective devices are suitable for installation on both the loadside or lineside of the service entrance overcurrent protective device. SurgePOD PRO SPDs are available in popular voltage and system specific versions to match common residential and light commercial electrical system and equipment requirements. They deliver superior surge protection using MOV thermal disconnect technology that eliminates the need for additional overcurrent protection. Parallel connection to the electrical system permits the SurgePOD PRO SPD to be installed on panels of any amp rating. 2011/65/EU Features:
- These SPDs are easily selected and installed on the loadside or lineside of the service entrance overcurrent protective device
- Voltage specific models precisely match and protect electrical systems and equipment better than “one-size-fits-all” SPDs
- Thermal disconnect technology eliminates the need for additional fusing
- Compact UV resistant NEMA® 4X enclosure for indoor or outdoor installation
- easyID™ LED status indicator provides surge protection status at a glance
- Two year warranty Specifications: Ratings
- See ratings and specifications tables on page 2 Agency information
- UL® Listed Type 1 1449 4th Edition
- CSA (120-480 V)
- RoHS compliant Catalog numbers Volts AC System type SPP40SP1120SN 120 Single-phase SPP40SP2240PN 240 Split-phase SPP40SP3240DLG 240 3-phase DeltaSPP40SP3480DLG 480 SPP40SP3208WYG 208 3-phase WyeSPP40SP3480WYG 480 SPP40SP3600WYG 600
SurgePOD™ PRO UL Listed Type 1 surge protective devices Eaton.com/bussmannseries SurgePOD PRO ratings and specifications: Voltages and system types Catalog number Nominal system voltage (Vac) Max. Continuous Operating Voltage AC (MCOV) (VC) System type Connection points SPP40SP1120SN 120 150 Single-phase 2 wire 2 SPP40SP2240PN 120/240 150 Split-phase 3 wire 3 SPP40SP3240DLG 240 320 Three-phase Delta 3 wire + G 4 SPP40SP3480DLG 480 550 Three-phase Delta 3 wire + G 4 SPP40SP3208WYG 208 150 Three-phase Wye 3 wire + G 4 SPP40SP3480WYG 480 320 Three-phase Wye 3 wire + G 4 Specifications For all SurgePOD PRO units Values Short Circuit Current Rating (SCCR) 200 kA Discharge current (8x20µs) Nominal In 10 kA Maximum Imax 40 kA Response time (ns) tA <25ns Frequency 50/60 Hz Operating state/fault indication Bi-color LED - green (good) / red (replace) Conductor length/gauge 18 inches, 10 AWG stranded tinned copper Mounting Chase nipple / bracket* Enclosure/flammability ratings NEMA 4X - UL 94-5VA Degree of protection (installed state) IP20 (finger-safe) SPD install location Indoor/outdoor Circuit location Lineside or loadside of service entrance overcurrent protective device Standard UL Type 1 1449 4th Edition Agency information UL Listed, CSA Certified**, RoHS compliant Warranty 2 Y ears† Operating temperature range -40°C to +65°C Maximum operating altitude 12000 ft. * Customer-supplied bracket. ** 600 V Wye version not CSA Certified. † See Bussmann series SPD limited warranty statement (3A1502) for details at www.cooperbussmann.com/Surge. Voltage Protection Ratings (VPRs) Catalog number Nominal system voltage (Vac_ MCOV (VC) (Vac) Voltage Protection Ratings (VPRs) L-N L-L L-G SPP40SP1120SN 120 150 700 — — SPP40SP2240PN 120V/240 150 700 1200 — SPP40SP3240DLG 240 320 — 2500 1200 SPP40SP3480DLG 480 550 — 3000 1800 SPP40SP3208WYG 208 150 — 1200 700 SPP40SP3480WYG 480 320 — 2500 1200 SPP40SP3600WYG* 600 420 — 2500 1500 * Not CSA Certified.
SurgePOD™ PRO UL Listed Type 1 surge protective devices Eaton.com/bussmannseries Wiring connectionsDimensions — in Mounting SurgePOD PRO is a panel mount device. It may also be mounted using a customer supplied bracket or directly onto a female threaded conduit fitting. Black White Black Black White Black Black Black Green Tighten locknut to 20.3 lb-in (2.3N•m) For NEMA 4X installation, install appropriate, customer- supplied gasket between SurgePOD™ PRO SPD and enclosure wall. 2-1/16” 2-1/16” 1-11/16” 1-11/16” 4-1/8” 3-3/16” 4-1/16” 3-3/8” 7/8” 1-1/16” Dia. L (Black) N (White) L1 (Black) L2 (Black) N (White) L1 (Black) L3 (Black) L2 (Black) GND (Green) L1 (Black) L2 (Black) L3 (Black) GND (Green) Single-phase
120 V (L-N) 2 Wire
Must be installed within 10 feet (3 m) of a bonded neutral-ground connection per IEEE C62.41-1991 . Catalog number: SPP40SP1120SN T wo-pole with Neutral (split-phase)
120 V (L-N) / 240 V (L1-L2), single-phase (split) center tap
For installations at or less than 10 feet (3 m) from the transformer. Catalog number: SPP40SP2240PN Wye + Ground 208, 480 V (L-L) 3 wire Wye + Ground Catalog numbers: SPP40SP3208WYG, SPP40SP3480WYG, SPP40SP3600WYG Black Black Black Green Delta + Ground 240, 480 V (L-L) 3 wire Delta + Ground Catalog numbers: SPP40SP3240DLG, SPP40SP3480DLG
SurgePOD™ PRO UL Listed Type 1 surge protective devices Technical Data 10033 Effective April 2018 Eaton, Bussmann, SurgePOD and easyID are valuable trademarks of Eaton in the U.S. and other countries. Y ou are not permitted to use the Eaton trademarks without prior written consent of Eaton. NEMA is a registered trademark of the National Electrical Manufacturers Association. UL is a registered trademark of the Underwriters Laboratories, Inc. Eaton
1000 Eaton Boulevard
Cleveland, OH 44122 Eaton.com Bussmann Division
114 Old State Road
Ellisville, MO 63021 United States Eaton.com/bussmannseries © 2018 Eaton All Rights Reserved Printed in USA Publication No. 10033 — BU-SB13071 April 2018 Follow us on social media to get the latest product and support information. The only controlled copy of this data sheet is the electronic read-only version located on the Eaton network drive. All other copies of this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Eaton reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Eaton also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications. easyID LED status indicator The easyID LED status indicator will illuminate when the unit is properly installed and the system or equipment being protected is energized. The following LED color/status indicates: GREEN LED = Good
- The circuit is energized and protected. RED LED = Replace
- The circuit is energized and unprotected.
- The unit needs replacing. LED is Out / Unlit:
- The circuit is most likely de-energized
- The unit’s leads are disconnected
- The unit is damaged Authorized personnel should follow all prescribed lockout/tagout and safety procedures in troubleshooting the cause for the above conditions. Opening SurgePOD PRO enclosure will void UL listing and warranty.