Switched mode power supply for DIN rail mounting type SMP11 DC24V/10A www.e-t-a.de1646 Type No. SMP11 Single phase switch-mode power supply for rail mounting Connector design L pcb mounting (preferred type) S plug-in type Terminal design 20 screw terminals Output voltage DC24V DC 24 V Output current 10 A SMP11–L20-DC24V-10A ordering example

Description

Technical data (TU = 25°C, UB = AC 100 V...240 V, I0 = 10 A) Switched mode power supply for rail mounting, wide range voltage input, high efficiency, integral active power factor compensation (PFC), parallel mode for performance improvement EN 61000-6-3, EN 61000-6-2, EN 61204-3 l Wide range voltage input from AC 88 to 264 V l Efficiency up to 93% l Integral power factor compensation l Parallel mode for performance improvement (selectable by switch) Process control, industrial switch- and controlgear, machine construction, telecommunication systems SMP11-DC24V/10A Version L20 Approvals EMC Operating data Input voltage ranges UE AC 88…264 V Operating voltage range UB AC 100...240 V Effective output 240 W Output voltage UO 24 V SELV Output current rating IO 10 A Efficiency 91 % min. / 93 % typically General data Switching frequency typically 90 kHz Insulation voltage between input and output input and protective conductor output and protective conductor AC 3000 V, DC 4242 V AC 1500 V, DC 2121 V AC 500 V, DC 710 V Insulation resistance 100 MΩ (DC 500 V) between input and output Ambient temperature -40 °C…+71°C Derating factor (see curve) 2.5 % / °C Storage temperature -40 °C…+85 °C Relative humidity 20…90 % RH MTBF to Bellcore, ed. 6 481,000 hours at 40°C, GB Max. altitude in operation to IEC 60068-2-13 5000 m above sea level Cooling by convection Mounting direction wall-mounted (see dimensions) Pollution degree 2 Input circuit Input rated voltage AC 100...240 V Input voltage range AC 88…264 V Input current 1.15 A typically at U B = AC 230 V

2.3 A typically at UB = AC 115 V

Max. input current 3.2 A typically at UB = AC 88 V Supply frequency 47...63 Hz Inrush current at AC 115 V at AC 230 V 24 A max. 48 A max. Approval authority Standards UL UL508, CSA C22.2 No. 107.1 (listed) UL 60950-1, CSAC22.2 No. 60950-1 (recognized) TÜV Rheinland EN 60950-1

Switched mode power supply for DIN rail mounting type SMP11 DC24V/10A www.e-t-a.de 1646 Dimensions GENERAL TOLERANCE 7 97 9 6 1 6 1 60 V DC/0.3 A 100-240 V AC 3.2 A 47-63Hz

24 V DC/10 A

124.50 (4.9) 124.50 (4.9) 143.50 (5.65) 60 V DC/0.3 A 100-240 V AC 3.2 A 47-63Hz (at UB 230 V, I0 10 A)

18 W typically

compensation (active) typically 0.97 Output circuit Rated voltage U

0 DC 24 V SELV

Output voltage accuracy 0…+1 % Min. load 0 % Supply regulation ± 1 % at UE min. … UE max. Load regulation Single mode Parallel mode ± 1 % ± 5 % Voltage adjustment range DC 22.5 … 28.5 V at 0.8 x I Continuous load 10 A at U0 = DC 24 V, 8.4 A at U0 = DC 28.5 V Power boost factor typically 120 % / typically 150 % - 3s, see output trip curve Short circuit behaviour Hiccup mode Exposure time 25 / 20 ms ON delay at: resistive load capacitive load of 7,000 µF 1 s 1.5 s Rise time at: resistive load capacitive load of 7,000 µF 150 ms 0.5 s Release time 150 ms Residual ripple 100 mV, spectrum = 20 MHz Power back immunity DC 35 V min. Capacitive load 7,000 µF max. Parallel mode 3 power supplies max. at 0.1 x I 0 … 0.9 x I0 Control and protection circuit Input protection internal blade fuse T5A / AC 250 V Recommended back-up fuse 1-pole MCB, e.g. E-T-A type 4230 Current rating 10 A / 16 A ➞ max. 20 A Characteristic curve B / C / D Internal overvoltage protection varistor Aux. contact (output RDY) Contact closed at: DC 17.6…19.4 V Insulation voltage Contact load at DC 500 V (to output) DC 60 V / 0.3 A Overvoltage protection 30…33 V at 0.8 x I Degree of protection IP20 Physical data Dimensions (h x w x d) version L20 with screw terminals: version S20 with removeable plug 124.5 x 64 x 123.6 mm (4.9 x 2.52 x 4.87 inches) 143.5 x 64 x 123.6 mm (5.65 x 2.52 x 4.87 inches) Housing material: metal Mass approx. 860 g Vibration (random vibration to IEC 60068-2-6) mounted on symmetrical rail, 10 - 500 Hz, 2 g, on X, Y & Z axis, per axis 10 min. / 60 min. Shock (random to IEC 60068-2-27) halfsine 4 g (22 ms), 3 axes, 6 sides, 3 times per side

Switched mode power supply for DIN rail mounting type SMP11 DC24V/10A www.e-t-a.de1646 Switched mode power supply for DIN rail mounting type SMP11 DC24V/10A V+ V+ V- V- RDY C RDY No N PE V105

10 A compact

Mounting snap onto DIN rail (TS35/7.5 or TS35/15) Ventilation / cooling normal air convection, recommended distance on each side 25 mm Mounting position wall-mounted with the input terminals pointing downwards (see dimensions) Version L20 with screw terminals: Screw terminals input terminal AWG24-10 (0.2 mm² – 4 mm²) flexible/rigid output terminal AWG24-10 (0.2 mm² – 4 mm²) flexible/rigid Tightening torque input connector 1 Nm max. Output terminal 0.6 Nm max. Wire stripping length 8 mm Version S20 with removeable plug Screw terminals input terminal AWG24-10 (0.2 mm² – 4 mm²) flexible/rigid output terminal AWG24-10 (0.2 mm² – 4 mm²) flexible/rigid Tightening torque input connector 0.5 Nm max. Output connector 0.8 Nm max. Wire stripping length 4…5 mm Pin assignment - Display - Controls pin no. name description RDY limit value DC ON, relay contact (make contact)

3.4 V + Output voltage +

5.6 V - output voltage -

7 PE earth conductor

8 N Input voltage, neutral conductor

(not polarised with DC input voltage)

9 L Input voltage, phase conductor

(not polarised with DC input voltage) DC ON visual status indication with LED DC LO DC LOW output voltage LED indication Vout Adj potentiometer for adjustment of output voltage U S/P change-over switch single / parallel mode Schematic diagram Vo+ Vo- Vout ADJ. DC ON (Green LED)Output Level Detection Error amp OVP Reference & Error Amp. Current Detection Opto- Isolation Opto- Isolation RectifierSwitching Device PWM Controller PFC Inrush Current Limiter Rectifier Filter Fuse DC LOW (Red LED) RDY (Relay Contact) Single/Parallel select L N Y

Switched mode power supply for DIN rail mounting type SMP11 DC24V/10A www.e-t-a.de 1646 Typical output trip curve Power out (%) 100 110 120 130 140 150 160 100 Output Voltage (%) Continuous For 3 sec OCP Derating curve Current-voltage curve Typical efficiency curve 100 Power out (%) -40 61 71 Temperature (°C) Safe Operating Area Efficiency (%) Power out (%) 50 75 100

230 Vac

115 Vac

current-voltage-curve ➞ short circuit current: — 10 A / Div voltage: - - - 10 V / Div time 1 s / Div. current: — 10 A / Div voltage: - - - 10 V / Div time 20 ms / Div.

Switched mode power supply for DIN rail mounting type SMP11 DC24V/10A www.e-t-a.de1646 Switched mode power supply for DIN rail mounting type SMP11 DC24V/10A N PE L1.1 N.1 X11 - E0.3E0.1E0.0 X10 X9X7 M L1 N PE V+ V+ V- V- RDY RDY C NO 4230-T110-K0CE-16A X1 X2 X3 X4 X5 X6 1 12 1 12 1 12 1 12 1 12 1 12 2 2 11 14 2 11 14 2 11 14 2 11 14 2 11 14 11 14 11 14 11 14 11 14 11 14 1 12 1 12 1 12 1 12 1 12 1 12 1 1 1 1 1 1 2 2 2 2 2 2 0,5 A 2A 2A 1A 1A 4A SMP11 12 (b) 12 (b) 12 (b) 12 (b) 12 (b) 12 (b) ETA.80PLUS-PT01 ETA.REF16-S100-DC24V-0,5A ETA.80PLUS-PT01 ETA.REF16-S101-DC24V-2A ETA.80PLUS-PT01 ETA.REF16-S101-DC24V-2A ETA.80PLUS-PT01 ETA.REF16-S101-DC24V-1A ETA.80PLUS-PT01 ETA.REF16-S101-DC24V-1A ETA.80PLUS-PT01 ETA.REF16-S124-DC24V-4A LINE+ GND LOAD+ LOAD+ Si Si LOAD+ Si Si LOAD+ Si Si LOAD+ Si Si 2.1/2.2 11(a) 14(c) 2.1/2.2 11(a) 14(c) 2.1/2.2 11(a) 14(c) 2.1/2.2 11(a) 14(c) 2.1/2.2 11(a) 14(c) 2.1/2.2 11(a) 14(c) LOAD+ RE SF +24V RE SF +24V Reset IN Status OUT LINE+ GND LINE+ GND LINE+ GND LINE+ GND LINE+ GND 2 (see catalog Circuit Breaker Thermal Magnetic Datasheet 4230-T) (see catalog electronic overcurrent protection Chapter 6) Current-voltage curve Notes for installation l The power distribution system must only be installed by qualified personnel. l Only after expert installation must the device be supplied with power. l The user has to ensure that the cable cross section complies with the applicable current rating. l The national standards (e.g. for Germany DIN VDE 0100) have to be observed for installation and selection of feed and return cables. l Recommended circuit breaker for the primary input cable protection: E-T-A type 4230 IN max. 20 A l Recommended selective overcurrent protection for the secondary output protection: E-T-A types ESS.., ESX.., und REF… l In addition special precautions must be taken in the system or machine (e.g. use of a safety PLC) which reliably prevent an automatic re-start of parts of the system (cf. Machinery Directive 2006/42/EU and EN 60204-1, Safety of Machinery). In the event of a failure (short circuit/overload) the load circuit will be disconnected by the circuit breaker/protector or the switched mode power supply. current-voltage-curve short circuit ➞ output REF16-S101-DC24V-6A current: — 2 A / Div voltage: - - - 10 V / Div time 20 ms / Div.

www.e-t-a.de 1646 All dimensions without tolerances are for reference only. E-T-A reserves the right change specifications at any time in the interest of improved design, performance and cost effectiveness, the right to make changes in these specifications without notice is reserved. Product markings may not be exactly as the ordering codes. Errors and omissions excepted.