SL30 BANNER | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 4
Technical content
- An easy-to-use self-contained opposed-mode sensor pair in a rugged U-shaped housing
- Easy and economical to mount
- Molded-in beam guides simplify mounting and beam placement
- 30 mm slot width for a wide variety of sensing applications
- Applications include label detection, hole detection, gear tooth detection, edge guiding and counting
- 10 V dc to 30 V dc operation
- Bipolar PNP/NPN outputs
- Visible red beam
- Choose 1 millisecond or 300 microsecond response
- 4-turn potentiometer sensitivity adjustment
- 2 mm effective beam
- Dark or light operate
- Choose integral, unterminated cable or QD models WARNING: Not To Be Used for Personnel Protection Never use this device as a sensing device for personnel protection. Doing so could lead to serious injury or death. This device does not include the self-checking redundant circuitry necessary to allow its use in personnel safety applications. A sensor failure or malfunction can cause either an energized or de-energized sensor output condition. Models Models Sensing Beam Slot Width Cable1 Supply Voltage Output Type Response Repeatability SL30VB6V Visible red, 680 nm 30 mm (1.2 in) 2 m (6.5 ft) 5-wire cable
10 V dc to 30
glance the position of the beam, simplifying installation placement. Figure 1. Features
23 February 2018
Figure 2. Typical Applications Connect the gray wire to +V (10 V dc to 30 V dc) for Dark Operate; and to dc common (or open) for Light Operate. See wiring diagrams. *For Dark operate, connect gray wire to + (brown). For Light operate, connect gray wire to - (blue). Note: Quick disconnect (QD) wiring diagrams are functionally identical. Adjust the sensitivity by turning the 4-turn clutched Sensitivity potentiometer with a small slotted screwdriver.
- Apply power to the sensor.
- Turn the potentiometer fully counter-clockwise, 4 full turns or more to set the sensor to the minimum sensitivity.
- Present the Light condition.
If the amber Signal Condition indicator is ON, that is the Light condition sensitivity position. If not, proceed to the next step.
- Turn the potentiometer clockwise, just until the amber Signal Condition indicator turns ON and note the position of the potentiometer.
- Present the Dark condition.
- Turn the potentiometer clockwise, just until the amber Signal Condition indicator turns ON, and note the position of the potentiometer.
- For maximum reliability, the difference between these two positions should be at least one full turn. Set the sensitivity midway between the
two positions for best sensing results. indicator comes ON solidly. If this does not occur, investigate other sensing alternatives.
Supply Voltage and Current 10 to 30V dc, 30 mA Supply Protection Circuitry Protected against reverse polarity and transient voltages Output Configuration Bipolar: NPN and PNP Output Rating 150 mA, each output Output Protection Circuitry Protected against output short-circuit and false pulse on power up Output Response Time 1 millisecond or 300 microseconds, depending on model Repeatability 250 microseconds or 75 microseconds, depending on model Adjustments 4-turn clutched potentiometer sensitivity adjustment Slot Opening 30 mm (1.2 in) wide x 45 mm (1.8 in) deep overall; beam set in 10 mm (0.4 in) from outer edge Indicators Green: Power on/off indicator Amber: Signal condition indicator Construction Housing: ABS/polycarbonate blend Optic windows: acrylic Connections 2 m (6.5 ft) or 9 m (30 ft) 5-conductor PVC-jacketed attached cable or 5-pin Euro-style quick-disconnect (QD) connector Environmental Rating IEC IP67; NEMA 6 Operating Conditions 90% at +50 °C maximum relative humidity (non-condensing) Required Overcurrent Protection WARNING: Electrical connections must be made by qualified personnel in accordance with local and national electrical codes and regulations. Overcurrent protection is required to be provided by end product application per the supplied table. Overcurrent protection may be provided with external fusing or via Current Limiting, Class 2 Power Supply. Supply wiring leads < 24 AWG shall not be spliced. For additional product support, go to www.bannerengineering.com. Supply Wiring (AWG) Required Overcurrent Protection (Amps) 20 5.0 22 3.0 24 2.0 26 1.0 28 0.8 30 0.5 Certifications E224071 Dimensions M12 x 1 Signal LED (Amber) Power LED (Green) 20.2 mm (0.80") 18.8 mm(0.74") 6.0 mm(0.24") 10.9 mm(0.43") 10.0 mm(0.39) 30.2 mm(1.19") 45.0 mm(1.77") 72.0 mm(2.84") 40.0 mm(1.58") 52.0 mm(2.05") All measurements are listed in millimeters [inches], unless noted otherwise. SL30 Series Slot Sensor P/N 56407 Rev. D www.bannerengineering.com - Tel: +1-763-544-3164 3
5-Pin Threaded M12/Euro-Style Cordsets—Single Ended Model Length Style Dimensions Pinout (Female) MQDC1-501.5 0.50 m (1.5 ft) Straight 44 Typ. ø 14.5 M12 x 1 2 1 = Brown 2 = White 3 = Blue 4 = Black 5 = Gray MQDC1-506 1.83 m (6 ft) MQDC1-515 4.57 m (15 ft) MQDC1-530 9.14 m (30 ft) MQDC1-506RA 1.83 m (6 ft) Right-Angle 32 Typ.[1.26"] 30 Typ.[1.18"] ø 14.5 [0.57"] M12 x 1 MQDC1-515RA 4.57 m (15 ft) MQDC1-530RA 9.14 m (30 ft) Brackets SMBSL
- Angled bracket
- 304 stainless steel
- Hardware included 6 X Ø5.541 Banner Engineering Corp. Limited Warranty Banner Engineering Corp. warrants its products to be free from defects in material and workmanship for one year following the date of shipment. Banner Engineering Corp. will repair or replace, free of charge, any product of its manufacture which, at the time it is returned to the factory, is found to have been defective during the warranty period. This warranty does not cover damage or liability for misuse, abuse, or the improper application or installation of the Banner product. THIS LIMITED WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER EXPRESS OR IMPLIED (INCLUDING, WITHOUT LIMITATION, ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE), AND WHETHER ARISING UNDER COURSE OF PERFORMANCE, COURSE OF DEALING OR TRADE USAGE. This Warranty is exclusive and limited to repair or, at the discretion of Banner Engineering Corp., replacement. IN NO EVENT SHALL BANNER ENGINEERING CORP. BE LIABLE TO BUYER OR ANY OTHER PERSON OR ENTITY FOR ANY EXTRA COSTS, EXPENSES, LOSSES, LOSS OF PROFITS, OR ANY INCIDENTAL, CONSEQUENTIAL OR SPECIAL DAMAGES RESULTING FROM ANY PRODUCT DEFECT OR FROM THE USE OR INABILITY TO USE THE PRODUCT, WHETHER ARISING IN CONTRACT OR WARRANTY, STATUTE, TORT, STRICT LIABILITY, NEGLIGENCE, OR OTHERWISE. Banner Engineering Corp. reserves the right to change, modify or improve the design of the product without assuming any obligations or liabilities relating to any product previously manufactured by Banner Engineering Corp. Any misuse, abuse, or improper application or installation of this product or use of the product for personal protection applications when the product is identified as not intended for such purposes will void the product warranty. Any modifications to this product without prior express approval by Banner Engineering Corp will void the product warranties. All specifications published in this document are subject to change; Banner reserves the right to modify product specifications or update documentation at any time. Specifications and product information in English supersede that which is provided in any other language. For the most recent version of any documentation, refer to: www.bannerengineering.com. SL30 Series Slot Sensor © Banner Engineering Corp. All rights reserved