SFB0320-230-12 TALEMA | Alldatasheet

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 1

Technical content

Ireland: Int.+35 374-954 8666 • Germany: Int.+4989-841 00-0 • Czech Rep: Int.+420 377 - 338 351 • Indi a: Int.+91 427-244 1325 Datasheet :: Control Panel Transformers :: 320VA Nuvotem Talema Part Number Primary V prim [V] Full Load V sec [V] Rated Current Per Sec [A] No Load Vsec [V] SFB0320-230-12 230 12-0-12 13.333 13.12-0-13.12 SFB0320-230-24 230 24-0-24 6.667 25.95-0-25.95 SFB0320-230-55 230 55-0-55 2.909 59.07-0-59.07 SFB0320-400-12 400 12-0-12 13.333 13.12-0-13.12 SFB0320-400-24 400 24-0-24 6.667 25.95-0-25.95 SFB0320-400-55 400 55-0-55 2.909 59.07-0-59.07 Temperature Class : Winding Wire (Primary & Secondary) Class H (180° C) Insulation between windings Class B (130° C) Connection lead insulation Class A (105° C) Standards: Designed and manufactured to conform to the requirements of : EN61558 Class II, Non-Short-Circuit-Proof EN60065 Class II (IEC65) EN60950 Class II VDE0550 Class II VDE0551 Class II BS415 Class II Physcial Data Dimensions (L x W x H) 117 x 82 x 120mm Mounting Holes (X x Y) 96 x 43mm between centres Approximate Weight 2.50 Kg Terminations Screw terminals suitable for conductors 0.5mm² to 4mm², rated at 16A (VDE0551) Material : Polyamide 6/6 (PA 6/6), Meets requirements of VBG4 and VDE0106, part 100, “Finger Safety Guard” VDE0470, Part 1 Note : Items marked have two terminals for secondary 0V, due to high current. Vsec Vsec Vprim 0V Blue Brown Red Black Red Primary 0 – V prim ±10%, 50-60Hz Secondary V sec –0–Vsec , @ 160VA Each (Centre-Tapped winding)