SDN-P SOLAHD | Alldatasheet
Document overview
- Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
- PDF pages: 6
Technical content
Features
- Power Factor Correction (per EN61000-3-2)
- Auto Select 115/230 Vac, 50/60 Hz Input
- Single Phase models meet SEMI F47 Sag Immunity
- Class 1, Zone 2 Hazardous Locations – ATEX approval on 2.5 through 10A, 24 Vdc Single Phase Models – ATEX approval pending on 12 Vdc and 48 Vdc single phase models
- Improved metal mounting clip
- DC OK Signal
- Adjustable Voltage
- SDN10-24-100P New Compact width (3.26”)
- Parallel Capability standard on all units
- Industrial grade design – -10°C to 60°C operation without derating. Indefinite short circuit, overvoltage and overtemperature protection. – Powers high inrush loads without shutdown or foldback – Rugged metal case and DIN connector
- SDN2.5-24-100P and SDN4-24-100LP meet NEC Class 2
- Narrow width on rail for space critical applications
- User-friendly front panel – Large, rugged, accessible, multiple connection screw terminations – Easy installation
- Broad range of product to fit almost any application – 2.5 A through 40 A, 24 Vdc
- Single and three phase inputs available
- 12 Vdc and 48 Vdc single phase models available
- Highly efficient >90% switching technology
- High MTBF and reliability
- RoHS compliant
Related Products
- SDP™ Series
- SFL Series
- SCP Series
- SCL Series
- SDU UPS
Applications
- Industrial/Machine Control
- Process Control
- Conveying Equipment
- Material Handling
- Vending Machines
- Packaging Equipment
- DeviceNet TM
- Amusement Park Equipment
- Semiconductor Fabrication Equipment Accessories
- Chassis Mount Bracket (SDN-PMBRK2)
Visit our website at www.solahd.com or contact Technical Services at (800) 377-4384 with any questions. 107 4Power Supplies SDN-P Specifications (Single Phase), 24 Vdc Output
Description
SDN 2.5-24-100P SDN 4-24-100LP SDN 5-24-100P SDN 10-24-100P SDN 20-24-100P Input Nominal Voltage 115/230 Vac auto select -AC Range 85-132/176-264 Vac -DC Range1 90-375 Vdc 210-375 Vdc N/A -Frequency 47 - 63 Hz -Inrush current max. typ. < 25 A typ. < 20 A typ. < 40 A Power Factor Correction Units Fulfill EN61000-3-2 Output Nominal Voltage 24 Vdc (22.5 - 28.5 Vdc adj.)
24 Vdc
(22.5 - 25.5 Vdc adj.) (22.5 - 28.5 Vdc adj.) -Tolerance < ±2% overall (combination Line, load, time and temperature related changes) -Ripple4 < 50 mVpp Overvoltage Protection > 30 Vdc, but < 33 Vdc, auto recovery Nominal Current 2.5 A (60 W) 3.8 A (92 W) 5 A (120 W) 10 A (240 W) 20 A (480 W) -Current Limit Fold Forward (Current rises, voltage drops to maintain constant power during overload up to max peak current) Holdup Time5 > 50 ms > 100 ms Parallel Operation Single or Parallel use is selectable via Front Panel Switch (SDN 2.5, 4 should not be used in parallel as Class 2 rating would be violated.) General EMC: -Emissions EN61000-6-3, -4; Class B EN55011, EN55022 Radiated and Conducted including Annex A. -Immunity EN61000-6-1, -2; EN61000-4-2 Level 4, EN61000-4-3 Level 3; EN61000-4-6 Level 3; EN61000-4-4 Level 4 input and Level 3 output; EN61000-4-5 Isolation Class 4, EN61000-4-11; Approvals EN60950; UL508 Listed, cULus; UL60950, cRUus, CE (LVD 73/23 & 93/68/EEC). EN61000-3-2, IEC60079-15 (Class 1, Zone 2, Hazardous Location, Groups A, B, C, D w/ T3A temp class up to 60°C Ambient.) SEMI F47 Sag Immunity. SDN 2.5 & SDN 4 - UL60950 testing to include approval as Class 2 power supply in accordance with UL1310. Temperature Storage: -25 oC...+85oC Operation. -10°-60oC full power with operation to 70°C possible with a linear derating to half power from 60oC to 70oC (Con- vection cooling, no forced air required). Operation up to 50% load permissible with sideways or front side up mounting orientation. Humidity The relative humidity is < 90% RH, noncondensing; IEC 68-2-2, 68-2-3. MTBF: > 820,000 hours > 640,000 hours > 600,000 hours > 510,000 hours - Standard Bellcore Issue 6 Method 1 Case 3 @ 40oC MIL STD 217F @ 30oC Warranty 5 years General Protection/ Safety Protected against continuous short-circuit, overload, open-circuit. Protection Class 1 (IEC536), degree of protection IP20 (IEC 529) Safe low voltage: SELV (acc. EN60950) Status Indicators Green LED and DC OK signal (N.O. Solid State Contact rated 200 mA / 60 Vdc) Installation Fusing -Input Internally fused. External 10 A slow acting fusing for the input is recommended to protect input wiring. -Output Outputs are capable of providing high currents for short periods of time for inductive load startup or switching. Fusing may be required for wire/loads if 2x Nominal O/P current rating cannot be tolerated. Continuous current overload allows for reliable fuse tripping. Mounting Simple snap-on system for DIN Rail TS35/7.5 or TS35/15 or chassis-mounted (optional screw mounting set SDN-PMBRK2 required). Connections Input: IP20-rated screw terminals, connector size range: 16-10 AWG (1.5-6 mm2) for solid conductors. 16-12 AWG (0.5-4 mm2) for flexible conductors. Output: Two connectors per output, connector size range: 16-10 AWG (1.5 - 6 mm2) for solid conductors. Case Fully enclosed metal housing with fine ventilation grid to keep out small parts. -Free Space 25 mm above and below, 25 mm left and right, 10 mm in front 25 mm above and below, 25 mm left and right, 15 mm in front 70 mm above and below, 25 mm left and right, 15 mm in front H x W x D (inches/mm) 4.88. x 1.97 x 4.55 (124 x 50 x 116) 4.88 x 2.56 x 4.55 (124 x 65 x 116) 4.88 x 3.26 x 4.55 (124 x 83 x 116) 4.88 x 6.88 x 4.55 (124 x 175 x 116) 1. Not UL listed for DC input. 2. Input current ratings are conservatively specified with low input, worst case efficiency and power factor. 3. Losses are heat dissipation in watts at full load, nominal input line. 4. Ripple/noise is stated as typical values when measured with a 20 MHz, bandwidth scope and 50 Ohm resistor. 5. Full load, 100 Vac Input @ Tamb = +25°C Ï DEMK0 06 ATEX 05 21715U
Visit our website at www.solahd.com or contact Technical Services at (800) 377-4384 with any questions.108
4 Power Supplies
SDN-P Specifications (Single Phase), 12 Vdc and 48 Vdc Output Description Catalog Number SDN 9-12-100P SDN 5-48-100P SDN 16-12-100P Input Nominal Voltage 115/230 Vac auto select -AC Range 85-132/176-264 Vac -DC Range1 210-375 Vdc -Frequency 47-63 Hz, 400 Hz -Inrush current max. Typ. < 20 A typ. < 40 A Power Factor Correction Units fulfill EN61000-3-2 Output Tolerance < ±2 % overall (combination Line, load, time and temperature related changes) -Line Regulation < 0.5% -Load Regulation < 0.5% -Time & Temp. Drift < 1% Ripple3 < 50 mVpp Overvoltage Protection < 16 Vdc with auto-recovery < 60 Vdc with auto-recovery < 16 Vdc with auto-recovery Nominal Current 9 A (108 W) 5 A (240 W) 16 A (192 W) -Current Limit4 110% of nominal - Fold Forward (Current rises, voltage drops to maintain constant power during overload up to max peak current) Holdup T ime5 >20 ms (Full load, 100 Vac Input @ Tamb=+25°C) to 95% output Voltage Parallel Operation Supplies will not be damaged with parallel operation Power Back Immunity 16 Vdc 60 Vdc 16 Vdc General EMC: -Emissions EN61000-6-3, EN61204-3, EN55022 Class B, EN61000-3-2, EN61000-3-3 -Immunity EN61000-6-2, EN61204-3, EN55024, IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8, IEC61000-4-11 Approvals UL508 Listed, cULus; UL 60950-1, cURus; CE (LVD 73/23 & 93/68/EEC), (EMC 89/336 & 93/68/EEC). EN61000-3-2; UL 60079-15 pending (Class 1, Zone 2 hazardous location, Groups IIA, IIB, IIC w/ T3 temp. class up to 60°C Ambient.); EN60079-15 (ATEX); SEMI F47 Sag Immunity, RoHS Temperature Storage: -25 to +85 oC, Operation -10 to +60oC full power; with linear derating to half power from 60 to 70oC (Convection cooling, no forced air required). Operation up to 50% load permissible with sideways or front side up mounting orientation. Humidity < 90% RH, non-condensing; IEC 68-2-2, 68-2-3 MTBF: >500,000 hrs - Standard Telcordia/Bellcore, Issue Case 3 @25oC Warranty 5 years General Protection/Safety Protected against continuous short -circuit, continuous overload, continuous open circuit. Protection Class 1 (IEC536), Degree of Protection IP20 (IEC 529) Safe low voltage: SELV (acc. EN60950) Status Indicators (Visual) Green LED on when V out > 75% (with ± 5% tolerance) of nominal output voltage Status Indicators (Relay) Normally Open solid state relay - signal active when Vout >70% of nominal output voltage (rated up to 200 mA, 60 Vdc) Installation Fusing -Input Internally fused -Output Outputs are capable of providing high currents for short periods of time for inductive load startup or switching. Fusing may be required if Nominal O/P current rating cannot be tolerated. Continuous current overload allows for reliable fuse tripping. Mounting Simple snap-on to DIN TS35/7.5 or TS35/15 rail system. Unit should handle normal shock and vibration of industrial use and transportation without falling off the rail. Connections Input: Screw terminals, connector size range: 16-10 AWG (1.5-6mm 2) for solid conductors. Output: Two terminals per output, connector size range: 16-10 AWG (1.5-6mm2) for solid conductors. Case Fully enclosed metal housing with fine ventilation grid to keep out small parts. -Free Space 70 mm above and below, 25 mm left and right, 15mm in front Weight (lbs/kg) 2.4 (1.05) 3.3 (1.48) 1. Input current ratings are specified with low input, line conditions and worst case efficiency values. Input current at nominal input settings will be typically half these values. 2. Losses are heat dissipation in watts at full load, nominal line. 3. Ripple/ noise is stated as typical values when measured with a 20 MHz bandwidth scope and 50 Ohm resister. Ï DEMK0 06 ATEX 05 21715U 4. Unit shall not shutdown or ‘hiccup’ during overload or short circuit. Maximum current value shown shall be maintained indefinitely without damage to the supply. Voltage shall drop according to amount of overload to protect supply from damage.
Visit our website at www.solahd.com or contact Technical Services at (800) 377-4384 with any questions. 109 4Power Supplies SDN 5-24-480 SDN 10-24-480 SDN 20-24-480C SDN 30-24-480 SDN 40-24-480 Input Nominal Voltage 1Ø or 3Ø 380-480 Vac 1Ø or 3Ø 380 - 480 Vac1 3Ø 380 - 480 Vac -AC Range 340 - 576 Vac -DC Range2 450 - 820 Vdc -Frequency 47 - 63 Hz -Inrush current max. typ. < 18 A typ. < 30 A Efficiency (Losses4) > 90% typ. (12 W) > 90% typ. (48 W) > 90% typ. (72 W) > 90% typ. (96 W) Power Factor Correction Units Fulfill EN61000-3-2 Output Nominal Voltage 24 Vdc (22.5 - 28.5 Vdc adj.) -Tolerance < ±2% overall (combination Line, load, time and temperature related changes) -Ripple5 < 50 mVpp Overvoltage Protection > 30 Vdc, but < 33 Vdc, auto recovery Nominal Current 5 A (120 W) 10 A (240 W) 20 A (480 W) 30 A (720 W) 40 A (960 W) -Peak Current 6A, 2x Nominal Current < 2 sec. 12A, 2x Nominal Current < 2 sec. 25A, 2x Nominal Current < 2 sec. 35A, 2x Nominal Current < 2 sec. 45A, 2x Nominal Current < 2 sec -Current Limit Fold Forward (Current rises, voltage drops to maintain constant power during overload up to max peak current) Holdup Time6 > 40 ms > 28 ms > 20 ms Parallel Operation 5A through 30A units may be passively paralleled by selecting the “P” position of the switch on the unit. The SDN 40 contains active current balancing. General EMC: -Emissions EN61000-6-3, -4; Class B EN55011, EN55022 Radiated and Conducted including Annex A. -Immunity EN61000-6-1, -2; EN61000-4-2 Level 4, EN61000-4-3 Level 3; EN61000-4-6 Level 3; EN61000-4-4 Level 4 input and Level 3 output; EN61000-4-5 Isolation Class 4, EN61000-4-11; Approvals CB Scheme, EN60950; UL508 Listed, cULus; UL60950, cRUus, CE (LVD 73/23 & 93/68/EEC). EN61000-3-2, UL60079-15 Class 1, Zone 2 Hazardous Location, Groups IIA, IIB, IIC w/T3 temp class up to 60°C Ambient. Temperature Storage: -25°C...+85°C Operation. -10°C -60°C full power with operation to 70°C possible with a linear derating to half power from 60°C to 70°C (Convection cooling, no forced air required). Operation up to 50% load permissible with sideways or front side up mounting orientation. The relative humidity is < 90% RH, noncondensing; IEC 68-2-2, 68-2-3. MTBF: > 1,110,000 hours > 940,000 hours > 550,000 hours > 620,000 hours > 490,000 hours - Standard MIL STD 217F @ 30oC Warranty 5 years General Protection/ Safety Protected against continuous short-circuit, overload, open-circuit. Protection Class 1 (IEC536), degree of protection IP20 (IEC 60529) Safe low voltage: SELV (acc. EN60950) Status Indicators Green LED on when V out = 18V or greater. Installation Fusing -Input Internally fused -Output Outputs are capable of providing high currents for short periods of time for inductive load startup or switching. Fusing may be required for wire/loads if 2x Nominal O/P current rating cannot be tolerated. Continuous current overload allows for reliable fuse tripping. Mounting Simple snap-on system for DIN Rail TS35/7.5 or TS35/15 or chassis-mounted (optional screw mounting set SDN-PMBRK2 required). Connections 7 Input: IP20-rated screw terminals, connector size range: 16-10 AWG (1.5-6 mm2) for solid conductors. 16-12 AWG (0.5-4 mm2) for flexible conductors. Output: Two connectors per output, connector size range: 16-10 AWG (1.5-6 mm2) for solid conductors. Case Fully enclosed metal housing with fine ventilation grid to keep out small parts. -Free Space 25 mm above and below, 25 mm left and right, 15 mm in front 70 mm above and below, 25 mm left and right , 15 mm in front H x W x D (inches/mm) 4.88 x 2.91 x 4.55 (124 x 73 x 116) 4.88 x 3.5 x 4.55 (124 x 89 x 116) 4.88 x 5.9 x 4.55 (124 x 150 x 116) 4.88 x 9.72 x 4.55 (124 x 247 x 116) 4.88 x 11.1 x 4.55 (124 x 282 x 116) 1. For the SDN 20-24-480C, single phase input is permissible, but output is derated to 75% (15 Amps @ 24 Vdc). 2. Not UL listed for DC input. 3. Input current ratings are conservatively specified with low input, worst case efficiency and power factor. SDN-P Specifications (Three Phase) 4. Losses are heat dissipation in watts at full load, nominal input line. 5. Ripple/noise is stated as typical values when measured with a 20 MHz, bandwidth scope and 50 Ohm resistor. 6. Full load, 100 Vac Input @ T amb = +25°C 7. For the SDN 40-24-480, output: one (+) two (-) connectors, size range 16-5 AWG (1.5016 mm2) solid conductor.
Visit our website at www.solahd.com or contact Technical Services at (800) 377-4384 with any questions.110 115/230 VAC 1.3-0.7A50/60 HZ ).$ #/.4 %1 US LISTED Power Supply SDN 2.5-24-100P SOL A Parallel Single C LU LN 24 VDC/2 .5 A + + NEC Class2 Power Supply OK - - OK SDN-P Series Dimensions W D H Catalog Number Dimensions - inches (mm) H W D
12 Vdc
SDN 9-12-100P 4.88 (124) 2.56 (65) 4.55 (116) SDN 16-12-100P 4.88 (124) 3.26 (83) 4.55 (116) SDN 4-24-100LP 4.88 (124) 2.56 (65) 4.55 (116) SDN 5-24-100P 4.88 (124) 2.56 (65) 4.55 (116) SDN 5-24-480 4.88 (124) 2.91 (73) 4.55 (116) SDN 10-24-100P 4.88 (124) 3.26 (83) 4.55 (116) SDN 20-24-100P 4.88 (124) 6.88 (175) 4.55 (116)
48 Vdc
SDN 5-48-100P 4.88 (124) 3.26 (83) 4.55 (116) H W D SOL A SDN 20-24-480C Power Supply Electronically protected
24 VDC/2 0A
Output: L1 L2 +L3 + - - 24- 28V OKOverload Fuse M ode Continuous M ode3PH 380/500 VAC 1.7/1.5A/Phase 50/60 Hz Input: Single Use ParallelUse Resetfuse m ode ).$ #/.4 %1 US LISTED UC L Catalog Number Dimensions - inches (mm) H W D SDN 10-24-480 4.88 (124) 5.90 (150) 4.55 (116) SDN 30-24-480 4.88 (124) 9.72 (247) 4.55 (116) SDN 40-24-480 4.88 (124) 11.10 (282) 4.55 (116)
Visit our website at www.solahd.com or contact Technical Services at (800) 377-4384 with any questions. 111 4Power Supplies SDN-P Series Mounting DIN Rail Mounting Snap on the DIN Rail: 1. Tilt unit slightly backwards 2. Put it onto the DIN Rail 3. Push downwards until stopped 4. Push at the lower front edge to lock 5. Shake the unit slightly to ensure that the retainer has locked Alternative Panel Mount: Using the optional SDN-PMBRK2 accessory, the unit can be screw mounted to a panel. Detachment from DIN Rail: Chassis Mounting Instead of snapping a Sola SDN™ unit on the DIN Rail, you can also attach it using the screw mounting set SDN-PMBRK2. This set consists of two metal brackets, which replace the existing two aluminum profiles. Dimensions