Features

 Compatible with the Gamewell-FCI 600 Series analog addressable FACPs.  Supervises and operates notification appliance circuit.  Supervises DC power-in.  LED annunciates activation.  Fully supervised.  Surface or flush mounting.  Field programmable.  Style four, six, or seven wiring.  Screw terminals for field wiring connections.  2.0 A output.. CS-2064ph1.wmf SCE-95

12 Clintonville Road, Northford, CT 06472-1610 USA  Tel: (203) 484-7161  Fax: (203) 484-7118

CS-2047 Rev. A page 2 of 2 www.gamewell-fci.com Programming All other programming is accomplished at the Fire Alarm Control Panel (FACP), either through a laptop computer or the control panel operator’s display. Mounting The SCE-95 is designed to mount in a standard 4.688" (11.908 cm) electrical backbox. The SCE-95 should be mounted in an easily accessible location of proper connec- tion and activation. Engineer’s Specifications A programmable electronic device shall be provided for the remote control of notification appliances. The device shall communicate with the main FACP via the SLC circuit. It shall supervise its notification appliance circuit and include an LED for circuit activation annunciation. It shall be Gamewell-FCI SCE-95. Specifications P+, P- Power: 20-24 VDC from listed supply. Standby Current: 0.0005 A. Alarm Current: 0.0015 A. Operating Temperature: 0° C to 49° C (32°F to 120°F). Relative Humidity: 85% non-condensing. Housing Requirements: 4.688" (11.908 cm) backbox. Output Rating: 0.2 Amp DC signal circuit. Auxiliary input Power:24 VDC signalling power.

Ordering Information

SCE-95 Signal control element device. XP95 protocol compatible. 70839 Trim ring for flush mounting the SCE-95. SCD Optional signal control display; provides annunciation of the SCE-95 dontrol element devices at the FACP . One needed for every eight SCEs. Compatible only with the IF632 and IF650 FACPs.