MODEL: SML SML SPECIFICATIONS ES-6371 Rev.4 Page 1/17 http://www.m-system.co.jp/ Single Loop Controller Series REMOTE I/O MODULE (for NestBus use) Functions & Features
- Remote I/O module for the NestBus use
- Plugin hardware
- Twisted-pair cable transmission
- Removable terminal block
- Self-diagnostics
- Monitor LED provided for contact I/O modules (2.83) 142 (5.59) (3.15) mm (inch) 1234567890 RUN PWR ■ OTHER THAN SML-R2 36/ 183 (2.83) (3.15) 149 (5.87) mm (inch) ■ SML-R2 MODEL: SML–[1]-[2][3]
ORDERING INFORMATION
- Code number: SML-[1]-[2][3] Specify a code from below each [1] through [3]. (e.g. SML-A4-K) [1] I/O SECTION A4: Di 8 points C7: Do 8 points (photo MOSFET relay) C8: Do 8 points (relay) E5: Di 4 + Do 4 points (relay) G3: Ai 8 points G4: Ai 4 points M4: Ao 4 points P4: Pi 4 points R2: Ai 2 points (isolated between chs) + Ao 2 points (isolated between chs, current output) (power input code K, L not selectable) R3: Ai 4 + Ao 4 points S5: Ai 4 + Di 4 points S6: Ao 4 + Do 4 points (relay) [2] POWER INPUT AC Power M2: 100 – 240 V AC (Operational voltage range 85 – 264 V, 47 – 66 Hz) (Selectable only for SML-R2) K: 85 – 132 V AC (Operational voltage range 85 – 132 V, 50 – 60 Hz) L: 170 – 264 V AC (Operational voltage range 170 – 264 V, 50 - 60 Hz) DC Power R: 24 V DC (Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) [3] OPTIONS Lowpass Filter (only for SML-P4) blank: Without /LF: With
RELATED PRODUCTS
- Loop configuration builder software (model: SFEW3E) Builder software downloadable at M-System’s web site. A dedicated cable is required to connect the module to the PC. Please refer to the users manual for the Builder software for applicable cable types. GENERAL SPECIFICATIONS Construction: Plug-in Connection I/O signal, Power input: M3.5 screw terminals (torque 0.8 N·m) NestBus, RUN contact output: Euro type connector terminal Applicable wire size: 0.2 to 2.5 mm2, stripped length 7 mm Screw terminal: Chromated steel Housing material: Flame-resistant resin (black) Isolation: I/O selection codes other than R2: NestBus to I/O to RUN contact output to power to FG R2: NestBus to input 1 to input 2 to output 1 to output 2 to RUN contact output to power to FG Power indicator: Red LED turns on when power is supplied. RUN indicator: Red LED turns on when data are transmitted to the NestBus. ■ RUN Output: Contact opens in an abnormality.
MODEL: SML SML SPECIFICATIONS ES-6371 Rev.4 Page 2/17 http://www.m-system.co.jp/ Rating: 100 V AC @ 0.5A (cos ø = 1) 30 V DC @ 0.5 A (resistive load) Maximum switching voltage: 250 V AC or 220 V DC Maximum switching power: 62.5 VA or 60 W Minimum load: 10 mV DC @ 1 mA Mechanical life: 5 x 107 cycles NestBus Configuration: Bus type multi-drop Standard: Conforms to TIA/EIA-485-A Transfer rate: 19.2 kbps Protocol: NestBus (M-System’s own protocol) Max. transmission distance: 1 kilometer Transmission media: Shielded twisted-pair cable (CPEV-S 0.9 dia.) Terminating resistor: Incorporated Card No. adjustment: Rotary switch; 0 - F (16) INSTALLATION Power consumption
- AC I/O selection codes other than R2: Approx. 3 VA R2: Approx. 5 VA at 100 V AC Approx. 7 VA at 200 V AC Approx. 8 VA at 264 V AC
- DC: Approx. 3 W (125 mA) Operating temperature: -5 to +55°C (23 to 131°F) Operating humidity: 30 to 90 %RH (non-condensing) Mounting: Surface or DIN rail Work area: 170 mm (6.7") min. from the mounting surface required Weight I/O selection codes other than R2: Approx. 400 g (0.88 lb) R2: Approx. 500 g (1.10 lb) PERFORMANCE Permissible power failure duration: ≤ 20 ms Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength I/O selection codes other than R2: 1500 V AC @ 1 minute (NestBus to I/O to RUN contact output to power to FG) R2: 1500 V AC @ 1 minute (NestBus to input 1 to input 2 to output 1 to output 2 to RUN contact output to power to FG)
MODEL: SML SML SPECIFICATIONS ES-6371 Rev.4 Page 3/17 http://www.m-system.co.jp/ EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch) 80 (3.15) 50 (1.97) 80 (3.15) (.79) 60 (2.36) 72 (2.83) 7.8 (.31) CLAMP (top & bottom) DIN RAIL 35mm wide 2–4.5 (.18) dia. MTG HOLE 25 (.98) deep 14–M3.5 SCREW
- When mounting, no extra space is needed between units. 12 5614 11 110 15 103 (4.06) min. (.39) ■ OTHER THAN SML-R2 80 (3.15) 109 (4.29) [3.3 (.13)] (.79) (top & bottom) CLAMP DIN RAIL 35mm wide 2–4.5 (.18) dia. MTG HOLE 25 (.98) deep 14–M3.5 SCREW 7.8 (.31) 80 (3.15) 60 (2.36) 72 (2.83)
- When mounting, no extra space is needed between units. (.39) min. ■ SML-R2
MODEL: SML SML SPECIFICATIONS ES-6371 Rev.4 Page 4/17 http://www.m-system.co.jp/ SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM Isolation Base Socket Nest Bus Comm. Circuit Control Circuit U(+) V(–) POWER Ry GROUND FG I / O RUN CONTACT OUTPUT Shielded Twisted-pair Cable To Other Nest Bus Devices Jumper Pin* TERMINATOR CARD NO. SET SW RUN LED *When the device is located at the end of a transmission line via twisted-pair cable (when there is no cross-wiring), close across the terminal T2 – T3 with the attached jumper pin (or with a leadwire). When the device is not at the end, remove the jumper pin. For cross-wiring, use the terminal T1, T2 and T4.
MODEL: SML SML SPECIFICATIONS ES-6371 Rev.4 Page 5/17 http://www.m-system.co.jp/ CONTACT INPUT MODULE (Di 8 points) MODEL: SML–A4–[1]
- Code number: SML-A4-[1] Specify a code from below for [1]. (e.g. SML-A4-K) [1] POWER INPUT AC Power K: 85 – 132 V AC L: 170 – 264 V AC DC Power R: 24 V DC GENERAL SPECIFICATIONS Connection: M3.5 screw terminals Isolation: NestBus to input to RUN contact output to power to FG Input status indicator LED: Red LEDs assigned to each channel INPUT SPECIFICATIONS ■ Contact Input Input: Dry contact, 8 points Commons: All negatives Sensing: 24 V DC ON current/resistance: 3 mA min., 1 kΩ max. OFF current/resistance: 1 mA max., 50 kΩ min. EXTERNAL VIEW PWR RUN Input Status Indicator LEDs Card No. Set SW Modular Jack Euro Type Connector Terminal Run Indicator LED Jumper Pin Power Indicator LED TERMINAL CONNECTION (INPUT) Base Socket COM(–) Di 6 Di 7 Di 8 Di 5 COM(–) Di 4 Di 3 Di 2 Di 1 24V Italic figures indicate LED No. on the front panel.
MODEL: SML SML SPECIFICATIONS ES-6371 Rev.4 Page 6/17 http://www.m-system.co.jp/ CONTACT OUTPUT MODULE (Do 8 points (photo MOSFET relay)) MODEL: SML-C7–[1]
- Code number: SML-C7-[1] Specify a code from below for [1]. (e.g. SML-C7-K) [1] POWER INPUT AC Power K: 85 – 132 V AC L: 170 – 264 V AC DC Power R: 24 V DC GENERAL SPECIFICATIONS Connection: M3.5 screw terminals Isolation: NestBus to output to RUN contact output to power to FG Output status indicator LED: Red LEDs assigned to each channel OUTPUT SPECIFICATIONS ■ Contact Output Output: Photo MOSFET relay, 8 points Commons: All negatives Rating: 125 V AC/DC @ 50 mA (resistive load) Maximum ON resistance: 50 Ω EXTERNAL VIEW PWR RUN Output Status Indicator LEDs Card No. Set SW Modular Jack Run Indicator LED Jumper Pin Power Indicator LED Euro Type Connector Terminal TERMINAL CONNECTION (OUTPUT) Base Socket Do 6 Do 8 COM2(–) Do 5 COM1(–) Do 7 Do 4 Do 3 Do 2 Do 1 Italic figures indicate LED No. on the front panel.
MODEL: SML SML SPECIFICATIONS ES-6371 Rev.4 Page 7/17 http://www.m-system.co.jp/ CONTACT OUTPUT MODULE (Do 8 points (relay)) MODEL: SML-C8–[1]
- Code number: SML-C8-[1] Specify a code from below for [1]. (e.g. SML-C8-K) [1] POWER INPUT AC Power K: 85 – 132 V AC L: 170 – 264 V AC DC Power R: 24 V DC GENERAL SPECIFICATIONS Connection: M3.5 screw terminals Isolation: NestBus to output to RUN contact output to power to FG Output status indicator LED: Red LEDs assigned to each channel OUTPUT SPECIFICATIONS ■ Contact output Output: Relay contact, 8 points Commons: 1 common per 4 points Rating: 100 V AC @ 0.5 A (cos ø = 1) 30 V DC @ 0.5 A (resistive load) Maximum switching voltage: 250 V AC or 220 V DC Maximum switching power: 62.5 VA or 60 W Minimum load: 10 mV DC @ 1 mA Mechanical life: 5 × 107 cycles EXTERNAL VIEW PWR RUN Output Status Indicator LEDs Card No. Set SW Modular Jack Run Indicator LED Jumper Pin Power Indicator LED Euro Type Connector Terminal TERMINAL CONNECTION (OUTPUT) Base Socket Do 6 Do 7 Do 8
15 COM2
Italic figures indicate LED No. on the front panel.
MODEL: SML SML SPECIFICATIONS ES-6371 Rev.4 Page 8/17 http://www.m-system.co.jp/ CONTACT I/O MODULE (Di 4 + Do 4 points (relay)) MODEL: SML-E5–[1]
- Code number: SML-E5-[1] Specify a code from below for [1]. (e.g. SML-E5-K) [1] POWER INPUT AC Power K: 85 – 132 V AC L: 170 – 264 V AC DC Power R: 24 V DC GENERAL SPECIFICATIONS Connection: M3.5 screw terminals Isolation: NestBus to I/O to RUN contact output to power to FG I/O status indicator LED: Red LEDs assigned to each channel (No. 1 – 4 for input, 5 – 8 for output) INPUT SPECIFICATIONS ■ Contact Input Input: Dry contact, 4 points Commons: All negatives Sensing: 24 V DC ON current/resistance: 3 mA min., 1 kΩ max. OFF current/resistance: 1 mA max., 50 kΩ min. OUTPUT SPECIFICATIONS ■ Contact Output Output: Relay contact, 4 points Commons: 1 common per 4 points Rating: 100 V AC @ 0.5 A (cos ø = 1) 30 V DC @ 0.5 A (resistive load) Maximum switching voltage: 250 V AC or 220 V DC Maximum switching power: 62.5 VA or 60 W Minimum load: 10 mV DC @ 1 mA Mechanical life: 5 × 107 cycles EXTERNAL VIEW PWR RUN I/O Status Indicator LEDs Card No. Set SW Modular Jack Run Indicator LED Jumper Pin Power Indicator LED Euro Type Connector Terminal I/O TERMINAL CONNECTION Base Socket COM2 Do 2 Do 3 Do 4 Do 1 COM1(–) Di 4 Di 3 Di 2 Di 1 24V Italic figures indicate LED No. on the front panel.
MODEL: SML SML SPECIFICATIONS ES-6371 Rev.4 Page 9/17 http://www.m-system.co.jp/ ANALOG INPUT MODULE (Ai 8 points) MODEL: SML–G3–[1]
- Code number: SML-G3-[1] Specify a code from below for [1]. (e.g. SML-G3-K) [1] POWER INPUT AC Power K: 85 – 132 V AC L: 170 – 264 V AC DC Power R: 24 V DC GENERAL SPECIFICATIONS Connection: M3.5 screw terminals Isolation: NestBus to input to RUN contact output to power to FG INPUT SPECIFICATIONS ■ Analog Input Input: DC voltage, 8 points Operational range: 0.5 – 5.5 V DC (1 – 5 V DC) Commons: All negatives Input resistance: 1 MΩ minimum PERFORMANCE in percentage of span A/D conversion: ±0.1 % Temp. coefficient: ±0.015 %/°C (±0.008 %/°F) EXTERNAL VIEW PWR RUN Card No. Set SW Modular Jack Euro Type Connector Terminal Run Indicator LED Jumper Pin Power Indicator LED TERMINAL CONNECTION (INPUT) Base Socket Ai 7 Ai 6 Ai 8 COM(–) Ai 5 COM(–) Ai 4 Ai 3 Ai 2 Ai 1
MODEL: SML SML SPECIFICATIONS ES-6371 Rev.4 Page 10/17 http://www.m-system.co.jp/ ANALOG INPUT MODULE (Ai 4 points) MODEL: SML–G4–[1]
- Code number: SML-G4-[1] Specify a code from below for [1]. (e.g. SML-G4-K) [1] POWER INPUT AC Power K: 85 – 132 V AC L: 170 – 264 V AC DC Power R: 24 V DC GENERAL SPECIFICATIONS Connection: M3.5 screw terminals Isolation: NestBus to input to RUN contact output to power to FG INPUT SPECIFICATIONS ■ Analog Input Input: DC voltage, 4 points Operational range: 0.5 – 5.5 V DC (1 – 5 V DC) Commons: All negatives Input resistance: 1 MΩ minimum PERFORMANCE in percentage of span A/D conversion: ±0.1 % Temp. coefficient: ±0.015 %/°C (±0.008 %/°F) EXTERNAL VIEW PWR RUN Card No. Set SW Modular Jack Euro Type Connector Terminal Run Indicator LED Jumper Pin Power Indicator LED TERMINAL CONNECTION (INPUT) Base Socket COM(–) Ai 4 Ai 3 Ai 2 Ai 1
MODEL: SML SML SPECIFICATIONS ES-6371 Rev.4 Page 11/17 http://www.m-system.co.jp/ ANALOG OUTPUT MODULE (Ao 4 points) MODEL: SML–M4–[1]
- Code number: SML-M4-[1] Specify a code from below for [1]. (e.g. SML-M4-K) [1] POWER INPUT AC Power K: 85 – 132 V AC L: 170 – 264 V AC DC Power R: 24 V DC GENERAL SPECIFICATIONS Connection: M3.5 screw terminals Isolation: NestBus to output to RUN contact output to power to FG OUTPUT SPECIFICATIONS ■ Analog Output Output: DC voltage, 4 points Operational range: 0.5 – 5.5 V DC (1 – 5 V DC) Commons: All negatives Load resistance: 10 kΩ minimum PERFORMANCE in percentage of span D/A conversion: ±0.1 % Temp. coefficient: ±0.015 %/°C (±0.008 %/°F) EXTERNAL VIEW PWR RUN Card No. Set SW Modular Jack Euro Type Connector Terminal Run Indicator LED Jumper Pin Power Indicator LED TERMINAL CONNECTION (OUTPUT) Base Socket COM(–) Ao 4 Ao 3 Ao 2 Ao 1
MODEL: SML SML SPECIFICATIONS ES-6371 Rev.4 Page 12/17 http://www.m-system.co.jp/ PULSE INPUT MODULE (Pi 4 points) MODEL: SML–P4–[1][2]
- Code number: SML-P4-[1][2] Specify a code from below each [1] and [2]. (e.g. SML-P4-K/LF) [1] POWER INPUT AC Power K: 85 – 132 V AC L: 170 – 264 V AC DC Power R: 24 V DC [2] OPTIONS Lowpass Filter blank: Without /LF: With GENERAL SPECIFICATIONS Connection: M3.5 screw terminals Isolation: NestBus to input to RUN contact output to power to FG Input status indicator LED: Red LEDs assigned to each channel INPUT SPECIFICATIONS ■ Pulse Input Input: open collector, 4 points Commons: All negatives Frequency range: 0 – 10 kHz (without lowpass filter) 0 - 10 Hz (with lowpass filter) Pulse width time requirement: 50 μsec.(without lowpass filter) 60 msec.(with lowpass filter) Sensing: 24V DC ON current/resistance: 3mA min., 1 kΩ max. OFF current/resistance: 1mA max., 50 kΩ min. Counter: 0 – 9999 (reset to zero with overflow) EXTERNAL VIEW PWR RUN Input Status Indicator LEDs Card No. Set SW Modular JackRun Indicator LED Jumper Pin Power Indicator LED Euro Type Connector Terminal TERMINAL CONNECTION (INPUT) Base Socket COM(–) Pi 4 Pi 3 Pi 2 Pi 1 24V Italic figures indicate LED No. on the front panel.
MODEL: SML SML SPECIFICATIONS ES-6371 Rev.4 Page 13/17 http://www.m-system.co.jp/ ANALOG I/O MODULE (Ai 2 points (isolated between chs) + Ao 2 points (isolated between chs, current output) MODEL: SML–R2–[1]
- Code number: SML-R2-[1] Specify a code from below for [1]. (e.g. SML-R2-M2) [1] POWER INPUT AC Power M2: 100 – 240 V AC DC Power R: 24 V DC GENERAL SPECIFICATIONS Connection: M3.5 screw terminals Isolation: NestBus to input 1 to input 2 to output 1 to output 2 to RUN contact output to power to FG INPUT SPECIFICATIONS ■ Analog Input Input: DC voltage, 2 points (isolated between chs) Operational range: 0.5 – 5.5 V DC (1 – 5 V DC) Input resistance: ≥ 1 MΩ OUTPUT SPECIFICATIONS ■ Analog Output Output: DC Current, 2 points (isolated between chs) Operational range: 3.2 – 20.8 mA DC (4 - 20 mA DC) Load resistance: ≤ 300 Ω PERFORMANCE in percentage of span A/D conversion: ±0.1 % D/A conversion: ±0.1 % Temp. coefficient: Output: ±0.015%/°C (±0.008%/°F) EXTERNAL VIEW PWR RUN Card No. Set SW Modular Jack Euro Type Connector Terminal Run Indicator LED Jumper Pin Power Indicator LED I/O TERMINAL CONNECTION
1 Ao 1 (+)
Ai 2 (–) Ai 2 (+) Ai 1 (–) Ai 1 (+) Ao 2 (–) Ao 2 (+) Ao 1 (–) Base Socket Enclosing broken lines indicate insulation sections.
MODEL: SML SML SPECIFICATIONS ES-6371 Rev.4 Page 14/17 http://www.m-system.co.jp/ ANALOG I/O MODULE (Ai 4 + Ao 4 points) MODEL: SML–R3–[1]
- Code number: SML-R3-[1] Specify a code from below for [1]. (e.g. SML-R3-K) [1] POWER INPUT AC Power K: 85 – 132 V AC L: 170 – 264 V AC DC Power R: 24 V DC GENERAL SPECIFICATIONS Connection: M3.5 screw terminals Isolation: NestBus to I/O to RUN contact output to power to FG INPUT SPECIFICATIONS ■ Analog Input Input: DC voltage, 4 points Operational range: 0.5 – 5.5 V DC (1 – 5 V DC) Commons: All negatives Input resistance: 1 MΩ minimum OUTPUT SPECIFICATIONS ■ Analog Output Output: DC voltage, 4 points Operational range: 0.5 – 5.5 V DC (1 – 5 V DC) Commons: All negatives Load resistance: 10 kΩ minimum PERFORMANCE in percentage of span A/D conversion: ±0.1 % D/A conversion: ±0.1 % Temp. coefficient: Output: ±0.015%/°C (±0.008%/°F) EXTERNAL VIEW PWR RUN Card No. Set SW Modular Jack Euro Type Connector Terminal Run Indicator LED Jumper Pin Power Indicator LED I/O TERMINAL CONNECTION Base Socket Ao 3 Ao 2 Ao 4 COM(–)
3 Ao 1
COM(–) Ai 4 Ai 3 Ai 2 Ai 1
MODEL: SML SML SPECIFICATIONS ES-6371 Rev.4 Page 15/17 http://www.m-system.co.jp/ ANALOG & CONTACT INPUT MODULE (Ai 4 + Di 4 points) MODEL: SML-S5–[1]
- Code number: SML-S5-[1] Specify a code from below for [1]. (e.g. SML-S5-K) [1] POWER INPUT AC Power K: 85 – 132 V AC L: 170 – 264 V AC DC Power R: 24 V DC GENERAL SPECIFICATIONS Connection: M3.5 screw terminals Isolation: NestBus to input to RUN contact output to power to FG Input status indicator LED: Red LEDs assigned to each contact channel (No. 1 – 4 for input) INPUT SPECIFICATIONS ■ Analog Input Input: DC voltage, 4 points Operational range: 0.5 – 5.5 V DC (1 – 5 V DC) Commons: All negatives Input resistance: 1 MΩ minimum ■ Contact Input Input: Dry contact, 4 points Commons: All negatives Sensing: 24 V DC ON current/resistance: 3 mA min., 1 kΩ max. OFF current/resistance: 1 mA max., 50 kΩ min. PERFORMANCE in percentage of span A/D conversion: ±0.1 % Temp. coefficient: ±0.015 %/°C (±0.008 %/°F) EXTERNAL VIEW PWR RUN Input Status Indicator LEDs Card No. Set SW Modular Jack Euro Type Connector Terminal Run Indicator LED Jumper Pin Power Indicator LED TERMINAL CONNECTION (INPUT) COM1(–) 24V Base Socket COM2(–) Di 2 Di 3 Di 4
3 Di 1
Italic figures indicate LED No. on the front panel.
MODEL: SML SML SPECIFICATIONS ES-6371 Rev.4 Page 16/17 http://www.m-system.co.jp/ ANALOG & CONTACT OUTPUT MODULE (Ao 4 + Do 4 points (relay)) MODEL: SML-S6–[1]
- Code number: SML-S6-[1] Specify a code from below for [1]. (e.g. SML-S6-K) [1] POWER INPUT AC Power K: 85 – 132 V AC L: 170 – 264 V AC DC Power R: 24 V DC GENERAL SPECIFICATIONS Connection: M3.5 screw terminals Isolation: NestBus to output to RUN contact output to power to FG Output status indicator LED: Red LEDs assigned to each contact channel (No. 1 – 4 for output) OUTPUT SPECIFICATIONS ■ Analog Output Output: DC voltage, 4 points Operational range: 0.5 – 5.5 V DC (1 – 5 V DC) Commons: All negatives Load resistance: 10 kΩ minimum ■ Contact Output Output: Relay contact, 4 points Commons: 1 common per 4 points Rating: 100 V AC @ 0.5 A (cos ø = 1) 30 V DC @ 0.5 A (resistive load) Maximum switching voltage: 250 V AC or 220 V DC Maximum switching power: 62.5 VA or 60 W Minimum load: 10 mV DC @ 1 mA Mechanical life: 5 × 107 cycles PERFORMANCE in percentage of span D/A conversion: ±0.1 % Temp. coefficient: ±0.015 %/°C (±0.008 %/°F) EXTERNAL VIEW PWR RUN Output Status Indicator LEDs Card No. Set SW Modular Jack Euro Type Connector Terminal Run Indicator LED Jumper Pin Power Indicator LED TERMINAL CONNECTION (OUTPUT) COM1(–) Base Socket COM2 Do 2 Do 3 Do 4 Do 1 Ao 4 Ao 3 Ao 2 Ao 1 Italic figures indicate LED No. on the front panel.
MODEL: SML SML SPECIFICATIONS ES-6371 Rev.4 Page 17/17 http://www.m-system.co.jp/ Specifications are subject to change without notice.